Air Conditioner Wire Size Calculator: MCA, MOCP and Breaker Size

The copper wire, ground wire and breaker for an air conditioner from the two numbers on its nameplate, the minimum circuit ampacity (MCA) and the maximum breaker or fuse (MOCP), with the voltage drop over your run.

By Marko Visic, BSc Physics · Updated · Sources below

Minimum circuit ampacity, on the condenser’s nameplate.

Maximum breaker or fuse, on the same nameplate.

Supply voltage
Wiring method
Terminal rating

75 °C only if the breaker, the disconnect and the condenser are listed for it.

Panel to the condenser, through the disconnect.

Your own limit for the run.

Copper only: Carrier and Amana both ask for copper conductors.

Carrier's 3-ton air conditioner, with an MCA of 17.6 A and an MOCP of 30 A, takes 12 AWG copper on a 30 A breaker, with a 12 AWG ground wire. The wire is sized to the MCA, not to the breaker: Table 240.4(G) sends air-conditioning circuits to Article 440, so the 30 A breaker is allowed on wire that 240.4(D) would otherwise hold to 20 A.

MCA and MOCP: the two numbers on the nameplate

Section 440.4(B) of the NEC asks multimotor and combination-load equipment, such as an air conditioner with its compressor and fan, for a nameplate with two numbers for the circuit: the minimum supply circuit conductor ampacity (MCA) and the maximum rating of the breaker or fuse (MOCP). The MCA is worked out by Part IV of Article 440, counting every motor and load that runs at the same time, and the maximum breaker by Part III. The wire is sized to the MCA, and no breaker or fuse may be larger than the MOCP.

Carrier's product data prints them as MCA and max fuse or circuit breaker; Amana's as minimum circuit ampacity and max overcurrent protection, with a note to check the rating plate of the unit being installed. Read your own unit's plate: two units of the same size can differ.

Wire for real air conditioners

Carrier's 26SCA5 and Amana's ALXS3N product data, both from 2025, give the MCA and MOCP of their 1.5- to 5-ton split-system air conditioners. The table runs each through the calculator: copper at 60 °C, which covers NM and UF cable and terminals not listed for more, at 75 °C where the breaker, the disconnect and the unit are all listed for it, the ground wire for the 60 °C wire, then the nameplate's two numbers. Tonnage alone does not set the wire: Carrier's 2.5-ton unit needs 12 AWG, Amana's 14 AWG.

Copper wire and ground wire for Carrier and Amana air conditioners, from the MCA and MOCP in their 2025 product data

UnitCopper 60 °CCopper 75 °CGroundMCAMOCP
1.5 ton,
Amana
14 AWG14 AWG14 AWG10.9 A15 A
1.5 ton,
Carrier
14 AWG14 AWG14 AWG10.9 A15 A
2 ton,
Amana
14 AWG14 AWG14 AWG10.9 A15 A
2 ton,
Carrier
14 AWG14 AWG14 AWG13.6 A20 A
2.5 ton,
Amana
14 AWG14 AWG14 AWG14.7 A25 A
2.5 ton,
Carrier
12 AWG14 AWG12 AWG16.5 A25 A
3 ton,
Amana
12 AWG14 AWG12 AWG17.5 A30 A
3 ton,
Carrier
12 AWG14 AWG12 AWG17.6 A30 A
3.5 ton,
Amana
12 AWG14 AWG12 AWG19.4 A30 A
3.5 ton,
Carrier
10 AWG12 AWG10 AWG22.7 A35 A
4 ton,
Amana
10 AWG10 AWG10 AWG25.6 A45 A
4 ton,
Carrier
10 AWG10 AWG10 AWG29.1 A40 A
5 ton,
Amana
8 AWG10 AWG10 AWG31.1 A50 A
5 ton,
Carrier
8 AWG10 AWG10 AWG31.1 A50 A

Carrier's coastal version, the 26SCA5C, prints 40 A for the 3.5-ton size and 50 A for the 4-ton size; the wire and the ground wire come out the same.

Why the breaker can be larger than the wire

On most circuits the breaker protects the wire, and 240.4(D) holds 14 AWG copper to 15 A, 12 AWG to 20 A and 10 AWG to 30 A. Its opening words leave room for the conductors 240.4(G) lists, and Table 240.4(G) sends air-conditioning and refrigeration circuit conductors to Parts III, IV and VI of Article 440.

