Wire Size for 60 Amp Breaker: 4 or 6 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 60 A breaker takes 4 AWG copper or 3 AWG aluminum in NM cable or at 60 °C terminals. Where every termination is listed and identified for 75 °C conductors, 6 AWG copper or 4 AWG aluminum is enough. 240.4(B) also lets a 60 A breaker protect 6 AWG copper at 60 °C when the load fits its 55 A.

The ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122).

Allowable ampacity, NEC Table 310.16, of the sizes around 60 A in the 60 °C and 75 °C columns: 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C; 2 AWG aluminum 75 A at 60 °C, 90 A at 75 °C. A 60 A breaker needs a size that reaches 60 A in the column its terminations allow: 4 AWG copper or 3 AWG aluminum at 60 °C, 6 AWG copper or 4 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations60 A breaker30 A40 A50 A60 A70 A80 A90 A100 A110 AAmpacity (size on the left)Copper8 AWG40 A50 A6 AWG55 A65 A4 AWG70 A85 A3 AWG85 A100 AAluminum6 AWG40 A50 A4 AWG55 A65 A3 AWG65 A75 A2 AWG75 A90 AAllowable ampacity, NEC Table 310.16, of the sizes around 60 A in the 60 °C and 75 °C columns: 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 4 AWG copper 70 A at 60 °C, 85 A at 75 °C; 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C; 3 AWG aluminum 65 A at 60 °C, 75 A at 75 °C; 2 AWG aluminum 75 A at 60 °C, 90 A at 75 °C. A 60 A breaker needs a size that reaches 60 A in the column its terminations allow: 4 AWG copper or 3 AWG aluminum at 60 °C, 6 AWG copper or 4 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations60 A breaker40 A60 A80 A100 AAmpacity (size on the left)Copper8 AWG6 AWG4 AWG3 AWGAluminum6 AWG4 AWG3 AWG2 AWG
The ampacity of the sizes around 60 A in the 60 °C column (open dots) and the 75 °C column (filled). 6 AWG copper's open dot falls short of 60 A at 55 A, a value that is not a standard breaker rating.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).

6 AWG on a 60 A breaker

In the 60 °C column, which covers NM cable (334.80) and terminals rated 60 °C, 6 AWG copper carries 55 A and 4 AWG carries 70 A, so a full 60 A circuit takes 4 AWG.

240.4(B) opens a second answer. Where a conductor's ampacity is not a standard rating of Table 240.6(A), the next higher standard rating may protect it, up to 800 A, provided the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads. 55 A is not a standard rating, so a 60 A breaker may protect 6 AWG copper at 60 °C, and 4 AWG aluminum the same way.

The load still has to fit the wire: under 210.19(A) for a branch circuit and 215.2(A) for a feeder, the conductors carry the noncontinuous load plus 125 % of the continuous load. On 6 AWG copper that is 55 A of noncontinuous load, or 44 A of continuous load. Where every termination is listed and identified for 75 °C conductors, 6 AWG carries 65 A and none of this applies.

A 60 A subpanel or service

A 60 A feeder takes the same sizes: 4 AWG copper or 3 AWG aluminum at 60 °C, 6 AWG copper or 4 AWG aluminum at 75 °C. Table 310.12, for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit, starts at 100 A, so a 60 A service or feeder is sized from Table 310.16 too.

A feeder to a separate building, such as a detached garage, runs four wires: two hots, the neutral and an equipment grounding conductor, and at that building the neutral stays off the grounding conductor and the electrode (250.32(B)(1)). The building's own disconnecting means must be rated at least 60 A for a garage or other building, which a 60 A feeder matches, and at least 100 A for a one-family dwelling (225.39). The garage subpanel calculator sizes the feeder for your run and gives the burial depth.

A 48 A EV charger on 60 A

625.41 sizes an EV charger's breaker at no less than 125 % of its output, so a 48 A charger goes on a 60 A breaker. Its wire must carry 60 A too, more than the 55 A of 6 AWG copper at 60 °C, so the 240.4(B) answer is out: the charger takes 4 AWG copper in NM cable, or 6 AWG where every termination is listed and identified for 75 °C. The EV charger wire guide shows the makers' own tables.

