Wire Size for 40 Amp Breaker: 8 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 40 A breaker takes 8 AWG copper, in NM cable or as single conductors. Aluminum depends on the terminals: 6 AWG at 60 °C, 8 AWG where every termination is listed and identified for 75 °C conductors.

The ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122). At 240 V the full 40 A runs 118 ft on 8 AWG copper before the drop reaches 3 %.

Allowable ampacity, NEC Table 310.16, of the sizes around 40 A in the 60 °C and 75 °C columns: 10 AWG copper 30 A at 60 °C, 35 A at 75 °C; 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 10 AWG aluminum 25 A at 60 °C, 30 A at 75 °C; 8 AWG aluminum 35 A at 60 °C, 40 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C. A 40 A breaker needs a size that reaches 40 A in the column its terminations allow: 8 AWG copper or 6 AWG aluminum at 60 °C, 8 AWG copper or 8 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations40 A breaker10 A20 A30 A40 A50 A60 A70 AAmpacity (size on the left)Copper10 AWG30 A35 A8 AWG40 A50 A6 AWG55 A65 AAluminum10 AWG25 A30 A8 AWG35 A40 A6 AWG40 A50 A4 AWG55 A65 AAllowable ampacity, NEC Table 310.16, of the sizes around 40 A in the 60 °C and 75 °C columns: 10 AWG copper 30 A at 60 °C, 35 A at 75 °C; 8 AWG copper 40 A at 60 °C, 50 A at 75 °C; 6 AWG copper 55 A at 60 °C, 65 A at 75 °C; 10 AWG aluminum 25 A at 60 °C, 30 A at 75 °C; 8 AWG aluminum 35 A at 60 °C, 40 A at 75 °C; 6 AWG aluminum 40 A at 60 °C, 50 A at 75 °C; 4 AWG aluminum 55 A at 60 °C, 65 A at 75 °C. A 40 A breaker needs a size that reaches 40 A in the column its terminations allow: 8 AWG copper or 6 AWG aluminum at 60 °C, 8 AWG copper or 8 AWG aluminum at 75 °C.60 °C: NM cable, 60 °C terminals75 °C: 75 °C terminations40 A breaker30 A50 A70 AAmpacity (size on the left)Copper10 AWG8 AWG6 AWGAluminum10 AWG8 AWG6 AWG4 AWG
The ampacity of the sizes around 40 A in the 60 °C column (open dots) and the 75 °C column (filled). 8 AWG copper reaches 40 A in both; 8 AWG aluminum only in the 75 °C column.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).

Copper stays 8 AWG; aluminum depends on the terminals

Under 110.14(C)(1)(a), circuits of this size start from the 60 °C column of Table 310.16, and use the 75 °C column only where the equipment is listed and identified for 75 °C conductors. At 40 A that choice moves aluminum, not copper.

8 AWG copper carries 40 A at 60 °C and 50 A at 75 °C. The next size down, 10 AWG, carries only 35 A even at 75 °C, and 240.4(D) holds it to a 30 A breaker anyway. In aluminum, 6 AWG carries 40 A at 60 °C, while 8 AWG reaches 40 A only at 75 °C.

8 AWG NM cable at exactly 40 A

334.80 holds NM cable to the 60 °C column, where 8 AWG copper carries 40 A, the breaker's rating with nothing to spare. Its 90 °C rating is the starting point for heat and bundling corrections, and the result may not exceed the 60 °C value. The wire size calculator applies both for cable in a hot attic or bundled with others.

Ranges and EV chargers on 40 A

Frigidaire's electric range instructions call for a 14-50R with a matching 40 A range cord, and on a 4-wire 40 A circuit at least 8 AWG copper for the hots, 10 AWG for the neutral and 8 AWG for the ground, a size larger than the 10 AWG of Table 250.122. Whirlpool's freestanding ranges rated 8.8 kW to 16.5 kW at 240 V take a 40 A or 50 A circuit. The range calculator works out a range's load from its rating.

