Horsepower to Amps Calculator: Motor Full-Load Current From the NEC Tables

A motor's full-load current by horsepower and voltage, read from the NEC's motor tables as 430.6(A) requires, never from a formula.

By Marko Visic, BSc Physics · Updated · Sources below

Motor

The motor's rating.

The voltage that supplies it.

A 1 hp single-phase motor draws 8 A at 230 V and 16 A at 115 V by NEC Table 430.248. A 5 hp three-phase motor draws 7.6 A at 460 V (Table 430.250). The NEC sizes a motor's conductors and short-circuit protection from these table currents, not from the nameplate (430.6(A)).

Table current, not a formula

One horsepower is 746 W, the electric horsepower in NIST's conversion tables. At 230 V, that power alone would draw 3.24 A; Table 430.248 gives a 1 hp motor 8 A, 2.47 times as much.

The U.S. Department of Energy's motor fact sheets explain the gap. A motor of a given horsepower is expected to deliver that power in mechanical form, and it takes in more than it delivers: its efficiency is its useful power output over its total power input. A motor is also an inductive load, a cause of low power factor, and a low power factor raises the current for the same power.

The gap is widest on small motors. In Table 430.248's 230 V column it falls row by row from 4.07 times at 1/6 hp to 1.54 times at 10 hp. In Table 430.250's 460 V column it is 2.35 times at 1/2 hp and 1.26 times at 500 hp.

Single-phase motors in the 230 V column: the Table 430.248 full-load current as a multiple of the current of the rated power alone (horsepower × 746 W ÷ 230 V): 1/6 hp 4.07 times (2.2 A against 0.54 A), 1/4 hp 3.58 times (2.9 A against 0.81 A), 1/3 hp 3.33 times (3.6 A against 1.08 A), 1/2 hp 3.02 times (4.9 A against 1.62 A), 3/4 hp 2.84 times (6.9 A against 2.43 A), 1 hp 2.47 times (8 A against 3.24 A), 1 1/2 hp 2.06 times (10 A against 4.87 A), 2 hp 1.85 times (12 A against 6.49 A), 3 hp 1.75 times (17 A against 9.73 A), 5 hp 1.73 times (28 A against 16.22 A), 7 1/2 hp 1.64 times (40 A against 24.33 A), 10 hp 1.54 times (50 A against 32.43 A)1×2×3×4×1/6 hp4.07×1/4 hp3.58×1/3 hp3.33×1/2 hp3.02×3/4 hp2.84×1 hp2.47×1 1/2 hp2.06×2 hp1.85×3 hp1.75×5 hp1.73×7 1/2 hp1.64×10 hp1.54×Table current ÷ current of the rated power alone, at 230 VSingle-phase motors in the 230 V column: the Table 430.248 full-load current as a multiple of the current of the rated power alone (horsepower × 746 W ÷ 230 V): 1/6 hp 4.07 times (2.2 A against 0.54 A), 1/4 hp 3.58 times (2.9 A against 0.81 A), 1/3 hp 3.33 times (3.6 A against 1.08 A), 1/2 hp 3.02 times (4.9 A against 1.62 A), 3/4 hp 2.84 times (6.9 A against 2.43 A), 1 hp 2.47 times (8 A against 3.24 A), 1 1/2 hp 2.06 times (10 A against 4.87 A), 2 hp 1.85 times (12 A against 6.49 A), 3 hp 1.75 times (17 A against 9.73 A), 5 hp 1.73 times (28 A against 16.22 A), 7 1/2 hp 1.64 times (40 A against 24.33 A), 10 hp 1.54 times (50 A against 32.43 A)1×2×3×4×1/6 hp4.07×1/4 hp3.58×1/3 hp3.33×1/2 hp3.02×3/4 hp2.84×1 hp2.47×1 1/2 hp2.06×2 hp1.85×3 hp1.75×5 hp1.73×7 1/2 hp1.64×10 hp1.54×Table current ÷ current of therated power alone, at 230 V
Each single-phase rating in the 230 V column: the table's full-load current over the current of the rated power alone. The dashed line marks the two as equal.

Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); NIST SP 811, Appendix B.8.

Single-phase motors: Table 430.248

Single-phase AC motors from 1/6 hp to 10 hp. In every row the 115 V current is twice the 230 V current.

NEC 2023 Table 430.248, full-load current in amperes

hp115 V200 V208 V230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.143.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1 1/22011.51110
22413.813.212
33419.618.717
55632.230.828
7 1/280464440
1010057.55550

Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission).

Three-phase motors: Table 430.250

Induction motors from 1/2 hp to 500 hp. A dash marks a voltage the table gives no current for: the 115 V column stops at 2 hp, and the 2,300 V column starts at 60 hp. The table also lists synchronous motors; this page and the calculator give the induction motor currents.