Bullfrog also lists a 60 A circuit at 240 V for its hot tubs; the hot tub calculator sizes it.

Ground wire for 60 A

Table 250.122 sizes the equipment grounding conductor by the breaker. Its row for breakers up to 60 A gives 10 AWG copper or 8 AWG aluminum, so a 60 A circuit sits at the top of that row. Going up a size for distance increases the ground wire in proportion to the larger circuit wires (250.122(B)); the ground wire calculator does that arithmetic.

60 A at 240 V: how far each size goes

At the full 60 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 4 AWG copper drops 3.63 V (1.51 %), 6 AWG copper 5.77 V (2.40 %), 3 AWG aluminum 4.74 V (1.97 %) and 4 AWG aluminum 5.97 V (2.49 %).

An informational note to 215.2(A) says feeders sized to keep the drop under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit.

Voltage drop of a 60 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 4 AWG copper 4.53 %, 3 AWG aluminum 5.92 %, 6 AWG copper 7.21 %, 4 AWG aluminum 7.46 %4 AWG copper, 60 °C3 AWG aluminum, 60 °C6 AWG copper, 75 °C4 AWG aluminum, 75 °C036912050100150200250300One-way length, ft (drop in % on the left)3 %: the feeder noteVoltage drop of a 60 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 4 AWG copper 4.53 %, 3 AWG aluminum 5.92 %, 6 AWG copper 7.21 %, 4 AWG aluminum 7.46 %4 AWG copper, 60 °C3 AWG aluminum, 60 °C6 AWG copper, 75 °C4 AWG aluminum, 75 °C0369120100200300One-way length, ft (drop in % on the left)3 %: the feeder note
Voltage drop of a 60 A circuit at full load, single-phase at 240 V, against one-way length: the 60 °C sizes as solid lines, the 75 °C sizes dashed, with the 215.2(A) note's 3 %.

Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

SizeLength
6 AWG125 ft
4 AWG199 ft
3 AWG250 ft
2 AWG316 ft
1 AWG398 ft
1/0 AWG502 ft

Aluminum: one-way length to a 3 % drop, ft

SizeLength
4 AWG121 ft
3 AWG152 ft
2 AWG192 ft
1 AWG242 ft
1/0 AWG305 ft
2/0 AWG385 ft

The wire size calculator finds the size for your length and load.

Ampacity of the sizes around 60 A

Both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together. NM cable uses the 60 °C column whatever its terminations (334.80).

Copper: Table 310.16 ampacity, A

Size60 °C75 °C
8 AWG40 A50 A
6 AWG55 A65 A
4 AWG70 A85 A
3 AWG85 A100 A

Aluminum: Table 310.16 ampacity, A

Size60 °C75 °C
6 AWG40 A50 A
4 AWG55 A65 A
3 AWG65 A75 A
2 AWG75 A90 A

Questions

Is 6 AWG wire good for 60 A?

With 75 °C terminations throughout, yes: it carries 65 A. At 60 °C or in NM cable it carries 55 A, and a 60 A breaker may protect it under 240.4(B) only when the load fits that.

Can 8 AWG wire go on a 60 A breaker?

No. 8 AWG copper carries 50 A even at 75 °C, and since that is a standard rating, 240.4(B) does not lift it to 60 A.

What size wire for a 60 A subpanel 100 ft away?

At the full 60 A, 4 AWG copper drops 1.51 % and 6 AWG copper 2.40 %, both inside the 3 % of the 215.2(A) note; the 6 AWG answer needs 75 °C terminations. The feeder to a detached building runs four wires.

What size wire for a 60 A service?

Table 310.12 starts at 100 A, so the Table 310.16 sizes apply: 4 AWG copper or 3 AWG aluminum at 60 °C, 6 AWG copper or 4 AWG aluminum at 75 °C.

What size aluminum wire for 60 A?

3 AWG at 60 °C terminals, 4 AWG where every termination is listed and identified for 75 °C conductors, with an 8 AWG aluminum ground wire. 4 AWG aluminum at 60 °C fits under 240.4(B) when the load stays within 55 A.

What size ground wire for a 60 A subpanel?

10 AWG copper or 8 AWG aluminum, from the 60 A row of Table 250.122, run with the feeder.