Well Pump Wire Size Calculator: Cable Length, Breaker and Amps
The copper or aluminum cable for a submersible pump at your run, with its breaker, fuses and amps, from Franklin Electric's 2026 tables for its 4-inch single-phase motors.
By Marko Visic, BSc Physics · Updated · Sources below
A 1 hp, 230 V pump 300 ft from the panel takes 12 AWG copper: Franklin's table allows 400 ft on it at a 5 % voltage drop, and 14 AWG stops at 250 ft. Its breaker is 25 A at most, per the NEC as Franklin lists it.
The length is the whole cable, from the service entrance to the motor down the well. Franklin figures each length at the motor's maximum nameplate amps.
Well pump wire size by length
Franklin Electric's AIM Manual lists, for each motor, the longest copper cable at a 5 % voltage drop. The single-phase table covers its 4-inch motors, 2-wire and 3-wire alike. Cells marked † are shaded in Franklin's table (see below), and “none” means the size cannot be used.
Longest copper cable run, ft, at a 5 % drop: Franklin 4-inch single-phase motors, 75 °C cable (shaded cells marked †)
| Motor | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 2 AWG | 1 AWG | 1/0 AWG |
|---|---|---|---|---|---|---|---|---|---|---|
| 1/2 hp, 230 V | 400 ft | 650 ft | 1,020 ft | 1,610 ft | 2,510 ft | 3,880 ft | 4,810 ft | 5,880 ft | 7,170 ft | 8,720 ft |
| 3/4 hp, 230 V | 300 ft | 480 ft | 760 ft | 1,200 ft | 1,870 ft | 2,890 ft | 3,580 ft | 4,370 ft | 5,330 ft | 6,470 ft |
| 1 hp, 230 V | 250 ft | 400 ft | 630 ft | 990 ft | 1,540 ft | 2,380 ft | 2,960 ft | 3,610 ft | 4,410 ft | 5,360 ft |
| 1.5 hp, 230 V | 190 ft | 310 ft | 480 ft | 770 ft | 1,200 ft | 1,870 ft | 2,320 ft | 2,850 ft | 3,500 ft | 4,280 ft |
| 2 hp, 230 V | 150 ft | 250 ft | 390 ft | 620 ft | 970 ft | 1,530 ft | 1,910 ft | 2,360 ft | 2,930 ft | 3,620 ft |
| 3 hp, 230 V | 120 ft † | 190 ft | 300 ft | 470 ft | 750 ft | 1,190 ft | 1,490 ft | 1,850 ft | 2,320 ft | 2,890 ft |
| 5 hp, 230 V | none | 110 ft † | 180 ft | 280 ft | 450 ft | 710 ft | 890 ft | 1,110 ft | 1,390 ft | 1,740 ft |
| 1/2 hp, 115 V | 100 ft | 160 ft | 250 ft | 390 ft | 620 ft | 960 ft | 1,190 ft | 1,460 ft | 1,780 ft | 2,160 ft |
Source: Franklin Electric, AIM Manual (60 Hz submersible systems), 2026 edition.
A 3 % drop instead of 5 %
For a 3 % drop, Franklin multiplies its lengths by 0.6: a 1 hp, 230 V motor on 12 AWG goes from 400 ft to 240 ft. The calculator's drop setting does the same.
Jacketed cable and shaded cells
Franklin's unshaded cells meet the NEC ampacity requirements for single conductors or for jacketed 75 °C cable, in conduit or buried directly; flat molded and web (ribbon) cable count as jacketed. The shaded cells meet them only as single conductors. In the single-phase table two cells are shaded: 3 hp on 14 AWG (120 ft) and 5 hp on 12 AWG (110 ft). With jacketed cable the calculator skips them and moves to the next size. A 5 hp motor cannot use 14 AWG at all.
Aluminum wire
The lengths are for copper. Franklin asks for aluminum two sizes larger than the copper the table calls for, with an oxidation inhibitor on the connections: 12 AWG copper becomes 10 AWG aluminum.
Two sizes in one run
An old buried cable and a new drop cable can share one run. Franklin divides each part's length by that size's maximum and adds the shares; the total must stay at or under one. Its own example is a 3 hp, 230 V motor with 160 ft of 10 AWG already buried (maximum 300 ft, a share of 53.3 %) and 310 ft down the well. 8 AWG there adds 66.0 %, which makes 119.3 %, too much; 6 AWG adds 41.3 %, for 94.7 %. The calculator's steps give the share of one size.
Breaker and fuse sizes
Franklin lists the largest breaker and fuses the NEC allows for each motor, and the sizes typical on submersible pumps. Either size protects the circuit; never go above the NEC value. The sizes are the same for Franklin's standard, “G” and 700 series motors.
