Wire Size for 40 Amp Breaker: 8 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
A 40 A breaker takes 8 AWG copper, in NM cable or as single conductors. Aluminum depends on the terminals: 6 AWG at 60 °C, 8 AWG where every termination is listed and identified for 75 °C conductors.
The ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122). At 240 V the full 40 A runs 118 ft on 8 AWG copper before the drop reaches 3 %.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793).
Copper stays 8 AWG; aluminum depends on the terminals
Under 110.14(C)(1)(a), circuits of this size start from the 60 °C column of Table 310.16, and use the 75 °C column only where the equipment is listed and identified for 75 °C conductors. At 40 A that choice moves aluminum, not copper.
8 AWG copper carries 40 A at 60 °C and 50 A at 75 °C. The next size down, 10 AWG, carries only 35 A even at 75 °C, and 240.4(D) holds it to a 30 A breaker anyway. In aluminum, 6 AWG carries 40 A at 60 °C, while 8 AWG reaches 40 A only at 75 °C.
8 AWG NM cable at exactly 40 A
334.80 holds NM cable to the 60 °C column, where 8 AWG copper carries 40 A, the breaker's rating with nothing to spare. Its 90 °C rating is the starting point for heat and bundling corrections, and the result may not exceed the 60 °C value. The wire size calculator applies both for cable in a hot attic or bundled with others.
Ranges and EV chargers on 40 A
Frigidaire's electric range instructions call for a 14-50R with a matching 40 A range cord, and on a 4-wire 40 A circuit at least 8 AWG copper for the hots, 10 AWG for the neutral and 8 AWG for the ground, a size larger than the 10 AWG of Table 250.122. Whirlpool's freestanding ranges rated 8.8 kW to 16.5 kW at 240 V take a 40 A or 50 A circuit. The range calculator works out a range's load from its rating.
An EV charger set to a 32 A output goes on a 40 A breaker, because 625.41 calls for at least 125 % of the output. The EV charger wire guide has the makers' tables.
40 A at 240 V: how far each size goes
At the full 40 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 8 AWG copper drops 6.11 V (2.55 %), 6 AWG aluminum 6.33 V (2.64 %) and 8 AWG aluminum 10.07 V (4.19 %).
An informational note to 215.2(A) says feeders sized to keep the drop under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit; the lengths below are where each size reaches it at the full rating.
Source: NFPA 70 (NEC) 2023, Table 310.16; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
Copper: one-way length to a 3 % drop, ft
| Size | Length |
|---|---|
| 8 AWG | 118 ft |
| 6 AWG | 187 ft |
| 4 AWG | 298 ft |
| 3 AWG | 375 ft |
| 2 AWG | 473 ft |
| 1 AWG | 597 ft |
Aluminum: one-way length to a 3 % drop, ft
| Size | Length |
|---|---|
| 8 AWG | 72 ft |
| 6 AWG | 114 ft |
| 4 AWG | 181 ft |
| 3 AWG | 228 ft |
| 2 AWG | 288 ft |
| 1 AWG | 363 ft |
A larger wire for distance takes a larger ground wire too, in proportion (250.122(B)); the wire size calculator sizes both.
Ampacity of the sizes around 40 A
Both columns of NEC Table 310.16 for the sizes on either side of the answer. The table assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.
Copper: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 10 AWG | 30 A | 35 A |
| 8 AWG | 40 A | 50 A |
| 6 AWG | 55 A | 65 A |
Aluminum: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 10 AWG | 25 A | 30 A |
| 8 AWG | 35 A | 40 A |
| 6 AWG | 40 A | 50 A |
| 4 AWG | 55 A | 65 A |
Questions
Is 8 AWG wire good for 40 A?
Yes, in NM cable or as single conductors: it carries 40 A at 60 °C and 50 A at 75 °C.
Can 10 AWG wire go on a 40 A breaker?
Not on an ordinary circuit: 240.4(D) protects 10 AWG copper at 30 A at most. Air conditioners are the exception, since Table 240.4(G) sends them to Article 440; the air conditioner calculator applies it.
What size wire for a 40 A subpanel?
The same sizes: 8 AWG copper, or 6 AWG aluminum (8 AWG with 75 °C terminations). A feeder to a separate building runs four wires, with the ground kept apart from the neutral there (250.32(B)(1)). That building's disconnect is rated at least 60 A unless it has no more than two 2-wire circuits (225.39).
What size wire for 40 A at 240 V?
8 AWG copper; at the full 40 A it drops 2.55 % over 100 ft and reaches 3 % at 118 ft.
What size aluminum wire for 40 A?
6 AWG at 60 °C terminals, 8 AWG where every termination is listed and identified for 75 °C conductors, with an 8 AWG aluminum ground wire.
What size ground wire for 40 A?
10 AWG copper or 8 AWG aluminum, from the 60 A row of Table 250.122. Frigidaire's range instructions ask for 8 AWG copper on their 40 A circuit.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 334.80 and 310.15(E), as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- manufacturer installation instructions (Whirlpool, GE, Frigidaire) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Article 625, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, 440.4(B), 440.14 and 240.4(G), as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.