NEC 2023 Table 430.250, induction motors, full-load current in amperes

hp115 V200 V208 V230 V460 V575 V2,300 V
1/24.42.52.42.21.10.9no value
3/46.43.73.53.21.61.3no value
18.44.84.64.22.11.7no value
1 1/2126.96.6632.4no value
213.67.87.56.83.42.7no value
3no value1110.69.64.83.9no value
5no value17.516.715.27.66.1no value
7 1/2no value25.324.222119no value
10no value32.230.8281411no value
15no value48.346.2422117no value
20no value62.159.4542722no value
25no value78.274.8683427no value
30no value9288804032no value
40no value1201141045241no value
50no value1501431306552no value
60no value177169154776216
75no value221211192967720
100no value2852732481249926
125no value35934331215612531
150no value41439636018014437
200no value55252848024019249
250no valueno valueno valueno value30224260
300no valueno valueno valueno value36128972
350no valueno valueno valueno value41433683
400no valueno valueno valueno value47738295
450no valueno valueno valueno value515412103
500no valueno valueno valueno value590472118

Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission).

DC motors: Table 430.247

DC motors from 1/4 hp to 200 hp, by rated voltage. DC has no power factor (on DC one volt-ampere is one watt), so there the gap between the two currents comes from the motor's efficiency alone: a 10 hp motor at 240 V is 38 A in the table against 31.08 A for the power alone.

NEC 2023 Table 430.247, full-load current in amperes

hp90 V120 V180 V240 V500 V550 V
1/443.121.6no valueno value
1/35.24.12.62no valueno value
1/26.85.43.42.7no valueno value
3/49.67.64.83.8no valueno value
112.29.56.14.7no valueno value
1 1/2no value13.28.36.6no valueno value
2no value1710.88.5no valueno value
3no value251612.2no valueno value
5no value402720no valueno value
7 1/2no value58no value2913.612.2
10no value76no value381816
15no valueno valueno value552724
20no valueno valueno value723431
25no valueno valueno value894338
30no valueno valueno value1065146
40no valueno valueno value1406761
50no valueno valueno value1738375
60no valueno valueno value2069990
75no valueno valueno value255123111
100no valueno valueno value341164148
125no valueno valueno value425205185
150no valueno valueno value506246222
200no valueno valueno value675330294

Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); U.S. EIA Glossary (power, power factor).

Which voltage column

The columns are rated motor voltages. The tables' notes give the column for each system voltage, which is what the calculator asks for; Table 430.248 has the first four:

System voltage and the table column it takes

SystemColumn
110–120 V115 V
200 V200 V
208 V208 V
220–240 V230 V
440–480 V460 V
550–600 V575 V
2,300–2,400 V2,300 V

208 V is not 230 V: a 5 hp three-phase motor is 16.7 A in the 208 V column and 15.2 A in the 230 V column. A house's 120/240 V supply is single-phase in ANSI C84.1's list of system voltages, as North Carolina's rule R8-17 prints it, so a 240 V motor there reads Table 430.248. Table 430.249 is for two-phase motors, a different system, and the calculator leaves it out.

Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); NCUC Rule R8-17 (ANSI C84.1 voltages).

Nameplate current and motor circuits

430.6(A) takes the table values, instead of the current marked on the motor's nameplate, for the conductors' ampacity, the switch ratings and the branch-circuit short-circuit and ground-fault protection. Separate overload protection follows the nameplate current, and the rule uses the nameplate current for low-speed, high-torque and multispeed motors too.

This site does not size motor conductors, overload protection or the breaker or fuse yet: the NEC's rules for them are still being checked against the 2023 text, so the calculator stops at the current (not covered yet). For a motor's measured power, the kilowatts to amps calculator and the three phase calculator convert with its power factor.

Questions

How many amps does a 1 hp motor draw?

Single-phase: 16 A at 115 V and 8 A at 230 V (Table 430.248). Three-phase: 4.2 A at 230 V and 2.1 A at 460 V (Table 430.250). A 1/2 hp single-phase motor: 9.8 A at 115 V and 4.9 A at 230 V.

How many amps is a 5 hp motor?

Single-phase at 230 V: 28 A. Three-phase: 15.2 A at 230 V, 16.7 A at 208 V and 7.6 A at 460 V.

What is the formula for horsepower to amps?

With the full-load efficiency and power factor from the motor's nameplate data: amps = hp × 746 ÷ (volts × efficiency × power factor), divided by √3 more on three-phase. Without them it gives the current of the rated power alone, below the table's. For a motor circuit, 430.6(A) takes the table current instead.

Is 240 V single-phase or two-phase?

Single-phase: 120/240 V is a single-phase system in ANSI C84.1's list (North Carolina rule R8-17). A 240 V motor in a house reads the 230 V column of Table 430.248, not the two-phase Table 430.249.

Nameplate amps or table amps?

Both, for different parts of the circuit. 430.6(A) takes the table current for the conductors, the switches and the short-circuit and ground-fault protection, and the nameplate current for separate overload protection.

What size wire does a motor need?

The table current is where that sizing starts, but this site does not yet turn it into a wire size or a breaker: the NEC's rules for motor conductors and protection are still being checked against the 2023 text.

Sources

The methodology page sets out each step and each source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.