Methodology: sources and formulas

By Marko Visic, BSc Physics · Updated

The calculators on wiresizes.com work from the published tables and definitions on this page. Each source has a section below: what it is and which edition was used, where it was read, how the calculators use it, and where that use stops. The first thirteen sections show how the wire size, circuit breaker, residential load, range, dryer, horsepower to amps, garage subpanel, box fill, RV hookup, well pump, hot tub, air conditioner and welder calculators work from them. Every calculator page, the AWG wire size chart, the NEC Table 310.16 page, NEC edition by state, the homepage and the calculators and guides pages also list their sources under Sources, near the bottom of the page.

Code values are from NFPA 70, the National Electrical Code (NEC), 2023 edition, unless a section says otherwise. They were read from documents NFPA publishes openly, such as its records of revisions to the code, and from reprints made with NFPA's permission; each section names its document. States and cities adopt NEC editions on their own schedules, and some amend them, so check which edition applies where the work is done.

How the wire size calculator picks a size

The wire size calculator starts from the breaker or fuse rating you choose, the conductor material, how the conductors are run and the circuit, and works in these steps:

  1. Pick the column of Table 310.16: 60 °C for NM or UF cable; for single conductors, the column 110.14(C) allows, 60 °C on circuits rated 100 A or less and 75 °C above, unless you say the terminals are marked 60 °C or listed and identified for 75 °C conductors (see Terminal temperatures).
  2. Take the smallest size whose ampacity in that column is at least the rating (see Ampacity). With an ambient other than the table's 30 °C, or more than three current-carrying conductors, the ampacity is first corrected, from the 90 °C column for single conductors, which it takes as rated 90 °C, or from the 60 °C column for cable, and then held to the size's value in the column of step 1 (see Ambient temperature and bundling).
  3. If that size is 14, 12 or 10 AWG copper, or 12 or 10 AWG aluminum, move up while the rating is above the size's 240.4(D) limit (see Small-conductor limits).
  4. With a load current marked continuous, check that the rating is at least 125 % of it, as 210.20(A) requires; a size that carries the rating then has the ampacity 210.19(A) asks of it (see Continuous loads).
  5. Take the ground wire for the rating from NEC Table 250.122, held at the conductor's size where the table lists a larger one, as 250.122(A) allows (see Ground wires).
  6. Work out the voltage drop at the load current over the one-way length, with conductor resistance at 75 °C. With no load entered, the rating is the load (see Conductor resistance).
  7. If the drop is above your target, try each larger size in Table 310.16 until it is not, up to 2000 kcmil, and enlarge the ground wire in proportion to the conductor area, as 250.122(B) requires.

Where 240.4(B) would let the rating protect the next smaller size, because that size's ampacity, corrected like the others, falls between two standard ratings with the rating the next one up, and 240.4(D) allows it, the result says so, with the largest load the smaller size may carry under 210.19(A). The calculator's own answer always carries the full rating. It starts from the rating you choose and does not pick one for a load.

Limits

  • NM and UF cable are corrected from the 60 °C column; the cable articles' own ampacity rules are not covered yet.
  • Single conductors rated below 90 °C need the ampacity calculator, which takes the insulation rating.
  • A load is entered as all continuous or all noncontinuous, and you enter the count of current-carrying conductors: the rules for whether neutral and ground wires count are not covered.

How the circuit breaker calculator picks a breaker

The circuit breaker calculator starts from a continuous and a noncontinuous load in amperes, the conductor material and how the conductors are run:

  1. The smallest rating the load allows is the noncontinuous load plus 125 % of the continuous load, as 210.20(A) requires (see Continuous loads). With no continuous load, it is the load.
  2. Take the smallest standard rating of Table 240.6(A) at or above it, from 15 A (see Standard breaker and fuse ratings).
  3. Size the wire for that rating as steps 1 to 3 of the wire size calculator do, at 30 °C with no more than three current-carrying conductors: the column the terminals allow, the smallest size whose ampacity is at least the rating, then 240.4(D).
  4. Take the ground wire for the rating from Table 250.122, not larger than the wire (250.122(A); see Ground wires).

Where 240.4(B) lets the rating protect the next smaller size, and that size's ampacity still reaches the smallest rating the load allows, as 210.19(A) asks of the conductors, the result says so. The page's table of the largest breaker for each wire size runs the same rules the other way: the 240.4(D) limit for 14, 12 or 10 AWG copper and 12 or 10 AWG aluminum; above them, the ampacity when it is a standard rating, or the next standard rating above it under 240.4(B).

Limits

  • A breaker or fuse whose assembly is listed for operation at 100 % of its rating (the exception to 215.3) is not covered.
  • Motor, air conditioner and other equipment circuits follow rules of their own (see Not covered yet).

How the residential load calculator counts a house

The residential load calculator runs both methods of NEC 2023 Article 220 on the same inputs for one dwelling unit and shows every step (see Dwelling load calculations). The standard method adds:

  1. The floor area at 3 VA per ft² (220.41) and 1,500 VA for each small-appliance and laundry circuit (220.52), through Table 220.45.
  2. The water heater and the other appliances fastened in place, at 75 % of their total when there are 4 or more (220.53).
  3. The dryer at 5,000 W or its nameplate, whichever is larger (220.54), and one range from Table 220.55, Column C: 8 kW up to 12 kW, with Note 1 above that.
  4. An EV charger at 7,200 W or its nameplate, whichever is larger (220.57).
  5. The larger of the heating at 100 % (220.51) and the cooling at 125 %, read from 220.60 as set out below.

The optional method of 220.82 puts the floor area at 3 VA per ft², 1,500 VA per small-appliance and laundry circuit and the nameplates of the range, dryer, water heater, other appliances and EV charger into one general load, counts the first 10,000 VA of it at 100 % and the rest at 40 %, and adds the largest heating or cooling selection of 220.82(C) that applies: air conditioning at 100 %; a heat pump at 100 %, or at 100 % plus 65 % of its backup heat; electric heat at 65 % in fewer than 4 separately controlled units, or 40 % in 4 or more. Each method's total is divided by 240 V, and the service is the smallest Table 310.12 rating at or above the current (see Dwelling services and feeders).

Readings

  • 220.60 lets a calculation keep only the largest of loads unlikely to run at the same time; where a motor or air-conditioning load is not the largest of them, it calls for “125 percent of either the motor load or air-conditioning load.” The calculator compares the heating with the cooling taken at 125 % and keeps the larger.
  • The standard method names no heat pump. The calculator counts one as heating together with its backup heat (220.51) and as cooling on its own.
  • The 2023 optional method has no item for an EV charger. The calculator adds its nameplate to the general load, with the appliances 220.82(B) lists as located on a specific circuit.

Limits

  • One dwelling unit: no multifamily (220.84), existing dwelling (220.83) or two-unit (220.85) calculation.
  • Motors other than the air conditioning or heat pump count at their rating: the motor and air-conditioning rules 220.50 points to are not applied.
  • One range: a separate cooktop and wall ovens, and the 220.61 neutral load, are not calculated.
  • A heat pump whose compressor is locked out while the backup heat runs is still counted with both.
  • 2023 values only; the 2026 values in Article 120 are not verified yet.

How the range calculator sizes a range circuit

The range calculator starts from what the circuit supplies, the nameplate ratings in kW, the supply voltage and the circuit rating the appliance's instructions give:

  1. The branch-circuit load from Table 220.55 and its notes (see Dwelling load calculations): one range by Column C with Note 1; one wall-mounted oven or one counter-mounted cooking unit at its nameplate; a counter-mounted cooking unit with not more than two wall-mounted ovens, on one circuit in one room, added and treated as one range.
  2. The current: that load divided by the supply, 240 V or 208 V. The circuit rating entered must reach it.
  3. The wire for the circuit rating as steps 1 to 3 of the wire size calculator size it, and the ground wire from Table 250.122, not larger than that wire (250.122(A)).