An EV charger set to a 32 A output goes on a 40 A breaker, because 625.41 calls for at least 125 % of the output. The EV charger wire guide has the makers' tables.

40 A at 240 V: how far each size goes

At the full 40 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 8 AWG copper drops 6.11 V (2.55 %), 6 AWG aluminum 6.33 V (2.64 %) and 8 AWG aluminum 10.07 V (4.19 %).

An informational note to 215.2(A) says feeders sized to keep the drop under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit; the lengths below are where each size reaches it at the full rating.

Voltage drop of a 40 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 8 AWG copper at 60 and 75 °C 7.64 %, 6 AWG aluminum 7.92 %, 8 AWG aluminum 12.58 %8 AWG copper, 60 °C and 75 °C6 AWG aluminum, 60 °C8 AWG aluminum, 75 °C036912050100150200250300One-way length, ft (drop in % on the left)3 %: the feeder noteVoltage drop of a 40 A circuit at full load, single-phase at 240 V, against one-way length, on the 60 °C sizes (solid) and the 75 °C sizes (dashed): at 300 ft, 8 AWG copper at 60 and 75 °C 7.64 %, 6 AWG aluminum 7.92 %, 8 AWG aluminum 12.58 %8 AWG copper, 60 °C and 75 °C6 AWG aluminum, 60 °C8 AWG aluminum, 75 °C0369120100200300One-way length, ft (drop in % on the left)3 %: the feeder note
Voltage drop of a 40 A circuit at full load, single-phase at 240 V, against one-way length, with the 215.2(A) note's 3 %.

Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

SizeLength
8 AWG118 ft
6 AWG187 ft
4 AWG298 ft
3 AWG375 ft
2 AWG473 ft
1 AWG597 ft

Aluminum: one-way length to a 3 % drop, ft

SizeLength
8 AWG72 ft
6 AWG114 ft
4 AWG181 ft
3 AWG228 ft
2 AWG288 ft
1 AWG363 ft

A larger wire for distance takes a larger ground wire too, in proportion (250.122(B)); the wire size calculator sizes both.

Ampacity of the sizes around 40 A

Both columns of NEC Table 310.16 for the sizes on either side of the answer. The table assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.

Copper: Table 310.16 ampacity, A

Size60 °C75 °C
10 AWG30 A35 A
8 AWG40 A50 A
6 AWG55 A65 A

Aluminum: Table 310.16 ampacity, A

Size60 °C75 °C
10 AWG25 A30 A
8 AWG35 A40 A
6 AWG40 A50 A
4 AWG55 A65 A

Questions

Is 8 AWG wire good for 40 A?

Yes, in NM cable or as single conductors: it carries 40 A at 60 °C and 50 A at 75 °C.

Can 10 AWG wire go on a 40 A breaker?

Not on an ordinary circuit: 240.4(D) protects 10 AWG copper at 30 A at most. Air conditioners are the exception, since Table 240.4(G) sends them to Article 440; the air conditioner calculator applies it.

What size wire for a 40 A subpanel?

The same sizes: 8 AWG copper, or 6 AWG aluminum (8 AWG with 75 °C terminations). A feeder to a separate building runs four wires, with the ground kept apart from the neutral there (250.32(B)(1)). That building's disconnect is rated at least 60 A unless it has no more than two 2-wire circuits (225.39).

What size wire for 40 A at 240 V?

8 AWG copper; at the full 40 A it drops 2.55 % over 100 ft and reaches 3 % at 118 ft.

What size aluminum wire for 40 A?

6 AWG at 60 °C terminals, 8 AWG where every termination is listed and identified for 75 °C conductors, with an 8 AWG aluminum ground wire.

What size ground wire for 40 A?

10 AWG copper or 8 AWG aluminum, from the 60 A row of Table 250.122. Frigidaire's range instructions ask for 8 AWG copper on their 40 A circuit.

Sources

The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.