Wire Size for 70, 80 and 90 Amp Breakers: 4 to 2 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

At 60 °C terminals or in NM cable, a 70 A breaker takes 4 AWG copper, an 80 A breaker 3 AWG and a 90 A breaker 2 AWG. Where every termination is listed and identified for 75 °C conductors, the three take 4 AWG, 4 AWG and 3 AWG.

All three share one ground wire, 8 AWG copper or 6 AWG aluminum (Table 250.122). In this range 240.4(B) often lets a breaker protect the next size down when the load fits it.

Allowable ampacity, NEC Table 310.16, of the sizes around 70, 80, 90 A in the 60 °C and 75 °C columns: 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 2 AWG copper 95 A at 60 °C, 115 A at 75 °C; 1 AWG copper 110 A at 60 °C, 130 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C; 2 AWG aluminum 75 A at 60 °C, 90 A at 75 °C; 1 AWG aluminum 85 A at 60 °C, 100 A at 75 °C; 1/0 AWG aluminum 100 A at 60 °C, 120 A at 75 °C; 2/0 AWG aluminum 115 A at 60 °C, 135 A at 75 °C. 70 A takes 4 AWG copper at 60 °C and 4 AWG at 75 °C; 80 A takes 3 AWG copper at 60 °C and 4 AWG at 75 °C; 90 A takes 2 AWG copper at 60 °C and 3 AWG at 75 °C60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations70 A80 A90 A20 A40 A60 A80 A100 A120 A140 AAmpacity (size on the left)Copper8 AWG40 A50 A6 AWG55 A65 A4 AWG70 A85 A3 AWG85 A100 A2 AWG95 A115 A1 AWG110 A130 AAluminum6 AWG40 A50 A4 AWG55 A65 A3 AWG65 A75 A2 AWG75 A90 A1 AWG85 A100 A1/0 AWG100 A120 A2/0 AWG115 A135 AAllowable ampacity, NEC Table 310.16, of the sizes around 70, 80, 90 A in the 60 °C and 75 °C columns: 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 2 AWG copper 95 A at 60 °C, 115 A at 75 °C; 1 AWG copper 110 A at 60 °C, 130 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C; 2 AWG aluminum 75 A at 60 °C, 90 A at 75 °C; 1 AWG aluminum 85 A at 60 °C, 100 A at 75 °C; 1/0 AWG aluminum 100 A at 60 °C, 120 A at 75 °C; 2/0 AWG aluminum 115 A at 60 °C, 135 A at 75 °C. 70 A takes 4 AWG copper at 60 °C and 4 AWG at 75 °C; 80 A takes 3 AWG copper at 60 °C and 4 AWG at 75 °C; 90 A takes 2 AWG copper at 60 °C and 3 AWG at 75 °C60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations70 A80 A90 A50 A90 A130 AAmpacity (size on the left)Copper8 AWG6 AWG4 AWG3 AWG2 AWG1 AWGAluminum6 AWG4 AWG3 AWG2 AWG1 AWG1/0 AWG2/0 AWG
The ampacity of the sizes from 8 AWG copper up, in the 60 °C column (open dots) and the 75 °C column (filled), against the three breakers. A size answers a rating when its dot for the column in use reaches the line.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).

Wire by breaker, 70 A to 90 A

110.14(C)(1)(a) starts circuits of 100 A or less from the 60 °C column of Table 310.16, which is also where NM cable stays; the 75 °C column applies only where the breaker, the panel and every device are listed and identified for 75 °C conductors. The table gives the smallest size that reaches each rating in each column.

Smallest size that reaches the breaker rating, Table 310.16

BreakerCu 60 °CCu 75 °CAl 60 °CAl 75 °C
70 A4 AWG4 AWG2 AWG3 AWG
80 A3 AWG4 AWG1 AWG2 AWG
90 A2 AWG3 AWG1/0 AWG2 AWG

Two sizes answer two ratings each: 4 AWG copper carries 85 A at 75 °C, enough for 70 A and 80 A, and 2 AWG aluminum carries 90 A, enough for 80 A and 90 A.

One size smaller under 240.4(B)

Where a conductor's ampacity is not a standard rating of Table 240.6(A), 240.4(B) lets the next higher standard rating protect it, up to 800 A, provided it is not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads. Between 70 A and 90 A it applies often, because several sizes here carry ampacities that fall between standard ratings. The load must still fit the smaller wire: the noncontinuous load plus 125 % of the continuous load (210.19(A) for a branch circuit, 215.2(A) for a feeder).