The calculator offers circuit ratings from 20 A to 80 A, the standard ratings of Table 240.6(A) between them, and never picks one: the NEC's minimum circuit for household ranges has not been verified here, so the rating comes from the appliance's instructions (see Range and dryer makers' instructions).

Limits

  • One circuit: a feeder or service with several appliances is counted by the residential load calculator.
  • No continuous-load factor: a household range is counted at its Table 220.55 load.
  • The neutral, taps and cord sets are not sized.

How the dryer calculator counts a dryer

The dryer calculator keeps a dryer's two numbers apart:

  1. Its load on a feeder or service: each dryer at 5,000 W or its nameplate, whichever is larger (220.54), times the number of dryers and Table 220.54's percent for that number, and the current at the supply voltage.
  2. Its own circuit: the rating the dryer's instructions give, from 20 A to 50 A, with the wire and ground wire as steps 1 to 3 of the wire size calculator size them.

Limits

  • The calculator never picks the circuit rating; the dryer's instructions give it.
  • Dryers on a 3-phase feeder and the 220.61 neutral are not calculated.

How the horsepower to amps calculator reads the tables

The horsepower to amps calculator reads one cell of an NEC full-load current table and does no arithmetic on it:

  1. The table by motor: Table 430.248 for single-phase AC, Table 430.250's induction motors for three-phase AC, Table 430.247 for DC (see Motor full-load currents).
  2. The column by voltage: a single- or three-phase system voltage takes the rated-voltage column the tables' notes give it; a DC motor takes the column of its rated voltage.
  3. The cell in the horsepower's row, or none where the table prints none.

Beside the current it shows the rated power, the horsepower times 746 W, and the current that power alone would draw at the column's voltage at 100 % efficiency and a power factor of 1, divided by √3 more on three-phase. That second current is a comparison, never an answer.

Limits

  • No conductor, overload or breaker size: the NEC's motor rules for them are not verified here yet.
  • Synchronous motors, two-phase motors (Table 430.249) and Table 430.250's power factor footnote are left out.

How the garage subpanel calculator sizes a feeder

The garage subpanel calculator sizes the feeder from a house panel to a subpanel in a separate building, for a breaker from 30 A to 200 A:

  1. The conductors, the ground wire and the voltage drop as the wire size calculator works them out, with the calculated load you enter, if any, for the drop and for one size smaller under 240.4(B).
  2. Four wires: two hots, the neutral and the equipment grounding conductor (250.32(B)(1); see Grounding at a separate building).
  3. The garage's disconnect: at least the calculated load and never below 60 A, or 30 A with no more than two 2-wire branch circuits (225.39; see Feeders to a separate building).
  4. The minimum cover from Table 300.5(A) for three wiring methods and five places to bury the run (see Underground cover).

Limits

  • The calculator never picks the feeder's rating; a load calculation does.
  • It sizes the hots; the neutral is sized for the 220.61 neutral load, at most the hots' size.
  • No conduit size, no electrode size and no depth for EMT.

How the box fill calculator adds the fill

The box fill calculator adds the volume allowances of 314.16(B), each a Table 314.16(B)(1) volume (see Box fill):

  1. Each conductor the reader counts under 314.16(B)(1), at its own size.
  2. One allowance for internal cable clamps and one for each type of support fitting, on the largest conductor in the box.
  3. Two allowances for each device yoke and for each extra gang of a wide device, on the largest conductor connected to the devices.
  4. One allowance for up to four ground wires and a quarter for each more, on the largest ground wire.

The box holds the fill when its volume, from Table 314.16(A) or as marked on it, plus marked rings and covers, is at least the sum (314.16). The result also names the smallest box of each kind in Table 314.16(A) with room for the fill.

Limits

  • The reader counts the conductors; the calculator does not trace cables or splices.
  • No terminal blocks (314.16(B)(6)) and no conduit bodies.

How the conduit fill calculator reads Annex C

The conduit fill calculator reads one row of Annex C (see Conduit fill):

  1. The raceway picks the table, Table C.1 for EMT to Table C.13 for Type EB PVC, and compact stranding its (A) table.
  2. The insulation type and the wire size pick the row. THW and TW take 14 AWG to 8 AWG from their own rows and larger sizes from the rows they share with RHH and RHW without an outer covering; XHHW takes its smaller sizes from the rows it shares with ZW.
  3. “How many fit” reads the count under the trade size; “Conduit size” takes the smallest trade size whose count is at least the number entered.

Every count is the annex's own, which applies Chapter 9 Table 1, Table 4 and Table 5 (Table 5A for compact stranding) with Note 7's rounding; the calculator computes no area.

Limits

  • Conductors all of one size and type; no mixed sizes, which need Table 4 and Table 5.
  • No fixture wires, cables or cable trays, and no nipple fill (Note 4).

How the RV hookup calculator sizes an outlet and a park

The RV hookup calculator does two jobs:

  1. One RV outlet at a house: the circuit of a TT-30R or a 14-50R, sized for its breaker as the wire size calculator sizes it, with the voltage drop at the full rating (120 V for a TT-30R, 240 V between the hots for a 14-50R) and the GFCI rule of 210.8(F) for outdoor outlets at dwellings (see NEMA receptacle configurations).
  2. An RV park feeder or service: each site's load from 551.73(A), times the Table 551.73(A) demand factor for the number of sites, as current at 120/240 V single-phase and 208Y/120 V three-phase, with the receptacle shares of 551.71 (see RV parks).

Limits

  • No tent sites, no supply that serves two RVs, and no park buildings or pools, which 551.73 adds on their own.
  • The park result is a calculated load; it does not size the feeder conductors or the service.

How the well pump calculator reads Franklin’s tables

The well pump calculator reads Franklin Electric's tables for its 4-inch single-phase submersible motors (see Submersible well pumps):

  1. The copper size: the smallest size whose longest run in the cable table, at a 5 % drop or 0.6 times that for 3 %, reaches the whole cable length; with jacketed cable it skips the shaded cells, which Franklin rates for single conductors only.
  2. The run's share of that size's longest run, the number Franklin adds up when a run joins two sizes.
  3. Aluminum two sizes larger than the copper size, as Franklin asks; none past 4/0 AWG.
  4. The breaker and fuses from Franklin's table for the motor, the NEC maximum and the typical size, and the motor's amps.

Limits

  • Franklin's 4-inch single-phase motors only: no three-phase, 6-inch or 8-inch motors, and no other makers' tables.
  • No NEC motor rule is applied on its own; the NEC values are the ones Franklin lists.

How the hot tub calculator sizes a hot tub circuit

The hot tub calculator takes the breaker the hot tub's manual asks for and sizes the circuit as the wire size calculator sizes it, in copper, at 240 V for hardwired hot tubs and 120 V for plug-in ones, with the voltage drop at the full rating. It counts four wires at 240 V and three at 120 V, and reports the makers' GFCI and disconnect requirements (see Hot tub makers' instructions).

Limits

  • Copper only, as the makers ask; no aluminum.
  • No NEC Article 680 rule is applied; the GFCI and disconnect lines are the makers'.

How the air conditioner calculator sizes a circuit

The air conditioner calculator takes the two numbers 440.4(B) puts on the nameplate, the minimum circuit ampacity (MCA) and the maximum breaker or fuse (MOCP), and the run (see Air conditioner circuits):

  1. The copper size: the smallest size whose Table 310.16 ampacity, in the column the terminal rules allow for a circuit of the MOCP's rating, is at least the MCA. The 240.4(D) limits do not cap the breaker, since Table 240.4(G) sends air-conditioning circuit conductors to Article 440.
  2. The voltage drop at the MCA over the one-way length; past the target, the next size up, as the wire size calculator does.
  3. The ground wire: Table 250.122's size for a breaker at the MOCP, not larger than the circuit conductors (250.122(A)), and grown in proportion when the drop moves the conductors up (250.122(B)).
  4. The breaker or fuse: no larger than the MOCP.

Limits

  • Copper only, as both makers' documents ask; single-phase supply at 240 V or 208 V.
  • It does not work out an MCA or MOCP, and applies no temperature or bundling correction.