There the wire is sized to the MCA, and the compressor's breaker or fuse may go up to 175 % of its rated-load current, or 225 % where that will not carry the starting current (440.22(A)); the MOCP on the nameplate is that limit worked out for the unit. Carrier's 3-ton unit, MCA 17.6 A, runs on 12 AWG copper with a 30 A breaker; its 2-ton unit, MCA 13.6 A, on 14 AWG with a 20 A breaker.

Amana asks for time-delay fuses or HACR-type circuit breakers of the size its sheet lists. Carrier's maximum is for a time-delay fuse or a breaker.

The ground wire

Table 250.122 sizes the ground wire by the breaker ahead of the circuit: 10 AWG copper for 30 A. Section 250.122(A) adds that the ground wire does not have to be larger than the circuit conductors, so the 3-ton example's 12 AWG circuit takes a 12 AWG ground wire, and the 2-ton unit's 14 AWG circuit a 14 AWG one. When the wire goes up a size for voltage drop, 250.122(B) grows the ground wire in proportion; the calculator does both.

Long runs and voltage drop

Table 310.16 sizes for current, not distance, and Amana's sheet notes that long runs need larger wire. At the example's MCA of 17.6 A and 240 V, copper at 75 °C drops 3 % at the lengths below. Past your target, the calculator moves the wire up a size and the ground wire with it.

One-way length at which a 17.6 A MCA at 240 V drops 3 %

CopperLength
12 AWG106 ft
10 AWG168 ft
8 AWG268 ft
6 AWG426 ft
The longest one-way copper run before a 17.6 A MCA at 240 V drops 3 %, copper at 75 °C: 12 AWG 106 ft, 10 AWG 168 ft, 8 AWG 268 ft, 6 AWG 426 ft.CopperLongest run at 3 %12 AWG106 ft10 AWG168 ft8 AWG268 ft6 AWG426 ftThe longest one-way copper run before a 17.6 A MCA at 240 V drops 3 %, copper at 75 °C: 12 AWG 106 ft, 10 AWG 168 ft, 8 AWG 268 ft, 6 AWG 426 ft.CopperLongest run at 3 %12 AWG106 ft10 AWG168 ft8 AWG268 ft6 AWG426 ft
The longest one-way copper run before an MCA of 17.6 A drops 3 % at 240 V.

Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated.

The disconnect

Section 440.14 puts the disconnect within sight from the air conditioner and readily accessible from it. It may be mounted on or in the unit, but not on a panel that opens for service or where it hides the nameplate, and it needs the working space of 110.26(A). The calculator's length is the whole run, from the panel through the disconnect to the unit.

What the calculator does not cover

  • Equipment without the two numbers: the calculator does not work out an MCA or MOCP.
  • Heat and bundling: wire on a hot roof, in a hot attic or in a full conduit may need corrections the calculator does not apply.
  • The indoor unit's circuit, with any electric heat, and three-phase units.
  • Room air conditioners, some of which need not carry the two numbers (440.4(B), Exception No. 2).

Questions

What size wire for a 3-ton air conditioner?

12 AWG copper with a 12 AWG ground wire for Carrier's and Amana's 3-ton units (MCA 17.6 A and 17.5 A, MOCP 30 A); 14 AWG copper where everything on the circuit is listed for 75 °C. Read your own nameplate: the MCA, not the tonnage, sets the wire.

What size wire for a 5-ton air conditioner?

8 AWG copper at 60 °C or 10 AWG at 75 °C for Carrier's and Amana's 5-ton units (MCA 31.1 A for both), on a breaker of up to 50 A, with a 10 AWG ground wire.

Can a 30 A breaker go on 12 AWG wire for an air conditioner?

Yes, when the nameplate allows it, as on the 3-ton units above: an MCA the wire carries and an MOCP of 30 A. Table 240.4(G) sends air-conditioning circuits to Article 440, so the 20 A cap of 240.4(D) on 12 AWG does not apply.

What wire for an air conditioner 150 ft from the panel?

For the 3-ton example, 10 AWG copper keeps the drop at the MCA to 2.67 %; 12 AWG would reach 4.25 %. The ground wire grows with it, to 10 AWG.

Can I use aluminum wire for an air conditioner?

Not on these units: Carrier's product data says copper wire must be used from the service disconnect to the unit, and Amana's wiring diagrams say to use copper conductors only. The calculator gives copper only.

Where does the air conditioner's disconnect go?

Within sight from the unit and readily accessible from it (440.14). It may be on or in the unit, but not on a service panel or over the nameplate.

Sources

The wire sizes are the 2023 NEC's; the NEC edition by state shows which edition applies where you live. The methodology page describes how the calculator works and each source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.