Wire Size for 15 Amp Breaker: 14 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
A 15 A breaker takes 14 AWG copper or 12 AWG aluminum. Table 310.16 lists 14 AWG copper at 20 A in the 75 °C column, but 240.4(D) holds it to a 15 A breaker, so the breaker limit sets the answer whatever the terminals.
The ground wire is 14 AWG copper or 12 AWG aluminum (Table 250.122). At 120 V the full 15 A drops 3 % in 39 ft of 14 AWG copper, so longer runs go up a size.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint).
Why 14 AWG stops at 15 A
Table 310.16 gives a conductor's ampacity; 240.4(D) then caps the breaker or fuse on the small sizes, whatever the table says. For 14 AWG copper the cap is 15 A, while the table lists 15 A at 60 °C, 20 A at 75 °C and 25 A at 90 °C.
That is why the terminal rating, which decides the answer at larger ratings under 110.14(C), changes nothing here: in every column the cap is the tighter limit. In NM cable, 334.80 holds 14 AWG to its 60 °C value, which is the 15 A of the breaker anyway.
Table 310.16 ampacity and the largest breaker under 240.4(D), A
| Size | 60 °C | 75 °C | 90 °C | Breaker |
|---|---|---|---|---|
| 14 AWG Cu | 15 A | 20 A | 25 A | 15 A |
| 12 AWG Cu | 20 A | 25 A | 30 A | 20 A |
| 10 AWG Cu | 30 A | 35 A | 40 A | 30 A |
| 12 AWG Al | 15 A | 20 A | 25 A | 15 A |
| 10 AWG Al | 25 A | 30 A | 35 A | 25 A |
12 AWG on a 15 A breaker
240.4(D) limits the breaker on each wire size, never the wire size on a breaker, so a larger wire on a 15 A breaker is always allowed. 12 AWG copper may carry up to 20 A under 240.4(D), and on a 15 A breaker it simply runs farther: at 120 V the full 15 A reaches 3 % at 62 ft on 12 AWG, against 39 ft on 14 AWG.
How far 15 A goes at 120 V
For feeders, an informational note to 215.2(A) says that conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit; the lengths below use the same percentage.
At the full 15 A, single-phase with the conductors at 75 °C, the drop reaches 3 % at these one-way lengths. A 120 V circuit gets half the distance of a 240 V one on the same wire, and a load below 15 A drops less in proportion.
Source: NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
Copper: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 14 AWG | 39 ft | 78 ft |
| 12 AWG | 62 ft | 124 ft |
| 10 AWG | 99 ft | 198 ft |
| 8 AWG | 157 ft | 314 ft |
Aluminum: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 12 AWG | 38 ft | 75 ft |
| 10 AWG | 60 ft | 120 ft |
| 8 AWG | 95 ft | 191 ft |
| 6 AWG | 152 ft | 303 ft |
The wire size calculator takes your length and load and grows the ground wire with a larger circuit wire, as 250.122(B) requires.
Aluminum and copper-clad aluminum
Under 240.4(D), 12 AWG aluminum is held like 14 AWG copper: a 15 A breaker at most, though Table 310.16 lists it at 20 A at 75 °C. 14 AWG copper-clad aluminum is held to 10 A, and only where continuous loads stay at 8 A or less, so it does not reach a 15 A circuit.
The 15 A receptacle
The 5-15R is rated 15 A at 125 V, 2-pole 3-wire grounding: one hot, a neutral and a ground, each landing on the circuit's 14 AWG copper.
Some plug-in hot tubs run on such a circuit: the Bullfrog A Series and Marquis Elite list a 15 A circuit at 120 V. The hot tub calculator covers their circuits and the larger 240 V ones.
Questions
What gauge wire for 15 A?
14 AWG copper or 12 AWG aluminum, the smallest sizes 240.4(D) allows on a 15 A breaker. Past 39 ft at 120 V the full load drops more than the 3 % of the 215.2(A) note on 14 AWG; 12 AWG holds it to 62 ft.
Can I use 12 AWG wire on a 15 A circuit?
Yes. A larger wire is always allowed; 240.4(D) only limits how large a breaker may protect each size.
What size wire for 15 A at 240 V?
The same 14 AWG copper. At 240 V the full 15 A reaches 3 % at 78 ft, twice the 120 V distance.
What size ground wire for 15 A?
14 AWG copper or 12 AWG aluminum, from the 15 A row of Table 250.122.
What size NM cable for 15 A?
14 AWG copper NM cable, which 334.80 holds to the 60 °C column: 15 A, the breaker's rating.
Can 14 AWG wire go on a bigger breaker?
Not on an ordinary circuit: 240.4(D) protects 14 AWG copper at 15 A at most. The wire size for 20 amp guide covers the next breaker up.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 334.80 and 310.15(E), as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- Hubbell NEMA configuration chart and Hubbell and Leviton device specifications (NEMA WD 6) — retrieved Nov 2026
- Hot Spring, Bullfrog and Marquis pre-delivery/owner manuals (2026) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.