How the welder calculator sizes a circuit

The welder calculator takes I1max, the minimum supply wire and the breaker or fuse from the welder's manual (see Welder makers' electrical service guides), and the run:

  1. The breaker against 630.12(A): at most 200 % of I1max, or the next standard rating where that is not one (see Welder circuits).
  2. The copper size: from the manual's minimum, the first size whose ampacity in the column the terminal rules allow lets 630.12(B) (at most 200 % of the ampacity) take the breaker. Table 240.4(G) sends welder circuits to 630.12, so the 240.4(D) limits do not apply.
  3. The voltage drop at I1max over the one-way length; past the target, the next size up.
  4. The ground wire: Table 250.122's size for the breaker, not larger than the manual's minimum wire (250.122(A)), grown in proportion when the wire is larger (250.122(B)).

Limits

  • The NEC's own rule for sizing a welder's supply conductors has not been read in a 2023 source; the calculator starts from the manual's minimum wire.
  • One welder on its own circuit, single phase, copper; no temperature or bundling correction.

Wire gauge sizes and areas

NIST's Copper Wire Tables (Handbook 100, published in 1966 by the National Bureau of Standards, now NIST) list every American Wire Gauge size from 4/0 AWG to 40 AWG with its diameter, cross-sectional area, resistance and weight, for solid annealed copper at 20 °C. The site takes AWG diameters and areas from its Table 5.

Source
NIST (NBS) Handbook 100, Copper Wire Tables, Table 5
Publisher
NIST (National Bureau of Standards)
Retrieved
Cited on
Wire Size Calculator, Voltage Drop Calculator, Ground Wire Calculator, Wire Resistance Calculator, Low Voltage Calculator, Service Entrance Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, AWG Wire Size Chart, Homepage

The gauge numbers follow one geometric rule. Gauge 36 is 0.005 in across, 4/0 AWG (written 0000) is 0.46 in, and there are 39 equal steps between them, so each step changes the diameter by the same factor, about 1.1229. With n the gauge number, counting 4/0 AWG as −3, 3/0 AWG as −2, 2/0 AWG as −1 and 1/0 AWG as 0, the diameter is:

d(n) = 0.005 in × 92 to the power (36 − n)/39

A mil is a thousandth of an inch, and the area in circular mils (cmil) is the diameter in mils, squared. Sizes above 4/0 AWG are named by their area in thousands of circular mils: 250 kcmil is 250,000 cmil.

Limits

  • The values are for solid round wire.

Conductor resistance and voltage drop

Copper resistance at 20 °C comes from the same Handbook 100 table, which is based on a resistivity of 10.371 Ω·cmil/ft and a temperature coefficient of 0.00393 per °C. For aluminum, NIST's Aluminum Wire Tables (Handbook 109) give the constants of EC-H19 aluminum: a conductivity of 61.0 % of the International Annealed Copper Standard (IACS), a resistivity of 17.002 Ω·cmil/ft and a temperature coefficient of 0.00403 per °C.

Source
NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated
Publisher
NIST (NBS)
Retrieved
Cited on
Wire Size Calculator, Voltage Drop Calculator, Wire Resistance Calculator, Low Voltage Calculator, AWG Wire Size Chart, Service Entrance Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

Aluminum resistance, and the resistance of copper kcmil sizes, which Table 5 does not cover, are calculated from the resistivity ρ and the area A in circular mils:

R per 1000 ft = ρ × 1000 ÷ A

Resistance at another temperature T comes from the value at 20 °C and the temperature coefficient α:

R(T) = R(20 °C) × (1 + α × (T − 20 °C))

The voltage drop calculator uses the conductor temperature you enter, starting at 75 °C; the voltage-drop step of the wire size calculator uses 75 °C. With I the current, R the resistance per 1000 ft of one conductor, n the number of conductors in parallel, L the one-way length in feet, V the supply voltage (line to line on three-phase), and k = 2 on a DC or single-phase circuit or √3 on a three-phase circuit:

Voltage drop
VD = k × I × (R ÷ n) × L ÷ 1000
Percent drop
100 × VD ÷ V

Asked for the smallest size, the voltage drop calculator tries each Table 310.16 size from the smallest it offers until the drop is at most your target. A load entered in watts becomes a current through the formulas in Real, reactive and apparent power, Three-phase power and Watts, volts and ohms.

The power lost in the conductors, in watts:

DC or single-phase
2 × I² × R × L ÷ 1000
Three-phase
3 × I² × R × L ÷ 1000

The wire resistance calculator uses the temperature you enter. The low voltage calculator lets you choose 20 °C or 75 °C and finds the copper area a DC circuit needs for your voltage-drop target, with the current I you enter (or watts ÷ volts, see Watts, volts and ohms) and the allowed drop VD in volts:

Area needed, in cmil
CM = 2 × K × I × L ÷ VD
Copper resistivity at T
K = 10.371 Ω·cmil/ft × (1 + 0.00393 × (T − 20 °C))

It then takes the smallest Table 310.16 size with at least that area, or the size the current needs in the 60 °C column, whichever is larger.

Limits

  • Solid conductors: stranded conductors of the same size measure slightly higher.
  • DC resistance only: the reactance of AC circuits is not included.
  • Aluminum values are calculated from the Handbook 109 constants, because the handbook's rows for each size could not be read in the scanned copy. Aluminum starts at 12 AWG, the smallest aluminum size in NEC Table 310.16.
  • These are calculated values, not the conductor tables in Chapter 9 of the NEC.

Ampacity

Table 310.16 of the NEC (2023) gives the allowable ampacity of insulated conductors from 18 AWG to 2000 kcmil in three temperature columns, 60 °C, 75 °C and 90 °C, for copper and for aluminum or copper-clad aluminum. Its values assume not more than three current-carrying conductors in a raceway, cable or earth, at 30 °C (86 °F).

Source
NFPA 70 (NEC) 2023, Table 310.16
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Voltage Drop Calculator, Ampacity Calculator, Circuit Breaker Calculator, Range Calculator, Dryer Calculator, Wire Resistance Calculator, Low Voltage Calculator, AWG Wire Size Chart, NEC Table 310.16, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Homepage, Wire Size for EV Charger, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

The 2023 values were read from NFPA's reprint of the table in the public comment document for a proposed amendment, TIA 1691, in February 2023. The amendment failed, so the printed table stands. NFPA's drafts of the 2026 edition show the same values from 12 AWG to 2000 kcmil.

The wire size calculator uses the column the terminals allow (see Terminal temperatures). The ampacity calculator shows the column you choose. The voltage drop calculator notes when the current is above the size's 60 °C ampacity, and the low voltage calculator never picks a size whose 60 °C copper ampacity is below the current.

Limits

  • Other temperatures and more conductors need the corrections in Ambient temperature and bundling.
  • The final 2026 table has not been read. NFPA's 2026 drafts change only the rows for sizes smaller than 12 AWG.
  • The wire size calculator does not size from the higher columns: see Not covered yet.

Ambient temperature and bundling

Two NEC tables (2023) adjust Table 310.16 for conditions it does not assume. Table 310.15(B)(1)(1) gives correction factors by ambient temperature, based on 30 °C (86 °F), for each temperature column. Table 310.15(C)(1) gives adjustment percentages for more than three current-carrying conductors in a raceway or cable, from 80 % for 4–6 conductors down to 35 % for 41 and above.

Source
NFPA 70 (NEC) 2023, Tables 310.15(B)(1)(1) and 310.15(C)(1)
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Ampacity Calculator, NEC Table 310.16

The 2023 values were read from NFPA's First Draft of the 2026 edition, which prints the 2023 tables as its base text; no revision in that draft changed them. The ampacity calculator applies both:

corrected ampacity = Table 310.16 value × correction factor × adjustment percent ÷ 100

The ampacity calculator reads the row whose printed range holds the temperature you enter, in °C or °F, and the band that holds your count of current-carrying conductors. The wire size calculator applies both the same way, from the 90 °C column for single conductors and the 60 °C column for cable.

