Wire Size for 70, 80 and 90 Amp Breakers: 4 to 2 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
At 60 °C terminals or in NM cable, a 70 A breaker takes 4 AWG copper, an 80 A breaker 3 AWG and a 90 A breaker 2 AWG. Where every termination is listed and identified for 75 °C conductors, the three take 4 AWG, 4 AWG and 3 AWG.
All three share one ground wire, 8 AWG copper or 6 AWG aluminum (Table 250.122). In this range 240.4(B) often lets a breaker protect the next size down when the load fits it.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).
Wire by breaker, 70 A to 90 A
110.14(C)(1)(a) starts circuits of 100 A or less from the 60 °C column of Table 310.16, which is also where NM cable stays; the 75 °C column applies only where the breaker, the panel and every device are listed and identified for 75 °C conductors. The table gives the smallest size that reaches each rating in each column.
Smallest size that reaches the breaker rating, Table 310.16
| Breaker | Cu 60 °C | Cu 75 °C | Al 60 °C | Al 75 °C |
|---|---|---|---|---|
| 70 A | 4 AWG | 4 AWG | 2 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 1 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 1/0 AWG | 2 AWG |
Two sizes answer two ratings each: 4 AWG copper carries 85 A at 75 °C, enough for 70 A and 80 A, and 2 AWG aluminum carries 90 A, enough for 80 A and 90 A.
One size smaller under 240.4(B)
Where a conductor's ampacity is not a standard rating of Table 240.6(A), 240.4(B) lets the next higher standard rating protect it, up to 800 A, provided it is not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads. Between 70 A and 90 A it applies often, because several sizes here carry ampacities that fall between standard ratings. The load must still fit the smaller wire: the noncontinuous load plus 125 % of the continuous load (210.19(A) for a branch circuit, 215.2(A) for a feeder).
Sizes a breaker may protect under 240.4(B), with the load they carry
| Breaker | Size | Column | Ampacity | Continuous load up to |
|---|---|---|---|---|
| 70 A | 3 AWG Al | 60 °C | 65 A | 52 A |
| 70 A | 6 AWG Cu | 75 °C | 65 A | 52 A |
| 70 A | 4 AWG Al | 75 °C | 65 A | 52 A |
| 80 A | 2 AWG Al | 60 °C | 75 A | 60 A |
| 80 A | 3 AWG Al | 75 °C | 75 A | 60 A |
| 90 A | 3 AWG Cu | 60 °C | 85 A | 68 A |
| 90 A | 1 AWG Al | 60 °C | 85 A | 68 A |
| 90 A | 4 AWG Cu | 75 °C | 85 A | 68 A |
ChargePoint's 50 A setting on a 70 A breaker
ChargePoint's instructions put its 50 A setting on a 70 A breaker, hardwired. 625.41 asks for a breaker of at least 125 % of the output, and the wire must carry 62.5 A too. 6 AWG copper at 75 °C carries 65 A: enough for the load, and a 70 A breaker may protect it under 240.4(B). In NM cable the answer is 4 AWG, at 70 A. The EV charger wire guide covers the other outputs.
Feeders to a subpanel or a detached building
A feeder to a separate building runs four wires: two hots, the neutral and an equipment grounding conductor, and at that building the neutral stays off the grounding conductor and the electrode (250.32(B)(1)). The grounding conductor is 8 AWG copper or 6 AWG aluminum for all three ratings, from the row of Table 250.122 for breakers up to 100 A.
225.39 sets the least rating of that building's disconnecting means: 60 A for a garage or other building, which any of these feeders exceeds, but 100 A for a one-family dwelling, more than the feeder that supplies it. The garage subpanel calculator sizes these feeders and gives the burial depth.
How far each rating goes at 240 V
An informational note to 215.2(A) says feeders sized to keep the drop under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. The table gives the one-way length at which each answer reaches it at the full rating, single-phase at 240 V with the conductors at 75 °C.
One-way length to a 3 % drop at full load, ft
| Breaker | Cu 60 °C | Cu 75 °C | Al 60 °C | Al 75 °C |
|---|---|---|---|---|
| 70 A | 170 ft | 170 ft | 164 ft | 130 ft |
| 80 A | 188 ft | 149 ft | 181 ft | 144 ft |
| 90 A | 210 ft | 167 ft | 203 ft | 128 ft |
Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
The wire size calculator finds the size for your length and load and grows the ground wire with it (250.122(B)).
Ampacity of the sizes in this range
Both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.
Copper: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 8 AWG | 40 A | 50 A |
| 6 AWG | 55 A | 65 A |
| 4 AWG | 70 A | 85 A |
| 3 AWG | 85 A | 100 A |
| 2 AWG | 95 A | 115 A |
| 1 AWG | 110 A | 130 A |
Aluminum: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 6 AWG | 40 A | 50 A |
| 4 AWG | 55 A | 65 A |
| 3 AWG | 65 A | 75 A |
| 2 AWG | 75 A | 90 A |
| 1 AWG | 85 A | 100 A |
| 1/0 AWG | 100 A | 120 A |
| 2/0 AWG | 115 A | 135 A |
Questions
What size wire for 70 A?
4 AWG copper or 2 AWG aluminum at 60 °C terminals or in NM cable; 4 AWG copper or 3 AWG aluminum where every termination is listed and identified for 75 °C conductors.
What size wire for 80 A?
3 AWG copper or 1 AWG aluminum at 60 °C terminals or in NM cable; 4 AWG copper or 2 AWG aluminum where every termination is listed and identified for 75 °C conductors.
What size wire for 90 A?
2 AWG copper or 1/0 AWG aluminum at 60 °C terminals or in NM cable; 3 AWG copper or 2 AWG aluminum where every termination is listed and identified for 75 °C conductors.
Can 6 AWG copper go on a 70 A breaker?
With 75 °C terminations, under 240.4(B), when the load fits its 65 A. At 60 °C or in NM cable it carries less, and 4 AWG is the answer.
What size wire for an 80 A subpanel?
3 AWG copper or 1 AWG aluminum at 60 °C, 4 AWG copper or 2 AWG aluminum at 75 °C, with an 8 AWG copper ground wire and four wires to a detached building.
What size ground wire for 70 A to 90 A?
8 AWG copper or 6 AWG aluminum for all three, larger in proportion if the circuit wires are upsized for distance (250.122(B)).
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- Tesla, ChargePoint and Emporia installation instructions (as linked) — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 625, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.