Box Fill Calculator: NEC 314.16 Box Size and Wire Count

How many wires fit in an electrical box: the fill NEC 314.16 counts for conductors, devices, ground wires and clamps, against the volume of a metal box from Table 314.16(A) or the volume marked on a plastic one.

By Marko Visic, BSc Physics · Updated · Sources below

device, 18.0 in³ (Table 314.16(A)).

Optional: a marked plaster or extension ring, or a domed cover.

Conductors, by size

Each wire that enters and ends or is spliced here counts once, a pass-through once, a long loop twice. Skip pigtails that stay in the box, and count ground wires below.

Up to four count once.

Sets the ground wire allowance.

A switch or receptacle on one yoke counts twice.

The device allowance uses this size.

Optional: gangs past one for a device wider than one box.

Cable clamps inside the box
Luminaire studs or hickeys

Each conductor takes 2.00 in³ at 14 AWG and 2.25 in³ at 12 AWG (Table 314.16(B)(1)). A switch or receptacle takes two of those for its yoke, up to four ground wires take one, and internal cable clamps one.

A receptacle fed by two 12 AWG cables, each with a ground wire, fills a 3 × 2 × 3½ in device box (18.0 in³) exactly when the box has internal clamps: 18.00 in³. On 14 AWG the same box keeps 2.00 in³ free.

Volume for each conductor

Table 314.16(B)(1) sets the free space a box needs for each conductor, from 1.50 in³ at 18 AWG to 5.00 in³ at 6 AWG. Box fill adds these volumes up, and under 314.16 the box's volume may not be less than the total.

Volume for each conductor, NEC Table 314.16(B)(1)

Conductorin³cm³
18 AWG1.5024.6
16 AWG1.7528.7
14 AWG2.0032.8
12 AWG2.2536.9
10 AWG2.5041.0
8 AWG3.0049.2
6 AWG5.0081.9

What counts in box fill

  • Conductors, 314.16(B)(1). A wire that comes in from outside and ends or is spliced in the box counts once, and so does one that passes through. A loop or coil at least twice the free length 300.14 asks for counts twice. A conductor that never leaves the box, such as a pigtail, is not counted.
  • Clamps, 314.16(B)(2). One allowance for all internal cable clamps together, sized on the largest conductor in the box; none for a connector whose clamp sits outside the box.
  • Support fittings, 314.16(B)(3). One allowance for each type, luminaire studs or hickeys, on the largest conductor in the box.
  • Devices, 314.16(B)(4). Two allowances for each yoke or strap, sized on the largest conductor connected to the device or devices it carries. A device wider than a single 2 in device box takes two for each gang it needs.
  • Ground wires, 314.16(B)(5). One allowance for up to four equipment grounding conductors entering, sized on the largest of them, and a quarter allowance for each one more: a fifth 12 AWG ground wire adds 0.5625 in³.
  • Terminal blocks, 314.16(B)(6). One allowance for each terminal block assembly, on the largest conductor terminated to it. A weight-supporting ceiling receptacle counts as a device (314.27(E)).

Small fittings such as locknuts and bushings take no allowance, and each space of a box divided by a barrier is calculated on its own.

A 18.0 in³ device box with one receptacle, four conductors, two ground wires and cable clamps: on 12 AWG they fill 18.00 in³, the whole box; on 14 AWG 16.00 in³, leaving 2.00 in³.12 AWG18.00 in³ of 18.0 in³each cell 2.25 in³14 AWG16.00 in³ of 18.0 in³2.00 in³ freeeach cell 2.00 in³ConductorsReceptacle ×2Ground wiresClampsA 18.0 in³ device box with one receptacle, four conductors, two ground wires and cable clamps: on 12 AWG they fill 18.00 in³, the whole box; on 14 AWG 16.00 in³, leaving 2.00 in³.12 AWG18.00 in³ of 18.0 in³each cell 2.25 in³14 AWG16.00 in³ of 18.0 in³2.00 in³ freeeach cell 2.00 in³ConductorsReceptacle ×2Ground wiresClamps
The worked example in the 18.0 in³ device box, to scale: four conductors, the receptacle's double allowance (4.50 in³ on 12 AWG), the ground wires and the clamps. On 12 AWG they fill 18.00 in³; on 14 AWG, 16.00 in³.