Limits

  • Where the table has no factor for an ambient temperature, that insulation rating is not permitted there, and the calculator says so.
  • You enter the number of current-carrying conductors. The rules for whether neutral and ground wires count are not covered yet.

Terminal temperatures

Section 110.14(C) of the NEC (2023) limits the column of Table 310.16 a conductor is sized from: the temperature rating used may not exceed the lowest rating of any connected termination, conductor or device. The terminals of equipment for circuits rated 100 A or less, or marked for 14 AWG through 1 AWG conductors, are used at the 60 °C ampacity unless the equipment is listed and identified for higher-rated conductors. Those for circuits rated over 100 A, or marked for conductors larger than 1 AWG, are used at the 75 °C ampacity unless listed and identified for more. A conductor with a higher rating may start from its own column for ampacity correction and adjustment.

Source
NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793)
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Ampacity Calculator, Circuit Breaker Calculator, Range Calculator, Dryer Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

The text was read in NFPA's Second Draft for the 2023 edition, where revision SR-7793 changed only the informational notes of 110.14(C). The ampacity calculator shows a corrected ampacity against the 60 °C and 75 °C values of the same size, never above the conductor's own column, and keeps NM and UF cable at the 60 °C column. The 200 A guide sizes a feeder rated over 100 A from the 75 °C column, and the wire size calculator sizes single conductors from the column these rules give for the rating, or from the one you confirm for the terminals.

Limits

  • Terminals listed and identified for 90 °C conductors are not covered.

Small-conductor limits

Section 240.4(D) of the NEC (2023) sets the largest breaker or fuse allowed on small conductors, whatever their ampacity: 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper; 15 A for 12 AWG and 25 A for 10 AWG aluminum or copper-clad aluminum.

Source
NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint)
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Ampacity Calculator, Circuit Breaker Calculator, Range Calculator, Dryer Calculator, AWG Wire Size Chart, NEC Table 310.16, Homepage, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

The limits were read from NFPA's records of revisions for the 2023 and 2026 editions (SR-8285 and SR-8377) and from the 2023 text as Leviton reprinted it with NFPA's permission. The wire size calculator moves up a size whenever the rating is above the limit, and the ampacity calculator shows the limit beside its result.

Limits

  • The rows that come with conditions, for 18 AWG copper, 16 AWG copper and 14 AWG copper-clad aluminum, are not used: no calculator recommends a conductor smaller than 14 AWG copper or 12 AWG aluminum.

Standard breaker and fuse ratings

Table 240.6(A) of the NEC (2023) lists the standard ampere ratings of fuses and inverse time circuit breakers, from 10 A to 6,000 A. The values come from Eaton's reprint of the 2023 table, made with NFPA's permission. Section 240.4(B) lets the next higher standard rating protect a conductor whose ampacity is not a standard rating, up to 800 A, where the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.

Source
NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints)
Publisher
NFPA (via Eaton/Leviton reprints with NFPA permission)
Retrieved
Cited on
Wire Size Calculator, Circuit Breaker Calculator, Range Calculator, Dryer Calculator, Ground Wire Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

The wire size calculator offers the standard ratings from 15 A to 400 A, and the ground wire calculator those from 15 A to 6,000 A.

Limits

  • The extra fuse-only ratings named in the text of 240.6(A) are not offered.
  • The calculators pick a conductor whose ampacity is at least the rating. The wire size calculator notes where 240.4(B) would allow the next smaller size, and the 200 A guide shows the allowance for a feeder of 4/0 AWG aluminum.

Continuous loads and the voltage-drop note

The 2023 NEC sizes branch circuits (210.19(A) and 210.20(A)), feeders (215.2(A) and 215.3) and service-entrance conductors (230.42(A)) for the noncontinuous load plus 125 % of the continuous load, the conductors and the breaker or fuse ahead of them alike. 215.2(A) also carries an informational note on voltage drop: feeder conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuit together, “will provide reasonable efficiency of operation.”

Source
NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft)
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Circuit Breaker Calculator, Voltage Drop Calculator, Low Voltage Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger, Garage Subpanel Calculator

NFPA's public inputs and First Draft for the 2026 edition print these 2023 sections as their base text; the voltage-drop note was read in two public inputs that quote 215.2(A) word for word.

The voltage drop calculator quotes the note as advice and starts its search for the smallest size at the note's 3 %, a target you can change; the low voltage calculator starts at the same figure. The wire size calculator applies the branch-circuit rules: for a load marked continuous, it asks for a rating of at least 125 % of the load.

Limits

  • The matching note for branch circuits has not been read in a 2023 text, so no page quotes it.
  • The pages give the note's figures as advice about efficiency, never as limits.

Ground wires and grounding electrode conductors

NFPA's 2020 grounding fact sheet, Using the Tables in Article 250 of the NEC, prints two tables the calculators use. Table 250.122 sizes the equipment grounding conductor (the ground wire) by the rating of the breaker or fuse ahead of the circuit, from 15 A to 6,000 A. Table 250.66 sizes the grounding electrode conductor by the largest service-entrance conductor.

Source
NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Circuit Breaker Calculator, Range Calculator, Dryer Calculator, Ground Wire Calculator, Service Entrance Calculator, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger, Garage Subpanel Calculator, RV Hookup Calculator, Hot Tub Wire Size Calculator, Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

Table 250.122 is the same in the fact sheet and in NFPA's record of revisions for the 2026 edition (SR-8360), which made no technical change to it. Table 250.66 comes from the fact sheet only; no 2023 or 2026 printing of it has been read.

The ground wire calculator and the wire size calculator take the ground wire from the first row of Table 250.122 whose rating is at least the breaker or fuse rating, in the copper column or the aluminum and copper-clad aluminum column. The ground wire calculator and the service entrance calculator take the grounding electrode conductor from Table 250.66 for the largest service conductor.

Section 250.122(A) does not require the ground wire to be larger than the circuit conductors. Every calculator that sizes the circuit wires therefore holds the table's size at the smallest conductor the rating allows, where the table lists a larger one, and the ground wire calculator says so for that rating. That sentence of the 2023 text was read in two of NFPA's public inputs for the 2026 edition (2573 and 3150). From 15 A to 400 A only one rating meets it: a 25 A breaker on aluminum, where the table gives 8 AWG and the conductor is 10 AWG.

When the wire size calculator chooses larger conductors for voltage drop, or when you tell the ground wire calculator the circuit wires were upsized, the ground wire grows in proportion, as 250.122(B) requires, rounded up to a Table 310.16 size and never larger than the circuit conductors:

ground wire area = starting ground wire area × installed conductor area ÷ minimum conductor area

Limits

  • Limits on grounding electrode conductors to ground rods and concrete-encased electrodes are not covered yet.

Dwelling services and feeders

Table 310.12 of the NEC (2023) lists conductor sizes for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit, from 100 A to 400 A, in copper and in aluminum or copper-clad aluminum. It applies the rule that these conductors may have an ampacity as low as 83 % of the service rating.

Source
NFPA 70 (NEC) 2023, Table 310.12
Publisher
NFPA
Retrieved
Cited on
Wire Size Calculator, Service Entrance Calculator, Residential Load Calculator, Ground Wire Calculator, NEC Table 310.16, Single vs Three Phase Systems, Wire Size for 200 Amp Service, Wire Size for 100 Amp Subpanel or Service

The 2023 values were read from NFPA's First Draft of the 2026 edition, which carries the 2023 table as its base text; the revisions in that draft changed only its wording. The service entrance calculator looks up the row for the rating you choose and never interpolates between rows.

Limits

  • Only for a 120/240 V single-phase service, or a feeder, that carries the entire load of one dwelling unit. Other services and feeders are sized from Table 310.16, as the 200 A guide compares.
  • The corrections for ambient temperature and bundling still apply.