Sizes a breaker may protect under 240.4(B), with the load they carry

BreakerSizeColumnAmpacityContinuous load up to
70 A3 AWG Al60 °C65 A52 A
70 A6 AWG Cu75 °C65 A52 A
70 A4 AWG Al75 °C65 A52 A
80 A2 AWG Al60 °C75 A60 A
80 A3 AWG Al75 °C75 A60 A
90 A3 AWG Cu60 °C85 A68 A
90 A1 AWG Al60 °C85 A68 A
90 A4 AWG Cu75 °C85 A68 A

ChargePoint's 50 A setting on a 70 A breaker

ChargePoint's instructions put its 50 A setting on a 70 A breaker, hardwired. 625.41 asks for a breaker of at least 125 % of the output, and the wire must carry 62.5 A too. 6 AWG copper at 75 °C carries 65 A: enough for the load, and a 70 A breaker may protect it under 240.4(B). In NM cable the answer is 4 AWG, at 70 A. The EV charger wire guide covers the other outputs.

Feeders to a subpanel or a detached building

A feeder to a separate building runs four wires: two hots, the neutral and an equipment grounding conductor, and at that building the neutral stays off the grounding conductor and the electrode (250.32(B)(1)). The grounding conductor is 8 AWG copper or 6 AWG aluminum for all three ratings, from the row of Table 250.122 for breakers up to 100 A.

225.39 sets the least rating of that building's disconnecting means: 60 A for a garage or other building, which any of these feeders exceeds, but 100 A for a one-family dwelling, more than the feeder that supplies it. The garage subpanel calculator sizes these feeders and gives the burial depth.

How far each rating goes at 240 V

An informational note to 215.2(A) says feeders sized to keep the drop under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. The table gives the one-way length at which each answer reaches it at the full rating, single-phase at 240 V with the conductors at 75 °C.

One-way length to a 3 % drop at full load, ft

BreakerCu 60 °CCu 75 °CAl 60 °CAl 75 °C
70 A170 ft170 ft164 ft130 ft
80 A188 ft149 ft181 ft144 ft
90 A210 ft167 ft203 ft128 ft
Voltage drop of a 80 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 3 AWG copper 4.79 %, 1 AWG aluminum 4.96 %, 4 AWG copper 6.04 %, 2 AWG aluminum 6.26 %3 AWG copper, 60 °C1 AWG aluminum, 60 °C4 AWG copper, 75 °C2 AWG aluminum, 75 °C036912050100150200250300One-way length, ft (drop in % on the left)3 %: the feeder noteVoltage drop of a 80 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 3 AWG copper 4.79 %, 1 AWG aluminum 4.96 %, 4 AWG copper 6.04 %, 2 AWG aluminum 6.26 %3 AWG copper, 60 °C1 AWG aluminum, 60 °C4 AWG copper, 75 °C2 AWG aluminum, 75 °C0369120100200300One-way length, ft (drop in % on the left)3 %: the feeder note
Voltage drop of an 80 A circuit at full load, single-phase at 240 V, against one-way length: the 60 °C sizes as solid lines, the 75 °C sizes dashed, with the 215.2(A) note's 3 %.

Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

The wire size calculator finds the size for your length and load and grows the ground wire with it (250.122(B)).

Ampacity of the sizes in this range

Both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.

Copper: Table 310.16 ampacity, A

Size60 °C75 °C
8 AWG40 A50 A
6 AWG55 A65 A
4 AWG70 A85 A
3 AWG85 A100 A
2 AWG95 A115 A
1 AWG110 A130 A

Aluminum: Table 310.16 ampacity, A

Size60 °C75 °C
6 AWG40 A50 A
4 AWG55 A65 A
3 AWG65 A75 A
2 AWG75 A90 A
1 AWG85 A100 A
1/0 AWG100 A120 A
2/0 AWG115 A135 A

Questions

What size wire for 70 A?

4 AWG copper or 2 AWG aluminum at 60 °C terminals or in NM cable; 4 AWG copper or 3 AWG aluminum where every termination is listed and identified for 75 °C conductors.

What size wire for 80 A?

3 AWG copper or 1 AWG aluminum at 60 °C terminals or in NM cable; 4 AWG copper or 2 AWG aluminum where every termination is listed and identified for 75 °C conductors.

What size wire for 90 A?

2 AWG copper or 1/0 AWG aluminum at 60 °C terminals or in NM cable; 3 AWG copper or 2 AWG aluminum where every termination is listed and identified for 75 °C conductors.

Can 6 AWG copper go on a 70 A breaker?

With 75 °C terminations, under 240.4(B), when the load fits its 65 A. At 60 °C or in NM cable it carries less, and 4 AWG is the answer.

What size wire for an 80 A subpanel?

3 AWG copper or 1 AWG aluminum at 60 °C, 4 AWG copper or 2 AWG aluminum at 75 °C, with an 8 AWG copper ground wire and four wires to a detached building.

What size ground wire for 70 A to 90 A?

8 AWG copper or 6 AWG aluminum for all three, larger in proportion if the circuit wires are upsized for distance (250.122(B)).

Sources

The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.