Wire Size for 50 Amp Breaker: 6 or 8 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 50 A breaker takes 6 AWG copper or 4 AWG aluminum from the 60 °C column of NEC Table 310.16, the column for NM cable and for terminals rated 60 °C. Where the breaker and every other termination are listed and identified for 75 °C conductors, single conductors of 8 AWG copper or 6 AWG aluminum are enough.

The ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122). In NM cable, 8 AWG copper carries only 40 A, which is why the cable answer is 6 AWG.

Allowable ampacity, NEC Table 310.16, of the sizes around 50 A in the 60 °C and 75 °C columns: 10 AWG copper 30 A at 60 °C, 35 A at 75 °C; 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 8 AWG aluminum 35 A at 60 °C, 40 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C. A 50 A breaker needs a size that reaches 50 A in the column its terminations allow: 6 AWG copper or 4 AWG aluminum at 60 °C, 8 AWG copper or 6 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations50 A breaker20 A30 A40 A50 A60 A70 A80 A90 AAmpacity (size on the left)Copper10 AWG30 A35 A8 AWG40 A50 A6 AWG55 A65 A4 AWG70 A85 AAluminum8 AWG35 A40 A6 AWG40 A50 A4 AWG55 A65 A3 AWG65 A75 AAllowable ampacity, NEC Table 310.16, of the sizes around 50 A in the 60 °C and 75 °C columns: 10 AWG copper 30 A at 60 °C, 35 A at 75 °C; 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 8 AWG aluminum 35 A at 60 °C, 40 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C. A 50 A breaker needs a size that reaches 50 A in the column its terminations allow: 6 AWG copper or 4 AWG aluminum at 60 °C, 8 AWG copper or 6 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations50 A breaker30 A50 A70 A90 AAmpacity (size on the left)Copper10 AWG8 AWG6 AWG4 AWGAluminum8 AWG6 AWG4 AWG3 AWG
The ampacity of the sizes around 50 A in the 60 °C column (open dots) and the 75 °C column (filled). 8 AWG copper reaches 50 A only in the 75 °C column; 6 AWG copper passes it in both.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).

6 or 8 AWG: the terminals decide

Under 110.14(C), the temperature rating used for a conductor's ampacity may not exceed that of any termination, conductor or device it connects to. For circuits rated 100 A or less, 110.14(C)(1)(a) starts from the 60 °C column. Conductors with a higher rating may be used, but at their 60 °C ampacity, unless the equipment is listed and identified for use with the higher-rated conductors.

That splits the 50 A answer. 8 AWG copper carries 40 A at 60 °C and 50 A at 75 °C, so it works only where the breaker, the panel and every device on the circuit are listed and identified for 75 °C conductors. 6 AWG copper carries 55 A at 60 °C and needs no such check. In aluminum the pair is 6 AWG (50 A at 75 °C) and 4 AWG (55 A at 60 °C).

THHN is rated 90 °C, and Table 310.16 gives 8 AWG copper 55 A in that column. Under 110.14(C) the circuit still uses the column of its terminals.

Wire for a 50 A breaker, by wiring method

WiringCopperAluminum
NM cable, or terminals rated 60 °C6 AWG4 AWG
Single conductors, every termination listed and identified for 75 °C8 AWG6 AWG
Ground wire, Table 250.12210 AWG8 AWG

For a run through a hot attic, or more than three current-carrying wires in one conduit, the wire size calculator opens on this breaker and applies the corrections.

NM cable on a 50 A breaker

NM cable stays in the 60 °C column whatever its terminations: 334.80 holds its ampacity to that of a 60 °C conductor. Its 90 °C rating may be the starting point for temperature and bundling corrections, but the result may not exceed the 60 °C value.

So 50 A in NM cable means 6 AWG copper, which carries 55 A. 8 AWG cable carries 40 A, and since that is itself a standard rating in Table 240.6(A), the next-size-up allowance of 240.4(B), which covers only ampacities that fall between standard ratings, does not reach 50 A.

A 50 A outlet

Three NEMA receptacles carry a 50 A rating. They differ in voltage and in the wires that land on them, and the older 10-50R has no ground. Behind any of them the wire is the circuit's: 6 AWG copper in NM cable.

The 50 A receptacles

ReceptacleVoltsWires
14-50R125/250 V4: two hots, a neutral and a ground
6-50R250 V3: two hots and a ground
10-50R125/250 V3: two hots, a neutral, no ground
  • Whirlpool's freestanding electric ranges take a 4-wire cord on a 14-50R, or a 3-wire cord on a 10-50R only where local codes permit. The range calculator works out a range's load from its rating.
  • An RV's 50 A outlet is a 14-50R; the RV hookup calculator sizes it for your run.
  • An EV charger set to a 40 A output goes on a 50 A breaker, because 625.41 calls for a breaker of at least 125 % of the output. The EV charger wire guide covers plug-in and hardwired chargers.
  • Hot Spring, Bullfrog and Marquis each list a 50 A circuit at 240 V for their hot tubs, run with four wires. The hot tub calculator sizes it.
  • Lincoln's AC-225C welder plugs into a 6-50R. The welder calculator sizes a welder's circuit from its own input current.

A 50 A subpanel or service

A 50 A feeder to a subpanel is sized the same way, from Table 310.16 at the column its terminations allow: 6 AWG copper or 4 AWG aluminum at 60 °C, 8 AWG copper or 6 AWG aluminum at 75 °C. Table 310.12, for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit, starts at 100 A, so it has no 50 A row.