Feeders to a separate building

Article 225 of the NEC (2023) covers outside branch circuits and feeders, among them a feeder to a separate building on the same property. Its 2023 text is read from NFPA's report of public inputs for the 2026 edition: Public Input 140 reprints the whole article as the 2023 edition prints it, with its own proposed words marked, and Public Input 3246, which renumbers the article, prints 225.39 word for word the same.

Source
NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
Wire Size for 100 Amp Subpanel or Service, Garage Subpanel Calculator

The 100 A guide uses three of its rules. Section 225.30 allows one feeder or branch circuit to a building unless one of its listed conditions permits more. Section 225.31 gives the building its own disconnecting means, inside or outside, readily accessible and nearest the point where the conductors enter. Section 225.39 sets the disconnect's least rating: 15 A for one branch circuit, 30 A for two 2-wire branch circuits, 100 A, 3-wire, for a one-family dwelling and 60 A for all others, and never less than the calculated load.

Limits

  • Burial depth and other wiring methods for the run to the building are not covered yet.

Grounding at a separate building

Section 250.32 of the NEC (2023) covers grounding at a building supplied by a feeder or branch circuit. Its 2023 text is read from NFPA's report of public inputs for the 2026 edition, where three submitters reprint 250.32(B)(1) as the 2023 edition prints it, each with a different proposed change marked, and a fourth reprints 250.32(A).

Source
NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
Wire Size for 100 Amp Subpanel or Service, Garage Subpanel Calculator

Section 250.32(A) gives the building its own grounding electrode system, unless a single branch circuit with an equipment grounding conductor supplies it. Section 250.32(B)(1) runs the equipment grounding conductor with the feeder, connects it to the building's disconnecting means and electrodes, sizes it by Table 250.122, and keeps the neutral from being connected to it or to the electrode at that building. Its Exception No. 1 lets a three-wire feeder installed under an earlier edition stay while three conditions hold.

Limits

  • Which electrodes make up the system, and how they are installed, are not covered yet.

Underground cover

Table 300.5(A) of the NEC (2023) gives the minimum cover, in inches and millimeters, for underground wiring of up to 1000 V by wiring method and location. It is read from NFPA's Second Revision SR-8551 of the 2023 cycle; the first row also matches three state and city summaries of the 2023 edition.

Source
NFPA 70 (NEC) 2023, Table 300.5(A) (NFPA 2023-cycle Second Draft SR-8551)
Publisher
NFPA
Retrieved
Cited on
Garage Subpanel Calculator

The garage subpanel calculator uses three of its columns (direct burial, rigid or intermediate metal conduit, and nonmetallic raceways listed for direct burial) and five of its rows. Cover is measured from the top of the cable, conductor or raceway to the top of finished grade, concrete or a similar cover (Note 1).

Limits

  • No depth for EMT: the 2023 column it falls in was not read clearly.
  • The row for runs under a building is left out: its conditions were not read clearly.

Box fill

Section 314.16 of the NEC (2023) sets how much volume a box needs for what it holds: Table 314.16(B)(1) gives the volume for each conductor by size, 314.16(B)(1) to (B)(6) say what counts and how often, and Table 314.16(A) lists the volume of twenty-four standard metal boxes. The table rows and their footnote are read from public input 3972 of the 2026 cycle, which reprints the 2023 table, and match First Revision 7727 of the 2023 cycle. The counting rules come from NFPA's revision records of the 2023 and 2026 cycles; the conductor and support fitting rules, which the 2023 cycle did not revise, from public input 1291, which reprints the 2020 text.

Source
NFPA 70 (NEC) 2023, 314.16 and Tables 314.16(A) and 314.16(B)(1), as reprinted in NFPA's committee records
Publisher
NFPA
Retrieved
Cited on
Box Fill Calculator

Limits

  • The 2026 edition's changes to 314.16 are not used.

Conduit fill

Chapter 9 of the NEC (2023) limits how much of a conduit's cross section conductors may fill (Table 1 and its Notes), and Informative Annex C applies those limits, with the conduit areas of Table 4 and the conductor areas of Table 5 (Table 5A for compact stranding), to list the most conductors of one size in each trade size of thirteen raceway types. Annex C's Tables C.1 to C.13(A) are read from public input 1588 of the 2026 cycle, which CMP-8 filed from Tentative Interim Amendment 23-7 and which prints the whole 2023 annex; its revision marks touch only the cable tray tables, which the site does not use. Table 1 and its Notes are read from First Revision 7763 of the 2026 First Draft, whose unmarked and struck text is the 2023 text.

Source
NFPA 70 (NEC) 2023, Chapter 9 Table 1 and Informative Annex C, Tables C.1 to C.13(A), as NFPA's 2026-cycle records print them
Publisher
NFPA
Retrieved
Cited on
Conduit Fill Calculator

Limits

  • Table 4 beyond intermediate metal conduit, and Table 5, are not verified, so the site calculates no conductor or conduit area.
  • Two printing slips in the record, a missing dash on two RMC rows and a THHN label in the LFNC-C table, are read as the other tables print them.

RV parks

Part VI of Article 551 of the NEC (2023) covers RV parks: 551.71 sets the receptacles each site has and where they need GFCI protection, and 551.73 the load a park's feeders and service are calculated for, with Table 551.73(A)'s demand factors by number of sites. Both are read from NFPA's public inputs and First Revisions for the 2026 edition: public input 3113 strikes the whole 2023 section 551.73 to move it, public input 638 and First Revision 8591 print the same table, and First Revision 8657 prints the 2023 section 551.71 it rewrites.

Source
NFPA 70 (NEC) 2023, 551.71 and 551.73, as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
RV Hookup Calculator

Limits

  • The 2026 edition's rewrite of 551.71 is not used.

Submersible well pumps (Franklin Electric)

Franklin Electric's AIM Manual (application, installation and maintenance of its 60 Hz submersible motors, 2026 edition) lists the longest copper cable for each motor at a 5 % voltage drop when the motor runs at its maximum nameplate amps, with the rule for 3 %, for aluminum and for shaded cells; the fuse and breaker sizes for each motor, both the NEC maximum and the size typical on submersibles; and the motors' amps. The values are read from Franklin's own PDF, and the shaded cells from the fill of the table cells.

Source
Franklin Electric, AIM Manual (60 Hz submersible systems), 2026 edition
Publisher
Franklin Electric
Retrieved
Cited on
Well Pump Wire Size Calculator

Limits

  • Only the 4-inch single-phase tables; the three-phase, 6-inch and 8-inch tables are not used.
  • The amps are Franklin's standard motors without the “G” suffix; other series draw slightly different currents.

Hot tub makers’ instructions

Three hot tub makers' 2026 documents give the circuit their hot tubs need: Hot Spring's pre-delivery instructions, Bullfrog's A Series owner's manual and Marquis's Elite owner's manual. Each names the breaker, the GFCI protection, the number of wires and copper wiring; Marquis also names the conductor sizes, and Marquis and Hot Spring the place of the disconnect.

Source
Hot Spring, Bullfrog and Marquis pre-delivery/owner manuals (2026)
Publisher
Watkins Wellness / Bullfrog Spas / Marquis
Retrieved
Cited on
Hot Tub Wire Size Calculator

Limits

  • Three makers' current models only; other makers and older models may ask for something else.

Air conditioner circuits, NEC Article 440

Article 440 of the NEC covers air-conditioning and refrigerating equipment. The site reads three of its rules in the 2023 text that NFPA's public inputs for the 2026 edition reprint with the proposed changes marked: 440.4(B), the nameplate's minimum supply circuit conductor ampacity and maximum protective device; 440.14, the place of the disconnect; and Table 240.4(G), which sends air-conditioning circuit conductors to Parts III, IV and VI of Article 440. The motor-compressor limits of 440.22(A) are read from the 2023-cycle Second Draft and Eaton's reprint of the 2023 values, made with NFPA's permission.

Source
NFPA 70 (NEC) 2023, 440.4(B), 440.14 and 240.4(G), as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
Air Conditioner Wire Size Calculator, Welder Wire Size Calculator

Limits

  • The rules for working out an MCA or MOCP, and the room air conditioner rules, have not been checked against a source.

