Horsepower to Amps Calculator: Motor Full-Load Current From the NEC Tables
A motor's full-load current by horsepower and voltage, read from the NEC's motor tables as 430.6(A) requires, never from a formula.
By Marko Visic, BSc Physics · Updated · Sources below
A 1 hp single-phase motor draws 8 A at 230 V and 16 A at 115 V by NEC Table 430.248. A 5 hp three-phase motor draws 7.6 A at 460 V (Table 430.250). The NEC sizes a motor's conductors and short-circuit protection from these table currents, not from the nameplate (430.6(A)).
Table current, not a formula
One horsepower is 746 W, the electric horsepower in NIST's conversion tables. At 230 V, that power alone would draw 3.24 A; Table 430.248 gives a 1 hp motor 8 A, 2.47 times as much.
The U.S. Department of Energy's motor fact sheets explain the gap. A motor of a given horsepower is expected to deliver that power in mechanical form, and it takes in more than it delivers: its efficiency is its useful power output over its total power input. A motor is also an inductive load, a cause of low power factor, and a low power factor raises the current for the same power.
The gap is widest on small motors. In Table 430.248's 230 V column it falls row by row from 4.07 times at 1/6 hp to 1.54 times at 10 hp. In Table 430.250's 460 V column it is 2.35 times at 1/2 hp and 1.26 times at 500 hp.
Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); NIST SP 811, Appendix B.8.
Single-phase motors: Table 430.248
Single-phase AC motors from 1/6 hp to 10 hp. In every row the 115 V current is twice the 230 V current.
NEC 2023 Table 430.248, full-load current in amperes
| hp | 115 V | 200 V | 208 V | 230 V |
|---|---|---|---|---|
| 1/6 | 4.4 | 2.5 | 2.4 | 2.2 |
| 1/4 | 5.8 | 3.3 | 3.2 | 2.9 |
| 1/3 | 7.2 | 4.1 | 4 | 3.6 |
| 1/2 | 9.8 | 5.6 | 5.4 | 4.9 |
| 3/4 | 13.8 | 7.9 | 7.6 | 6.9 |
| 1 | 16 | 9.2 | 8.8 | 8 |
| 1 1/2 | 20 | 11.5 | 11 | 10 |
| 2 | 24 | 13.8 | 13.2 | 12 |
| 3 | 34 | 19.6 | 18.7 | 17 |
| 5 | 56 | 32.2 | 30.8 | 28 |
| 7 1/2 | 80 | 46 | 44 | 40 |
| 10 | 100 | 57.5 | 55 | 50 |
Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission).
Three-phase motors: Table 430.250
Induction motors from 1/2 hp to 500 hp. A dash marks a voltage the table gives no current for: the 115 V column stops at 2 hp, and the 2,300 V column starts at 60 hp. The table also lists synchronous motors; this page and the calculator give the induction motor currents.
NEC 2023 Table 430.250, induction motors, full-load current in amperes
| hp | 115 V | 200 V | 208 V | 230 V | 460 V | 575 V | 2,300 V |
|---|---|---|---|---|---|---|---|
| 1/2 | 4.4 | 2.5 | 2.4 | 2.2 | 1.1 | 0.9 | no value |
| 3/4 | 6.4 | 3.7 | 3.5 | 3.2 | 1.6 | 1.3 | no value |
| 1 | 8.4 | 4.8 | 4.6 | 4.2 | 2.1 | 1.7 | no value |
| 1 1/2 | 12 | 6.9 | 6.6 | 6 | 3 | 2.4 | no value |
| 2 | 13.6 | 7.8 | 7.5 | 6.8 | 3.4 | 2.7 | no value |
| 3 | no value | 11 | 10.6 | 9.6 | 4.8 | 3.9 | no value |
| 5 | no value | 17.5 | 16.7 | 15.2 | 7.6 | 6.1 | no value |
| 7 1/2 | no value | 25.3 | 24.2 | 22 | 11 | 9 | no value |
| 10 | no value | 32.2 | 30.8 | 28 | 14 | 11 | no value |
| 15 | no value | 48.3 | 46.2 | 42 | 21 | 17 | no value |
| 20 | no value | 62.1 | 59.4 | 54 | 27 | 22 | no value |
| 25 | no value | 78.2 | 74.8 | 68 | 34 | 27 | no value |
| 30 | no value | 92 | 88 | 80 | 40 | 32 | no value |
| 40 | no value | 120 | 114 | 104 | 52 | 41 | no value |
| 50 | no value | 150 | 143 | 130 | 65 | 52 | no value |
| 60 | no value | 177 | 169 | 154 | 77 | 62 | 16 |
| 75 | no value | 221 | 211 | 192 | 96 | 77 | 20 |
| 100 | no value | 285 | 273 | 248 | 124 | 99 | 26 |
| 125 | no value | 359 | 343 | 312 | 156 | 125 | 31 |
| 150 | no value | 414 | 396 | 360 | 180 | 144 | 37 |
| 200 | no value | 552 | 528 | 480 | 240 | 192 | 49 |
| 250 | no value | no value | no value | no value | 302 | 242 | 60 |
| 300 | no value | no value | no value | no value | 361 | 289 | 72 |
| 350 | no value | no value | no value | no value | 414 | 336 | 83 |
| 400 | no value | no value | no value | no value | 477 | 382 | 95 |
| 450 | no value | no value | no value | no value | 515 | 412 | 103 |
| 500 | no value | no value | no value | no value | 590 | 472 | 118 |
Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission).
DC motors: Table 430.247
DC motors from 1/4 hp to 200 hp, by rated voltage. DC has no power factor (on DC one volt-ampere is one watt), so there the gap between the two currents comes from the motor's efficiency alone: a 10 hp motor at 240 V is 38 A in the table against 31.08 A for the power alone.