A feeder to a separate building, such as a detached garage or shop, runs four wires: two hots, the neutral and an equipment grounding conductor (250.32(B)(1)). At that building the neutral is not connected to the equipment grounding conductor or to the grounding electrode.

The building gets its own disconnecting means (225.31), and 225.39 sets its least rating: 60 A for a garage or other building, more than the 50 A feeder that supplies it, unless the building has no more than two 2-wire circuits (30 A) or a single circuit (15 A). The garage subpanel calculator sizes the feeder for other breakers and gives the burial depth.

Ground wire for 50 A

Table 250.122 sizes the equipment grounding conductor by the breaker ahead of it. A 50 A breaker falls in the row for breakers up to 60 A: 10 AWG copper or 8 AWG aluminum, whichever column sized the circuit wires. Going up a size for a long run changes that: 250.122(B) increases the ground wire in proportion to the area of the larger circuit wires. The ground wire calculator does that arithmetic.

50 A at 240 V: how far each size goes

Table 310.16 sizes a circuit for its current, not its length. At the full 50 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 6 AWG copper drops 4.81 V (2.00 %), 4 AWG aluminum 4.98 V (2.07 %), 8 AWG copper 7.64 V (3.18 %) and 6 AWG aluminum 7.92 V (3.30 %).

For feeders, an informational note to 215.2(A) says that conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. At the full rating, 8 AWG copper reaches 3 % at 94 ft, 6 AWG copper at 150 ft, 6 AWG aluminum at 91 ft and 4 AWG aluminum at 145 ft.

Voltage drop of a 50 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 6 AWG copper 6.01 %, 4 AWG aluminum 6.22 %, 8 AWG copper 9.55 %, 6 AWG aluminum 9.89 %6 AWG copper, 60 °C4 AWG aluminum, 60 °C8 AWG copper, 75 °C6 AWG aluminum, 75 °C036912050100150200250300One-way length, ft (drop in % on the left)3 %: the feeder noteVoltage drop of a 50 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 6 AWG copper 6.01 %, 4 AWG aluminum 6.22 %, 8 AWG copper 9.55 %, 6 AWG aluminum 9.89 %6 AWG copper, 60 °C4 AWG aluminum, 60 °C8 AWG copper, 75 °C6 AWG aluminum, 75 °C0369120100200300One-way length, ft (drop in % on the left)3 %: the feeder note
Voltage drop of a 50 A circuit at full load, single-phase at 240 V, against one-way length: the 60 °C sizes as solid lines, the 75 °C sizes dashed, with the 215.2(A) note's 3 %.

Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

SizeLength
8 AWG94 ft
6 AWG150 ft
4 AWG238 ft
3 AWG300 ft
2 AWG379 ft
1 AWG478 ft
1/0 AWG603 ft

Aluminum: one-way length to a 3 % drop, ft

SizeLength
6 AWG91 ft
4 AWG145 ft
3 AWG182 ft
2 AWG230 ft
1 AWG290 ft
1/0 AWG366 ft
2/0 AWG462 ft

The drop falls in proportion to the current, so a lighter load drops less. If you go up a size for distance, the ground wire grows with it (250.122(B)), and the wire size calculator sizes both for your length and load.

Ampacity of the sizes around 50 A

The sizes from one below the 75 °C answer to one past the 60 °C answer, with their ampacity in both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together. The AWG wire size chart gives each gauge's diameter and resistance.

Copper: Table 310.16 ampacity, A

Size60 °C75 °C
10 AWG30 A35 A
8 AWG40 A50 A
6 AWG55 A65 A
4 AWG70 A85 A

Aluminum: Table 310.16 ampacity, A

Size60 °C75 °C
8 AWG35 A40 A
6 AWG40 A50 A
4 AWG55 A65 A
3 AWG65 A75 A

Questions

What size wire for a 50 A service?

Table 310.12 starts at 100 A, so a 50 A service or feeder takes the Table 310.16 sizes: 6 AWG copper or 4 AWG aluminum at 60 °C terminals, 8 AWG copper or 6 AWG aluminum where every termination is listed and identified for 75 °C conductors.

What size wire for a 50 A subpanel 100 ft away?

At the full 50 A over 100 ft at 240 V, 6 AWG copper drops 2.00 % and 4 AWG aluminum 2.07 %, inside the 3 % of the 215.2(A) note. 8 AWG copper, allowed with 75 °C terminations, drops 3.18 %. To a detached building the feeder runs four wires.

What size ground wire for 50 A?

10 AWG copper or 8 AWG aluminum, from the 60 A row of Table 250.122, and larger in proportion when the circuit wires are upsized for distance (250.122(B)).

What wire does a 50 A outlet need?

A 14-50R takes two hots, a neutral and a ground; a 6-50R two hots and a ground. Size them like the circuit: 6 AWG copper in NM cable.

What size aluminum wire for 50 A?

4 AWG at 60 °C terminals, 6 AWG where every termination is listed and identified for 75 °C conductors, with an 8 AWG aluminum ground wire.

Can 8 AWG wire go on a 50 A breaker?

Yes, as single conductors, such as THHN in conduit, where the breaker and every other termination are listed and identified for 75 °C conductors: 8 AWG copper carries 50 A there. Not in NM cable, which holds it to 40 A.

Can 10 AWG wire go on a 50 A breaker?

Not on an ordinary circuit: 240.4(D) protects 10 AWG copper at 30 A at most. Air conditioners are the usual exception. Table 240.4(G) sends their circuits to Article 440, where the wire is sized to the nameplate's minimum circuit ampacity, so the breaker the nameplate allows can be larger than 240.4(D) would let the wire have. The air conditioner calculator applies those rules.