Air conditioner makers’ product data

Carrier's product data for its 26SCA5 air conditioners (Catalog No. 26SCA5-02PD, June 2025) and Amana's specification sheet for its ALXS3N air conditioners (SS-ALXS3N-R32, April 2025) give the MCA and MOCP of each size from 1.5 to 5 tons at 208/230 V single phase. Both ask for copper wire; Amana asks for time-delay fuses or HACR-type breakers. Carrier's coastal 26SCA5C sheet prints a higher MOCP for two sizes.

Source
manufacturer product data (Carrier 26SCA5-02PD; Amana SS-ALXS3N-R32)
Publisher
Carrier; Daikin/Amana (Goodman); Trane Technologies
Retrieved
Cited on
Air Conditioner Wire Size Calculator

Limits

  • Two makers' current models only; read the nameplate of the unit being installed.

Welder circuits, NEC Article 630

Article 630 of the NEC covers electric welders. The site reads three of its sections in the 2023 text: 630.12, the welder's and the conductors' overcurrent limits, from the 2026 edition's Second Draft, whose revision shows the 2023 wording it replaces, and a public input that reprints 630.12(A); 630.8, GFCI protection for the receptacles in a welding area, from three public inputs that reprint it; and 630.13, the disconnect, from the 2023 edition's own Second Draft.

Source
NFPA 70 (NEC) 2023, 630.8, 630.12 and 630.13, as NFPA's revision records and public inputs print them
Publisher
NFPA
Retrieved
Cited on
Welder Wire Size Calculator

Limits

  • The section that sets the ampacity of a welder's supply conductors is in no record of NFPA's last three revision cycles that the site has read, so no calculator applies it.

Welder makers’ electrical service guides

Miller's owner's manuals for the Millermatic 211 PRO and Multimatic 215 PRO (April 2026), the Multimatic 220 AC/DC (July 2023) and the Millermatic 211 (March 2016), and Lincoln Electric's operator's manuals for the POWER MIG 210 MP (May 2022) and the AC-225C (January 2010), each read from the maker's own site. Each has an electrical service guide: the supply current, the fuse or breaker, the smallest copper supply wire and, for Miller, the longest run and the NEC edition it follows.

Source
Miller and Lincoln Electric owner manuals (as linked)
Publisher
Lincoln Electric / Miller Electric (ITW)
Retrieved
Cited on
Welder Wire Size Calculator

Limits

  • Six machines; other welders' manuals may ask for something else.

NM cable and neutral counting

Section 334.80 of the NEC (2023) sets the ampacity of NM cable, and 310.15(E) says when a neutral counts as a current-carrying conductor. Both are read from NFPA's public inputs and First Revisions for the 2026 edition, which reprint the 2023 text with the proposed changes marked.

Source
NFPA 70 (NEC) 2023, 334.80 and 310.15(E), as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
Wire Size for 100 Amp Subpanel or Service, Wire Size for EV Charger

NM cable's ampacity may not exceed that of a 60 °C conductor. Its 90 °C rating may be the starting point for temperature and bundling corrections, with the result held to the 60 °C value. A neutral that carries only the unbalanced current of its own circuit is not counted; the neutral of a 3-wire circuit taken from a 4-wire wye system is counted, and so is a wye neutral whose load is mostly nonlinear.

Limits

  • The ampacity rule for UF cable and whether grounding conductors count are not covered yet: no NFPA document for the 2026 edition reprints their 2023 text.

EV charger circuits, NEC Article 625

Article 625 of the NEC (2023) covers the circuit of an electric vehicle charger. Its sections 625.40 to 625.44 and 625.54 are read from NFPA's public inputs and First Revisions for the 2026 edition, which reprint the 2023 text with the proposed changes marked; each section is in two inputs from different submitters, filed in 2023 against the issued edition.

Source
NFPA 70 (NEC) 2023, Article 625, as reprinted in NFPA's 2026-cycle public inputs
Publisher
NFPA
Retrieved
Cited on
Wire Size for EV Charger

A charger above 16 A or 120 V gets its own branch circuit (625.40). Charging is a continuous load (625.42), and the breaker is at least 125 % of the charger's maximum load (625.41). A charger rated above 60 A or 150 V to ground needs a lockable disconnect (625.43). Section 625.44 lists the receptacles a charger may plug into, and 625.54 requires GFCI protection for every receptacle installed for EV charging.

Limits

  • The 2023 text only. Charging stations with several chargers, bidirectional charging and wireless charging are not covered.

EV charger makers’ instructions

The installation instructions of three Level 2 chargers: Tesla's Wall Connector, ChargePoint's Home Flex and Emporia's EV Charger. Each gives the breaker for each output setting, the largest wire its terminals take and whether it may plug into a receptacle; Tesla also gives the least wire size at full power for a breaker rated 60 °C and one rated 75 °C.

Source
Tesla, ChargePoint and Emporia installation instructions (as linked)
Publisher
Tesla / ChargePoint / Emporia
Retrieved
Cited on
Wire Size for EV Charger

Limits

  • Each value belongs to that maker's chargers and documents; none is used as a rule for others.

The federal credit for home chargers

The IRS page on the alternative fuel vehicle refueling property credit, which gives the dates of the credit for a charger at a home.

Source
IRS, Alternative Fuel Vehicle Refueling Property Credit
Publisher
IRS
Retrieved
Cited on
Wire Size for EV Charger

Dwelling load calculations

Article 220 of the NEC (2023) sets the load calculation for a dwelling: the standard method's unit loads and demand factors, from 220.41 to 220.61, and the optional method of 220.82. The values were read from NFPA Public Input 4311, which reproduces the 2023 text under the Article 120 numbers it proposed; the site maps them back to Article 220.

Source
NFPA 70 (NEC) 2023, Article 220 (as reproduced in NFPA Public Input 4311)
Publisher
NFPA
Retrieved
Cited on
Residential Load Calculator, Range Calculator, Dryer Calculator, Wire Size for EV Charger, Garage Subpanel Calculator

The values the calculator uses: 3 VA per ft² of floor area; 1,500 VA for each small-appliance and laundry circuit; Table 220.45's first 3,000 VA at 100 %, up to 120,000 VA at 35 % and the rest at 25 %; Table 220.55's Column C and its Note 1, which adds 5 % for each kW, or major fraction of one, over 12 kW, up to 27 kW; and the percents of 220.51, 220.53, 220.54, 220.57, 220.60 and 220.82 listed above.

Limits

  • The numbers of the last two notes to Table 220.55 were inferred from their order, so the site cites those notes without a number.
  • The 2026 edition moved these rules to Article 120; its values have not been verified here.

Range and dryer makers’ instructions

Installation instructions that ranges and dryers ship with. The range calculator quotes two: Whirlpool's freestanding electric range manual W11640146A (the same kW table as its earlier W10403811C and W10575959A), which gives the circuit for each band of range ratings, the cords and receptacles and the direct-wire sizes, and Frigidaire's 40-inch electric range instructions P/N 318201707 Rev. A. The dryer calculator quotes Whirlpool's electric dryer instructions W10267633A, GE's Pub # 31-16135 / 500A187P054 and GE's DBLR333EE spec sheet: the circuit, the cord, the conductors and the ratings.

Source
manufacturer installation instructions (Whirlpool, GE, Frigidaire)
Publisher
Whirlpool; GE Appliances; Frigidaire (Electrolux)
Retrieved
Cited on
Range Calculator, Dryer Calculator

Limits

  • Each value belongs to that maker's appliances and documents; none is used as a rule for others.
  • The calculator asks for the circuit rating; it shows the Whirlpool band only as an example.

NEMA receptacle configurations

The ratings, poles and wires of NEMA straight-blade receptacles, 10 configurations in all, read from Hubbell and Leviton device sheets that state compliance with NEMA WD 6. The standard itself is sold through ANSI and was not read.