NEC 2023 Table 430.247, full-load current in amperes
| hp | 90 V | 120 V | 180 V | 240 V | 500 V | 550 V |
|---|---|---|---|---|---|---|
| 1/4 | 4 | 3.1 | 2 | 1.6 | no value | no value |
| 1/3 | 5.2 | 4.1 | 2.6 | 2 | no value | no value |
| 1/2 | 6.8 | 5.4 | 3.4 | 2.7 | no value | no value |
| 3/4 | 9.6 | 7.6 | 4.8 | 3.8 | no value | no value |
| 1 | 12.2 | 9.5 | 6.1 | 4.7 | no value | no value |
| 1 1/2 | no value | 13.2 | 8.3 | 6.6 | no value | no value |
| 2 | no value | 17 | 10.8 | 8.5 | no value | no value |
| 3 | no value | 25 | 16 | 12.2 | no value | no value |
| 5 | no value | 40 | 27 | 20 | no value | no value |
| 7 1/2 | no value | 58 | no value | 29 | 13.6 | 12.2 |
| 10 | no value | 76 | no value | 38 | 18 | 16 |
| 15 | no value | no value | no value | 55 | 27 | 24 |
| 20 | no value | no value | no value | 72 | 34 | 31 |
| 25 | no value | no value | no value | 89 | 43 | 38 |
| 30 | no value | no value | no value | 106 | 51 | 46 |
| 40 | no value | no value | no value | 140 | 67 | 61 |
| 50 | no value | no value | no value | 173 | 83 | 75 |
| 60 | no value | no value | no value | 206 | 99 | 90 |
| 75 | no value | no value | no value | 255 | 123 | 111 |
| 100 | no value | no value | no value | 341 | 164 | 148 |
| 125 | no value | no value | no value | 425 | 205 | 185 |
| 150 | no value | no value | no value | 506 | 246 | 222 |
| 200 | no value | no value | no value | 675 | 330 | 294 |
Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); U.S. EIA Glossary (power, power factor).
Which voltage column
The columns are rated motor voltages. The tables' notes give the column for each system voltage, which is what the calculator asks for; Table 430.248 has the first four:
System voltage and the table column it takes
| System | Column |
|---|---|
| 110–120 V | 115 V |
| 200 V | 200 V |
| 208 V | 208 V |
| 220–240 V | 230 V |
| 440–480 V | 460 V |
| 550–600 V | 575 V |
| 2,300–2,400 V | 2,300 V |
208 V is not 230 V: a 5 hp three-phase motor is 16.7 A in the 208 V column and 15.2 A in the 230 V column. A house's 120/240 V supply is single-phase in ANSI C84.1's list of system voltages, as North Carolina's rule R8-17 prints it, so a 240 V motor there reads Table 430.248. Table 430.249 is for two-phase motors, a different system, and the calculator leaves it out.
Source: NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission); NCUC Rule R8-17 (ANSI C84.1 voltages).
Nameplate current and motor circuits
430.6(A) takes the table values, instead of the current marked on the motor's nameplate, for the conductors' ampacity, the switch ratings and the branch-circuit short-circuit and ground-fault protection. Separate overload protection follows the nameplate current, and the rule uses the nameplate current for low-speed, high-torque and multispeed motors too.
This site does not size motor conductors, overload protection or the breaker or fuse yet: the NEC's rules for them are still being checked against the 2023 text, so the calculator stops at the current (not covered yet). For a motor's measured power, the kilowatts to amps calculator and the three phase calculator convert with its power factor.
Questions
How many amps does a 1 hp motor draw?
Single-phase: 16 A at 115 V and 8 A at 230 V (Table 430.248). Three-phase: 4.2 A at 230 V and 2.1 A at 460 V (Table 430.250). A 1/2 hp single-phase motor: 9.8 A at 115 V and 4.9 A at 230 V.
How many amps is a 5 hp motor?
Single-phase at 230 V: 28 A. Three-phase: 15.2 A at 230 V, 16.7 A at 208 V and 7.6 A at 460 V.
What is the formula for horsepower to amps?
With the full-load efficiency and power factor from the motor's nameplate data: amps = hp × 746 ÷ (volts × efficiency × power factor), divided by √3 more on three-phase. Without them it gives the current of the rated power alone, below the table's. For a motor circuit, 430.6(A) takes the table current instead.
Is 240 V single-phase or two-phase?
Single-phase: 120/240 V is a single-phase system in ANSI C84.1's list (North Carolina rule R8-17). A 240 V motor in a house reads the 230 V column of Table 430.248, not the two-phase Table 430.249.
Nameplate amps or table amps?
Both, for different parts of the circuit. 430.6(A) takes the table current for the conductors, the switches and the short-circuit and ground-fault protection, and the nameplate current for separate overload protection.
What size wire does a motor need?
The table current is where that sizing starts, but this site does not yet turn it into a wire size or a breaker: the NEC's rules for motor conductors and protection are still being checked against the 2023 text.
Sources
- NFPA 70 (NEC) 2023, Tables 430.247–430.250 (NFPA 2023 Second Draft; Eaton reprint with NFPA permission) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, sections as cited — retrieved Oct 2026
- NIST SP 811, Appendix B.8 — retrieved Oct 2026
- U.S. DOE fact sheet DOE/GO-10097-517, Determining Electric Motor Load and Efficiency — retrieved Nov 2026
- U.S. DOE fact sheet DOE/GO-10096-286, Reducing Power Factor Cost — retrieved Nov 2026
- U.S. EIA Glossary (power, power factor) — retrieved Nov 2026
- NCUC Rule R8-17 (ANSI C84.1 voltages) — retrieved Oct 2026
The methodology page sets out each step and each source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.