Source: NFPA 70 (NEC) 2023, 314.16 and Tables 314.16(A) and 314.16(B)(1), as reprinted in NFPA's committee records.

Metal box volumes

Table 314.16(A) lists the volume of twenty-four standard metal boxes and the most conductors of one size each may hold. Those counts hold only where nothing else in the box needs an allowance: no clamps, fittings, devices or ground wires. With any of them, add the allowances, as the calculator does.

Metal boxes, NEC Table 314.16(A): volume and the most conductors of one size

Box, inTypein³cm³18 AWG16 AWG14 AWG12 AWG10 AWG8 AWG6 AWG
3 × 2 × 1½device7.51235433321
3 × 2 × 2device10.01646554432
3 × 2 × 2¼device10.51727654432
3 × 2 × 2½device12.52058765542
3 × 2 × 2¾device14.02309876542
3 × 2 × 3½device18.0295121098763
4 × 2⅛ × 1½device10.31696554432
4 × 2⅛ × 1⅞device13.02138765542
4 × 2⅛ × 2⅛device14.52389876542
4 × 1¼square18.0295121098763
4 × 1½square21.03441412109874
4 × 2⅛square30.34972017151312106
4¹¹⁄₁₆ × 1¼square25.5418171412111085
4¹¹⁄₁₆ × 1½square29.5484191614131195
4¹¹⁄₁₆ × 2⅛square42.06892824211816148
4 × 1¼round or octagonal12.52058765542
4 × 1½round or octagonal15.525410876653
4 × 2⅛round or octagonal21.53531412109874
3¾ × 2 × 2½masonry box or gang14.02309876542
3¾ × 2 × 3½masonry box or gang21.03441412109874
1¾ deepFS — single cover/gang13.52219766542
2⅜ deepFD — single cover/gang18.0295121098763
1¾ deepFS — multiple cover/gang18.0295121098763
2⅜ deepFD — multiple cover/gang24.039516131210984

Plastic boxes, rings and covers

Under 314.16(A)(2), nonmetallic boxes, and other boxes of 100 in³ or less that are not in Table 314.16(A), are marked by the maker with their volume. Use that marked volume. A box's volume also includes plaster rings, extension rings and domed covers that are marked with their volume or made from a box in the table (314.16(A)); enter them under rings and covers.

What changed in 2023

  • Equipment bonding jumpers left the ground wire count of 314.16(B)(5); it now names equipment grounding conductors only.
  • Terminal blocks got their own allowance, 314.16(B)(6).
  • The paragraph on clamp assemblies with a cable termination was removed from 314.16(B)(2).
  • Table 314.16(A) corrected the 4 × 1¼ in round or octagonal box: its 8 AWG column now reads 4, the most its 12.5 in³ holds at 3.00 in³ each.

Questions

How many 12 AWG wires can go in a single-gang box?

It depends on the box's volume. A 3 × 2 × 3½ in device box (18.0 in³) holds 8 with nothing else in it. With a receptacle and its ground wires it holds 5, and 4 if the box also has internal clamps.

How many wires fit in a 4 in square box?

With nothing else in it, a 4 × 1½ in square box (21.0 in³) holds 10 conductors of 14 AWG or 9 of 12 AWG, and a 4 × 2⅛ in square box (30.3 in³) 15 or 13 (Table 314.16(A)). Devices, ground wires and clamps take their allowances from those numbers.

Do ground wires count in box fill?

Yes. Up to four equipment grounding conductors entering the box count as one allowance, sized on the largest of them; each one more adds a quarter allowance (314.16(B)(5)).

Do pigtails count in box fill?

No. A conductor no part of which leaves the box is not counted (314.16(B)(1)). The wires the pigtail is spliced to count once each.

How does a switch or receptacle count?

As two conductors for each yoke or strap, sized on the largest conductor connected to it: 4.00 in³ on 14 AWG, 4.50 in³ on 12 AWG (314.16(B)(4)).

Do cable clamps count in box fill?

Internal clamps count once in all, sized on the largest conductor in the box, however many there are. A cable connector whose clamp sits outside the box counts nothing (314.16(B)(2)).

Sources

Retrieved .

The rules are the 2023 NEC's; the NEC edition by state shows which edition applies where you live. The methodology page describes how the calculator works and its source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.