Source
Hubbell NEMA configuration chart and Hubbell and Leviton device specifications (NEMA WD 6)
Publisher
Hubbell; Leviton
Retrieved
Cited on
Range Calculator, Dryer Calculator, Wire Size for EV Charger, RV Hookup Calculator, Welder Wire Size Calculator

Limits

  • Only the configurations in the file; a configuration not in it is not named on the site.

Other NEC 2023 sections

Single sections of the 2023 NEC that the site cites, read from Leviton's Captain Code 2023 pages, which reprint them with NFPA's permission. The range and dryer calculators cite 210.8(D): GFCI protection for the branch circuit or outlet that supplies an electric range, a wall-mounted oven, a counter-mounted cooking unit or a clothes dryer. The horsepower to amps calculator cites 430.6(A): the full-load current tables, not the nameplate current, for a motor's conductor ampacity, switch ratings and short-circuit and ground-fault protection, and the nameplate current for its separate overload protection. The EV charger guide cites 210.8(F), as amended by Tentative Interim Amendment 23-3: GFCI protection for outdoor outlets at a dwelling on single-phase branch circuits rated 150 V or less to ground and 50 A or less.

Source
NFPA 70 (NEC) 2023, sections as cited
Publisher
NFPA (via Leviton licensed reprint) / NFPA
Retrieved
Cited on
Range Calculator, Dryer Calculator, Horsepower to Amps Calculator, Wire Size for EV Charger, RV Hookup Calculator

Limits

  • Only the sections that source covers; state adoptions can amend them.

Motor full-load currents

NEC 2023 Tables 430.247 to 430.250 list a motor's full-load current by horsepower and rated voltage: DC, single-phase, two-phase and three-phase motors. The values were read from NFPA's 2023-cycle Second Draft (SR-7559 changed the titles and notes only) and from Eaton's 2023 reprint, which carries NFPA's permission; Table 430.250's rows up to 40 hp match that reprint cell for cell, and every other cell was confirmed twice against the Second Draft. The tables' notes give the columns for system voltages: 110–120 V takes the 115 V column, 220–240 V the 230 V column, 440–480 V the 460 V column, 550–600 V the 575 V column and 2,300–2,400 V the 2,300 V column; 200 V and 208 V have columns of their own.

Source
NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission)
Publisher
NFPA (2023-cycle Second Draft SR-7559; Eaton and Leviton 2023 reprints with NFPA permission)
Retrieved
Cited on
Horsepower to Amps Calculator

Limits

  • Only the induction motor columns of Table 430.250; the synchronous motor columns are not used.
  • Table 430.250's footnote for synchronous motors at other power factors is not used.
  • Two-phase motors (Table 430.249) are in the file but not offered: a 120/240 V supply is single-phase.

Real, reactive and apparent power

The U.S. Energy Information Administration's glossary defines the powers the calculators work with. Apparent power is volts times amperes, in volt-amperes. It splits into real power, the part that does work, in watts, and reactive power, which does none and which motors and other magnetic equipment need, in vars. Power factor is real power divided by apparent power, so it is at most 1.

Source
U.S. EIA Glossary (power, power factor)
Publisher
U.S. Energy Information Administration
Retrieved
Cited on
Voltage Drop Calculator, Three Phase Calculator, Single vs Three Phase Systems, Power Factor Explained, Kilowatts to Amps Calculator, kVA to Amps Calculator, Volts to Amps Calculator, Watts to Amps Calculator, Amps to Watts Calculator, Ohm's Law Calculator, Horsepower to Amps Calculator, Electrical Power Calculations

With P the real power, S the apparent power, V the voltage and PF the power factor:

Power factor
PF = P ÷ S
Apparent power
S = P ÷ PF
Current, single-phase AC
I = P ÷ (V × PF)
Current from S, single-phase
I = S ÷ V

Limits

  • The calculators use the power factor you enter; none measures or estimates it.

Three-phase power

The U.S. Department of Energy's Motor Challenge fact sheet on motor load and efficiency gives the power of a three-phase load as V × I × PF × √3 ÷ 1000 kilowatts, V being the voltage between two lines and I the current in one line, and works it on a measured motor: 469.7 V, 37 A and a power factor of 0.763 give 22.9 kW.

The horsepower to amps calculator quotes the sheet on horsepower and efficiency: a motor of a given rated horsepower is expected to deliver that power in mechanical form, and its efficiency is the ratio of its useful power output to its total power input.

Source
U.S. DOE fact sheet DOE/GO-10097-517, Determining Electric Motor Load and Efficiency
Publisher
U.S. Department of Energy
Retrieved
Cited on
Voltage Drop Calculator, Three Phase Calculator, Single vs Three Phase Systems, Power Factor Explained, Kilowatts to Amps Calculator, Volts to Amps Calculator, Watts to Amps Calculator, Amps to Watts Calculator, Horsepower to Amps Calculator, Electrical Power Calculations
Three-phase real power
P = √3 × V × I × PF
Current, three-phase AC
I = P ÷ (√3 × V × PF)

The three-phase calculator solves it for whichever value you leave out, and the voltage drop calculator uses it to turn a three-phase load in watts into a current.

Limits

  • A balanced load: the same current in all three lines, with sinusoidal voltage and current.

Line-to-line and line-to-neutral voltage

MIT's course notes on polyphase networks (6.061, J. L. Kirtley Jr.) show that in a balanced three-phase system the voltage between two lines is √3 times the voltage from a line to neutral, and that three-phase power, 3 × V(line to neutral) × I, is the same as √3 × V(line to line) × I. The nominal wye systems bear it out: 208Y/120 V and 480Y/277 V.

Source
MIT OpenCourseWare 6.061, Polyphase Networks (class notes, ch. 3)
Publisher
Massachusetts Institute of Technology (MIT OpenCourseWare)
Retrieved
Cited on
Three Phase Calculator, Single vs Three Phase Systems, Power Factor Explained, Kilowatts to Amps Calculator, kVA to Amps Calculator, Volts to Amps Calculator, Watts to Amps Calculator, Amps to Watts Calculator, Electrical Power Calculations
Apparent power, three-phase
S = √3 × V × I
Line to neutral, wye
V(line to neutral) = V(line to line) ÷ √3

Limits

  • The three-phase calculator names a line-to-neutral voltage only at 208 V and 480 V, the wye systems among the nominal voltages.

Power factor correction

The U.S. Department of Energy's Motor Challenge fact sheet on power factor cost draws real, reactive and apparent power as a right triangle, reactive power at 90° to real power, and shows a capacitor bank taking over reactive power so the apparent power and the current fall: 100 kW at 142 kVA, raised to a power factor of 0.95.

Source
U.S. DOE fact sheet DOE/GO-10096-286, Reducing Power Factor Cost
Publisher
U.S. Department of Energy
Retrieved
Cited on
Three Phase Calculator, Power Factor Explained, Kilowatts to Amps Calculator, kVA to Amps Calculator, Watts to Amps Calculator, Horsepower to Amps Calculator, Electrical Power Calculations
Reactive power
Q = √(S² − P²)
Capacitor bank
Qc = Q before − Q after, at the same P
Current after
I′ = I × PF ÷ PF′

Limits

  • The sheet gives its capacitor in kW; capacitors are rated in kVAR, and the sheet's own figures give 67.95 kVAR.
  • The capacitor bank's own protection and switching are outside the calculator.

Watts, volts and ohms

NIST Special Publication 330, the U.S. edition of the International System of Units, defines the volt as a watt per ampere and the ohm as a volt per ampere (Table 4). A watt is therefore a volt times an ampere, and on DC the current is the power divided by the voltage.

Source
NIST SP 330 (2019), The International System of Units, Table 4
Publisher
National Institute of Standards and Technology
Retrieved
Cited on
Voltage Drop Calculator, Low Voltage Calculator, Volts to Amps Calculator, Watts to Amps Calculator, Amps to Watts Calculator, Ohm's Law Calculator, Electrical Power Calculations
Current, DC
I = P ÷ V

The Ohm's law calculator works out the other two of voltage, current, resistance and power from any two you enter:

Ohm's law
V = I × R
Power
P = V × I = I² × R = V² ÷ R

Limits

  • Ohm's law here is for DC, or AC with a purely resistive load; the resistance is taken as constant.

