Conduit Fill Calculator: How Many Wires Fit, NEC Annex C

The most wires of one size that fit in each trade size of 13 kinds of conduit and tubing, from the tables in the 2023 NEC's Annex C, and the smallest trade size for the wires you need to pull.

By Marko Visic, BSc Physics · Updated · Sources below

The Annex C table for this raceway is used.

As printed on the wire.

All the conductors are this size.

Stranding
Find

Metric designator in brackets.

In EMT, 12 AWG THHN fits 9 to a trade size 1/2, 16 to a 3/4 and 26 to a 1. 14 AWG fits 12, 22 and 35; 10 AWG fits 5, 10 and 16 (NEC Annex C, Table C.1).

The counts are for conductors all of one size, and a ground wire of the same size is one of them. They follow Chapter 9, Table 1, which lets more than two conductors fill 40 % of the inside of a conduit.

Fill limits and the notes

Chapter 9, Table 1 sets how much of a conduit's cross section the conductors may take: 53 % for a single conductor, 31 % for two and 40 % for more.

NEC Chapter 9, Table 1: percent of cross section for conductors and cables

Conductors or cablesFill
One53 %
Two31 %
More than two40 %

The notes to the tables carry the rest of the rule. Equipment grounding and bonding conductors count in the fill, at their actual size, bare or insulated (Note 3). A nipple between boxes or enclosures no longer than 24 in may be filled to 60 %, and the adjustment factors of Table 310.15(C)(1) need not apply to it (Note 4). A multiconductor cable or a flexible cord counts as one conductor (Note 9). The limits apply to complete conduit systems, not to a short sleeve that only protects a cable (Note 2).

Annex C rounds a count up when the calculation ends in a decimal of 0.8 or more (Note 7), which is why some counts sit a little above a strict 40 %. An informational note to Table 1 adds a warning for three conductors: when the conduit's inside diameter is between 2.8 and 3.2 times the conductor's outside diameter, they can jam on the pull.

THHN in EMT and PVC

These are Annex C's counts for THHN, THWN and THWN-2 in EMT and in Schedule 40 PVC, trade sizes 1/2 to 2; the calculator covers every size and trade size the tables list, for all 13 raceways.

THHN, THWN, THWN-2 in electrical metallic tubing (EMT): the most conductors of one size by trade size, NEC Annex C Table C.1

Wire1/23/411-1/41-1/22
14 AWG1222356184138
12 AWG916264561101
10 AWG51016283863
8 AWG369162236
6 AWG247121626
4 AWG12471016
3 AWG1136813
2 AWG1135711
1 AWG111458
1/0 AWG111347
2/0 AWG011236
3/0 AWG011135
4/0 AWG011124

THHN, THWN, THWN-2 in rigid PVC conduit, Schedule 40, and HDPE conduit: the most conductors of one size by trade size, NEC Annex C Table C.11

Wire1/23/411-1/41-1/22
14 AWG1121346082135
12 AWG81525435999
10 AWG5915273762
8 AWG359162136
6 AWG146111526
4 AWG1247916
3 AWG1136813
2 AWG1135711
1 AWG111358
1/0 AWG111347
2/0 AWG011236
3/0 AWG011135
4/0 AWG011124

Source: NFPA 70 (NEC) 2023, Chapter 9 Table 1 and Informative Annex C, Tables C.1 to C.13(A), as NFPA's 2026-cycle records print them.

Raceway types compared

The same trade size holds different counts in different raceways, because Annex C works from each one's own inside area (Table 4). In trade size 1, Type A PVC holds the most 12 AWG THHN, 32, and Schedule 80 PVC the fewest, 20. EMT holds 26 and Schedule 40 PVC 25. Type EB PVC conduit has no trade size 1 in its table.

NEC Annex C, the most 12 AWG THHN conductors in trade size 1 of each raceway: PVC Type A 32, IMC 29, EMT 26, LFNC-B 26, LFMC 26, RMC 26, ENT 25, LFNC-A 25, LFNC-C 25, PVC Sch. 40 25, FMC 24, PVC Sch. 80 20.RacewayConductorsPVC Type A32IMC29EMT26LFNC-B26LFMC26RMC26ENT25LFNC-A25LFNC-C25PVC Sch. 4025FMC24PVC Sch. 8020NEC Annex C, the most 12 AWG THHN conductors in trade size 1 of each raceway: PVC Type A 32, IMC 29, EMT 26, LFNC-B 26, LFMC 26, RMC 26, ENT 25, LFNC-A 25, LFNC-C 25, PVC Sch. 40 25, FMC 24, PVC Sch. 80 20.RacewayConductorsPVC Type A32IMC29EMT26LFNC-B26LFMC26RMC26ENT25LFNC-A25LFNC-C25PVC Sch. 4025FMC24PVC Sch. 8020
The most 12 AWG THHN conductors in trade size 1 of each raceway, from Annex C; EMT and Schedule 40 PVC in copper.

Source: NFPA 70 (NEC) 2023, Chapter 9 Table 1 and Informative Annex C, Tables C.1 to C.13(A), as NFPA's 2026-cycle records print them.

Choosing a conduit size

Count every conductor you will pull, the ground wire included, then take the smallest trade size whose count reaches that number: the calculator's “Conduit size” does this. Four 6 AWG THHN, three hots and a ground of the same size, need trade size 3/4 in EMT, which holds 4, and 3/4 in Schedule 40 PVC, which holds 4.

A ground wire smaller than the circuit wires is a different size, which Annex C does not cover. Counting it as one more wire of the larger size errs on the safe side: it can only take up less room than that.

Compact conductors

Compact stranding presses the strands together until the gaps between them are nearly gone, so a compact conductor takes less room than a concentric one of the same size. Each raceway has a second Annex C table for compact THHN, XHHW and THW, based on Table 5A: in trade size 2 EMT, 4/0 AWG XHHW fits 4 concentric or 5 compact. The compact tables start at 8 AWG, and compact THHN at 6 AWG. Choose “Compact” in the calculator when the wire is marked compact.

Wires of different sizes

For conductors of different sizes, Note 6 sends you to the areas: each conductor's area from Table 5 (Table 5A for compact stranding), added up, against the conduit's allowed area in Table 4. This calculator does not do that yet. Its numbers all come from NFPA's own records of the 2023 code, and no NFPA record we have found prints Table 5. Until one does, size a mixed pull from those two tables in the NEC itself, or count the smaller wires as the larger size, as above.

Questions

How many 12 gauge wires fit in 3/4 EMT?

16 THHN or THWN-2, 11 XHHW and 11 THW or TW, by Annex C Table C.1.

How many 10 gauge THHN fit in 1/2 EMT?

5. Trade size 3/4 holds 10.

Does the ground wire count in conduit fill?

Yes. Note 3 to the Chapter 9 tables counts equipment grounding and bonding conductors in the fill, bare or insulated, at their actual size.

What is the 40 percent rule?

Chapter 9, Table 1: more than two conductors may fill no more than 40 % of a conduit's cross section. One conductor may fill 53 %, two 31 %.

Can a short nipple hold more wires?

Yes. A nipple of up to 24 in between boxes, cabinets or similar enclosures may be filled to 60 % of its cross section (Note 4).

Do more wires in one conduit lower their ampacity?

Yes: more than three current-carrying conductors in a raceway take the adjustment factors of Table 310.15(C)(1). The ampacity calculator applies them; a nipple filled under Note 4 is exempt.

Sources

Retrieved .

The counts are the 2023 NEC's; the NEC edition by state shows which edition applies where you live. The methodology page describes how the calculator works and its source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.