Wire Size for 30 Amp Breaker: 10 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
A 30 A breaker takes 10 AWG copper or 8 AWG aluminum, whatever the terminals. 30 A is exactly the most 240.4(D) allows on 10 AWG copper. 10 AWG aluminum carries 30 A at 75 °C, but 240.4(D) stops it at 25 A, so aluminum goes up to 8 AWG.
The ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122). At 120 V, as on an RV's TT-30R, the full 30 A drops 3 % in 49 ft of 10 AWG.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint).
10 AWG at its limit
Table 310.16 gives 10 AWG copper 30 A at 60 °C and 35 A at 75 °C. 240.4(D) then caps its breaker at 30 A, which is this rating exactly, so 10 AWG is both the smallest copper a 30 A breaker may protect and the largest breaker that 10 AWG may sit on. The terminal rating that 110.14(C) looks at changes nothing here.
Aluminum is where the limit bites: 10 AWG aluminum would reach 30 A in the 75 °C column, but 240.4(D) holds it to 25 A. A 30 A breaker takes 8 AWG aluminum, with an 8 AWG aluminum ground wire.
30 A at 240 V and at 120 V
The wire size is the same at 240 V and at 120 V, the voltage of an RV's TT-30R; the distance is not, since the same drop in volts is twice the percentage at 120 V. At the full 30 A, single-phase with the conductors at 75 °C, 10 AWG copper reaches 3 % at 99 ft on 240 V and at 49 ft on 120 V.
The 3 % is from an informational note to 215.2(A): feeders sized to keep the drop under it, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. Over 100 ft, 10 AWG drops 3.04 % at 240 V and 6.07 % at 120 V; staying within it takes 8 AWG copper (1.91 %) and 6 AWG (2.40 %).
Source: NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
Copper: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 10 AWG | 49 ft | 99 ft |
| 8 AWG | 79 ft | 157 ft |
| 6 AWG | 125 ft | 250 ft |
| 4 AWG | 199 ft | 397 ft |
Aluminum: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 8 AWG | 48 ft | 95 ft |
| 6 AWG | 76 ft | 152 ft |
| 4 AWG | 121 ft | 241 ft |
| 3 AWG | 152 ft | 304 ft |
Going up a size for distance means a larger ground wire too (250.122(B)); the wire size calculator sizes both.
The four 30 A receptacles
Four NEMA receptacles carry a 30 A rating, and they differ in voltage and in the wires that land on them. All four take the circuit's 10 AWG copper.
The 30 A receptacles
| Receptacle | Volts | Wires |
|---|---|---|
| TT-30R | 125 V | 3: one hot, a neutral and a ground |
| 6-30R | 250 V | 3: two hots and a ground |
| 10-30R | 125/250 V | 3: two hots, a neutral, no ground |
| 14-30R | 125/250 V | 4: two hots, a neutral and a ground |
- Whirlpool and GE both ask for a 30 A circuit for their electric dryers, with 10 AWG copper. Whirlpool's instructions show a 4-wire cord on a 14-30R and a 3-wire cord on a 10-30R, and say a 4-wire connection is required in homes built after 1996. The dryer calculator keeps the circuit apart from the dryer's load on a service.
- An RV's 30 A outlet is a TT-30R at 125 V; the RV hookup calculator sizes it for your run.
- An EV charger set to a 24 A output goes on a 30 A breaker, because 625.41 calls for at least 125 % of the output; the EV charger wire guide has the makers' tables.
- The 6-30R is the 250 V receptacle with two hots and a ground, for equipment with no neutral.
10 AWG on a bigger breaker
On an ordinary circuit, no: 240.4(D) protects 10 AWG copper at 30 A at most, so the next standard rating, 35 A, needs 8 AWG. Air conditioners are an exception: Table 240.4(G) sends their circuits to Article 440, where the wire follows the nameplate's minimum circuit ampacity and the breaker may be larger than 240.4(D) would allow. The air conditioner calculator applies those rules.
A 30 A feeder to a shed or garage
A 30 A feeder takes the same 10 AWG copper or 8 AWG aluminum. At the building, 225.39 sets the least rating of its disconnecting means: 30 A where the building has no more than two 2-wire circuits, and 60 A for a garage or other building with more, whatever the feeder behind it. The garage subpanel calculator sizes the feeder for larger breakers and gives the burial depth.
Questions
Is 10 AWG wire good for 30 A?
Yes, exactly: 10 AWG copper carries 30 A at 60 °C, and 240.4(D) allows a breaker up to 30 A on it.
Can I use 12 AWG wire on a 30 A breaker?
No. 240.4(D) protects 12 AWG copper at 20 A at most. Air conditioners sized under Article 440 are the exception; their nameplate sets the wire.
What size wire for a 30 A circuit at 240 V?
10 AWG copper, which takes the full 30 A 99 ft before the drop reaches 3 %.
What size wire for 30 A at 100 ft?
For the full load within 3 %: 8 AWG copper at 240 V, 6 AWG at 120 V.
What size aluminum wire for 30 A?
8 AWG aluminum. 10 AWG aluminum is held to 25 A by 240.4(D).
What size ground wire for 30 A?
10 AWG copper or 8 AWG aluminum: a 30 A breaker falls in the row for breakers up to 60 A in Table 250.122.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- Hubbell NEMA configuration chart and Hubbell and Leviton device specifications (NEMA WD 6) — retrieved Nov 2026
- manufacturer installation instructions (Whirlpool, GE, Frigidaire) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Article 625, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, 440.4(B), 440.14 and 240.4(G), as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.