Water heater elements

Rheem's and A.O. Smith's documents for their 240 V electric water heaters with two 4,500 W elements wire the elements so only one heats at a time. The watts to amps calculator uses this to show why such a heater draws the current of one element; the current itself is calculated.

Source
Rheem and A.O. Smith water heater documentation (as linked)
Publisher
Rheem / A.O. Smith
Retrieved
Cited on
Watts to Amps Calculator

Nominal system voltages

North Carolina Utilities Commission Rule R8-17 has utilities use a nominal voltage from ANSI C84.1, the national standard for system voltages, and lists them. At the low voltages buildings use: 120 and 120/240 V single-phase; 208Y/120, 240/120, 240, 480Y/277, 480 and 600 V three-phase. ANSI C84.1 itself is sold, not published openly, so the rule is the public record the calculators cite.

Source
NCUC Rule R8-17 (ANSI C84.1 voltages)
Publisher
NC Utilities Commission
Retrieved
Cited on
Wire Size Calculator, Voltage Drop Calculator, Three Phase Calculator, Single vs Three Phase Systems, Power Factor Explained, Kilowatts to Amps Calculator, kVA to Amps Calculator, Volts to Amps Calculator, Watts to Amps Calculator, Amps to Watts Calculator, Horsepower to Amps Calculator, Electrical Power Calculations

The voltage drop calculator offers 208, 240, 480, 600 V line to line on three-phase, and 120, 208, 240, 277 V as quick choices on single-phase: each is a voltage one of these systems names, line to line or line to neutral. The three-phase calculator offers the same three-phase voltages as buttons and takes any other you type. The wire size calculator offers 120, 208, 240, 277, 480 V on single-phase and the same three-phase voltages.

Limits

  • A nominal voltage names the system; the voltage actually delivered varies within the limits the standard sets.
  • Other voltages can be typed into the voltage drop and three-phase calculators.

Unit conversions

NIST Special Publication 811 (2008), the Guide for the Use of the International System of Units, lists the conversion factors in its Appendix B.8.

Source
NIST SP 811, Appendix B.8
Publisher
NIST
Retrieved
Cited on
BTU to Watts Calculator, Horsepower to Amps Calculator

The calculators use these:

Btu per hour
1 Btu/h = 0.2930711 W
Ton of refrigeration
1 ton = 12,000 Btu/h
Horsepower (electric)
1 hp = 746 W

The BTU to watts calculator converts both ways and gives the load in tons. The horsepower to amps calculator gives a motor's rating in watts.

Limits

  • The Btu is the International Table Btu, the one SP 811 lists for Btu per hour.
  • A ton is a ton of refrigeration, a rate of heat removal, not a weight.

Metric conductor sizes

IEC 60228 is the international standard for the nominal cross-sections of cable conductors, in square millimeters. The site uses only its list of nominal sizes, to show beside each AWG size the metric size nearest to it and the next one up.

Source
IEC 60228:2023 nominal conductor sizes
Publisher
IEC
Retrieved
Cited on
AWG Wire Size Chart

The nearest size compares the AWG area in mm² from NIST's table with the IEC series; the AWG wire size chart lists both for each size.

Limits

  • Only the sizes from 0.5 mm² to 1,600 mm² were read, so AWG sizes with less area than 0.5 mm² get no IEC size.
  • The comparison is by area alone; nothing else in the standard is used.
  • Whether a metric cable may replace an AWG one is a question for the local code, not this list.

NEC editions adopted by the states

Which NEC edition applies depends on what each state has adopted, or, where a state has no single statewide electrical code, what its cities and counties have adopted. The NEC edition by state table has one row per state code, each read from a state or District of Columbia government record: a statute, an administrative rule or a page of the agency that enforces the code. Each row links its record.

Source
state code-adoption records as linked per state
Publisher
State building, electrical and fire-safety agencies, legislatures and administrative codes (one per state, each linked in the NEC edition by state table)
Retrieved
Cited on
NEC Edition by State, NEC Table 310.16, Homepage, Electrical Calculators, Electrical Guides

The pages under Cited on give, from these rows, the states on the newest edition and the number of states on each edition, counting each state and the District of Columbia once.

Limits

  • Hawaii and Mississippi have no verified edition, and none is guessed.
  • City and county codes and their amendments are not listed; the local inspection office says which apply.
  • The rows were verified as of and are checked again by .

The 2026 NEC: issue and effective dates

NFPA's Standards Council issues each edition of the NEC. The final minutes of the meeting that issued the 2026 edition give its issue date, , and its effective date, . They also record the council's decisions on appeals against parts of the final text, one of which kept the 310.5 rule that allows 16 AWG copper and 14 AWG copper-clad aluminum branch-circuit conductors.

Source
NFPA Standards Council, Final Minutes of the August 18–20, 2025 meeting (NFPA 70-2026 issuance and appeal decisions)
Publisher
NFPA
Retrieved
Cited on
NEC Edition by State, NEC Table 310.16, Homepage, Electrical Calculators, Electrical Guides

The pages under Cited on take the two dates from these minutes.

Limits

  • The minutes give dates and decisions, not the code text, so the changes themselves come from the state review in the next section.
  • NFPA can amend an issued edition with Tentative Interim Amendments. None issued for the 2026 edition by Nov 2026 changes a section this site states.

Changes in the 2026 NEC

Minnesota's Department of Labor and Industry reviewed the issued 2026 edition before the state adopted it. The minutes of its review committee include a table of the significant changes, section by section, and the site states only changes that table describes. The site's calculators and tables stay on the 2023 edition.

Source
Minnesota Department of Labor and Industry, Summary of Significant 2026 NEC Changes (NEC 2026 Adoption Review Committee minutes, Sept. 25, 2025)
Publisher
Minnesota Department of Labor and Industry
Retrieved
Cited on
NEC Edition by State, NEC Table 310.16, Residential Load Calculator, Wire Size for EV Charger

The NEC Table 310.16 page uses it for the new minimum sizes, 16 AWG copper, 14 AWG copper-clad aluminum and 12 AWG aluminum, in a section renumbered to 310.5, and for the load-calculation article, renumbered from 220 to 120. NEC edition by state lists those changes and others from the summary, among them the threshold of outdoor GFCI protection at dwellings and the outdoor service disconnect of one- and two-family dwellings.

Limits

  • Changes seen only in NFPA's revision drafts are labeled as drafts and never shown as final.
  • The final 2026 Table 310.16 has not been seen, so no 2026 ampacity is shown.
  • One line of the summary, on electric vehicle charging, describes draft text that the issued edition left out; the site does not use it.

Not covered yet

No calculator on the site covers the topics below. Their 2023 NEC text, or the maker's current tables, has not yet been checked in full against a document that can be cited:

  • The ampacity rule for UF cable, and whether ground wires count as current-carrying.
  • Stranded conductor dimensions, and the AC resistance and reactance of conductors.
  • Conduit fill for conductors of different sizes, which needs the NEC's conduit and wire area tables.
  • Grounding electrode conductors to ground rods and concrete-encased electrodes, and how electrodes are installed.
  • Working space around electrical equipment and clearances for service conductors.
  • Motor circuits: conductor size, overload protection and the breaker or fuse.
  • Three-phase air conditioners, and indoor units with electric heat.
  • Pool pump circuits, and the NEC's own Article 680 rules for pools, spas and hot tubs.
  • Welder supply conductors by the NEC's own rule, groups of welders and resistance welders.
  • Three-phase and larger submersible well pump motors, and other pump makers' tables.

Errors and corrections

If a number on this site disagrees with its source, email info@wiresizes.com. Fixes are dated in the corrections list on the About page.

NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association. wiresizes.com is not affiliated with or endorsed by NFPA.