Largest per the NEC / typical on submersibles, amps (Franklin AIM, 4-inch single-phase)
| Motor | Breaker | Time-delay fuse | Standard fuse |
|---|---|---|---|
| 1/2 hp, 115 V, 2-wire | 30 A / 30 A | 20 A / 15 A | 35 A / 30 A |
| 1/2 hp, 230 V, 2-wire | 15 A / 15 A | 10 A / 8 A | 20 A / 15 A |
| 3/4 hp, 230 V, 2-wire | 20 A / 20 A | 15 A / 10 A | 25 A / 20 A |
| 1 hp, 230 V, 2-wire | 25 A / 25 A | 20 A / 11 A | 30 A / 25 A |
| 1.5 hp, 230 V, 2-wire | 30 A / 30 A | 20 A / 15 A | 35 A / 35 A |
| 1/2 hp, 115 V, 3-wire | 30 A / 30 A | 20 A / 15 A | 35 A / 30 A |
| 1/2 hp, 230 V, 3-wire | 15 A / 15 A | 10 A / 8 A | 20 A / 15 A |
| 3/4 hp, 230 V, 3-wire | 20 A / 20 A | 15 A / 10 A | 25 A / 20 A |
| 1 hp, 230 V, 3-wire | 25 A / 25 A | 20 A / 11 A | 30 A / 25 A |
| 1.5 hp, 230 V, 3-wire | 30 A / 30 A | 20 A / 15 A | 35 A / 30 A |
| 2 hp, 230 V, 3-wire | 30 A / 30 A | 20 A / 15 A | 30 A / 30 A |
| 3 hp, 230 V, 3-wire | 40 A / 40 A | 30 A / 20 A | 45 A / 45 A |
| 5 hp, 230 V, 3-wire | 60 A / 60 A | 45 A / 30 A | 80 A / 70 A |
Motor amps
Line amps at full load and at the motor's maximum service factor load, the current the cable table is figured at. These are Franklin's standard motors without the “G” suffix; the motor's own nameplate decides.
Line amps of Franklin's standard 4-inch single-phase motors
| Motor | Full load | Maximum load | Service factor |
|---|---|---|---|
| 1/2 hp, 115 V, 2-wire | 10.0 A | 12.0 A | 1.6 |
| 1/2 hp, 230 V, 2-wire | 5.0 A | 6.0 A | 1.6 |
| 3/4 hp, 230 V, 2-wire | 6.8 A | 8.0 A | 1.5 |
| 1 hp, 230 V, 2-wire | 8.2 A | 10.4 A | 1.4 |
| 1.5 hp, 230 V, 2-wire | 10.6 A | 13.1 A | 1.3 |
| 1/2 hp, 115 V, 3-wire | 10.0 A | 12.0 A | 1.6 |
| 1/2 hp, 230 V, 3-wire | 5.0 A | 6.0 A | 1.6 |
| 3/4 hp, 230 V, 3-wire | 6.8 A | 8.0 A | 1.5 |
| 1 hp, 230 V, 3-wire | 8.2 A | 10.4 A | 1.4 |
| 1.5 hp, 230 V, 3-wire | 10.0 A | 11.5 A | 1.3 |
| 2 hp, 230 V, 3-wire | 10.0 A | 13.2 A | 1.25 |
| 3 hp, 230 V, 3-wire | 14.0 A | 17.0 A | 1.15 |
| 5 hp, 230 V, 3-wire | 23.0 A | 27.5 A | 1.15 |
Three-phase and larger motors
The calculator covers Franklin's 4-inch single-phase motors. The AIM Manual also has tables for 4-inch three-phase motors and for 6-inch and 8-inch motors, and other pump makers publish their own.
Questions
What size wire for a 1 hp well pump?
By length: at 230 V, Franklin allows 14 AWG to 250 ft, 12 AWG to 400 ft, 10 AWG to 630 ft and 8 AWG to 990 ft at a 5 % drop.
What size wire for a 1.5 hp well pump?
At 230 V: 14 AWG to 190 ft, 12 AWG to 310 ft, 10 AWG to 480 ft and 8 AWG to 770 ft at a 5 % drop.
What size breaker for a 1.5 hp well pump?
30 A at most for Franklin's 230 V motors, the NEC limit as Franklin lists it, and 30 A is also the typical size.
How many amps does a 1 hp well pump draw?
Franklin's 230 V motor draws 8.2 A at full load and up to 10.4 A at its maximum service factor load.
What wire for a 2 hp well pump 300 ft away?
10 AWG copper: Franklin allows 390 ft on it at 230 V. 12 AWG stops at 250 ft.
Can a well pump use aluminum wire?
Yes, two sizes larger than the copper size, with an oxidation inhibitor on the connections (Franklin): 12 AWG copper becomes 10 AWG aluminum.
Sources
Retrieved .
The values are Franklin Electric's, for its own motors; check your motor's nameplate and its maker's current manual. The methodology page describes how the calculator works and its source.