Wire Size for 15 Amp Breaker: 14 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 15 A breaker takes 14 AWG copper or 12 AWG aluminum. Table 310.16 lists 14 AWG copper at 20 A in the 75 °C column, but 240.4(D) holds it to a 15 A breaker, so the breaker limit sets the answer whatever the terminals.

The ground wire is 14 AWG copper or 12 AWG aluminum (Table 250.122). At 120 V the full 15 A drops 3 % in 39 ft of 14 AWG copper, so longer runs go up a size.

Allowable ampacity in NEC Table 310.16 of the small conductors that 240.4(D) limits, against the largest breaker 240.4(D) allows on each: 14 AWG copper: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 12 AWG copper: 20 A at 60 °C and 25 A at 75 °C, breaker at most 20 A; 10 AWG copper: 30 A at 60 °C and 35 A at 75 °C, breaker at most 30 A; 12 AWG aluminum: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 10 AWG aluminum: 25 A at 60 °C and 30 A at 75 °C, breaker at most 25 A.Largest breaker, 240.4(D)Table 310.16 at 60 °C and 75 °C0 A10 A20 A30 A40 A15 A breakerAmperes (size on the left)Copper14 AWG15 A12 AWG20 A10 AWG30 AAluminum12 AWG15 A10 AWG25 AAllowable ampacity in NEC Table 310.16 of the small conductors that 240.4(D) limits, against the largest breaker 240.4(D) allows on each: 14 AWG copper: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 12 AWG copper: 20 A at 60 °C and 25 A at 75 °C, breaker at most 20 A; 10 AWG copper: 30 A at 60 °C and 35 A at 75 °C, breaker at most 30 A; 12 AWG aluminum: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 10 AWG aluminum: 25 A at 60 °C and 30 A at 75 °C, breaker at most 25 A.Largest breaker, 240.4(D)Table 310.16 at 60 °C and 75 °C0 A20 A40 A15 A breakerAmperes (size on the left)Copper14 AWG12 AWG10 AWGAluminum12 AWG10 AWG
The small conductors 240.4(D) limits: each bar ends at the largest breaker it allows, the dots show its Table 310.16 ampacity at 60 °C (open) and 75 °C (filled). 14 AWG copper and 12 AWG aluminum stop at 15 A.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint).

Why 14 AWG stops at 15 A

Table 310.16 gives a conductor's ampacity; 240.4(D) then caps the breaker or fuse on the small sizes, whatever the table says. For 14 AWG copper the cap is 15 A, while the table lists 15 A at 60 °C, 20 A at 75 °C and 25 A at 90 °C.

That is why the terminal rating, which decides the answer at larger ratings under 110.14(C), changes nothing here: in every column the cap is the tighter limit. In NM cable, 334.80 holds 14 AWG to its 60 °C value, which is the 15 A of the breaker anyway.

Table 310.16 ampacity and the largest breaker under 240.4(D), A

Size60 °C75 °C90 °CBreaker
14 AWG Cu15 A20 A25 A15 A
12 AWG Cu20 A25 A30 A20 A
10 AWG Cu30 A35 A40 A30 A
12 AWG Al15 A20 A25 A15 A
10 AWG Al25 A30 A35 A25 A

12 AWG on a 15 A breaker

240.4(D) limits the breaker on each wire size, never the wire size on a breaker, so a larger wire on a 15 A breaker is always allowed. 12 AWG copper may carry up to 20 A under 240.4(D), and on a 15 A breaker it simply runs farther: at 120 V the full 15 A reaches 3 % at 62 ft on 12 AWG, against 39 ft on 14 AWG.

How far 15 A goes at 120 V

For feeders, an informational note to 215.2(A) says that conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit; the lengths below use the same percentage.

At the full 15 A, single-phase with the conductors at 75 °C, the drop reaches 3 % at these one-way lengths. A 120 V circuit gets half the distance of a 240 V one on the same wire, and a load below 15 A drops less in proportion.

One-way length at which 15 A drops 3 % on copper conductors at 75 °C, single-phase: 14 AWG 39 ft at 120 V and 78 ft at 240 V; 12 AWG 62 ft at 120 V and 124 ft at 240 V; 10 AWG 99 ft at 120 V and 198 ft at 240 V; 8 AWG 157 ft at 120 V and 314 ft at 240 V.120 V240 V0100200300One-way length to a 3 % drop, ft (copper)14 AWG39 ft78 ft12 AWG62 ft124 ft10 AWG99 ft198 ft8 AWG157 ft314 ftOne-way length at which 15 A drops 3 % on copper conductors at 75 °C, single-phase: 14 AWG 39 ft at 120 V and 78 ft at 240 V; 12 AWG 62 ft at 120 V and 124 ft at 240 V; 10 AWG 99 ft at 120 V and 198 ft at 240 V; 8 AWG 157 ft at 120 V and 314 ft at 240 V.120 V240 V0200One-way length to a 3 % drop, ft (copper)14 AWG39 ft78 ft12 AWG62 ft124 ft10 AWG99 ft198 ft8 AWG157 ft314 ft
One-way length at which 15 A drops 3 % on copper, at 120 V (gray) and 240 V (copper).

Source: NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

Size120 V240 V
14 AWG39 ft78 ft
12 AWG62 ft124 ft
10 AWG99 ft198 ft
8 AWG157 ft314 ft

Aluminum: one-way length to a 3 % drop, ft

Size120 V240 V
12 AWG38 ft75 ft
10 AWG60 ft120 ft
8 AWG95 ft191 ft
6 AWG152 ft303 ft

The wire size calculator takes your length and load and grows the ground wire with a larger circuit wire, as 250.122(B) requires.

Aluminum and copper-clad aluminum

Under 240.4(D), 12 AWG aluminum is held like 14 AWG copper: a 15 A breaker at most, though Table 310.16 lists it at 20 A at 75 °C. 14 AWG copper-clad aluminum is held to 10 A, and only where continuous loads stay at 8 A or less, so it does not reach a 15 A circuit.

The 15 A receptacle

The 5-15R is rated 15 A at 125 V, 2-pole 3-wire grounding: one hot, a neutral and a ground, each landing on the circuit's 14 AWG copper.

Some plug-in hot tubs run on such a circuit: the Bullfrog A Series and Marquis Elite list a 15 A circuit at 120 V. The hot tub calculator covers their circuits and the larger 240 V ones.

Questions

What gauge wire for 15 A?

14 AWG copper or 12 AWG aluminum, the smallest sizes 240.4(D) allows on a 15 A breaker. Past 39 ft at 120 V the full load drops more than the 3 % of the 215.2(A) note on 14 AWG; 12 AWG holds it to 62 ft.

Can I use 12 AWG wire on a 15 A circuit?

Yes. A larger wire is always allowed; 240.4(D) only limits how large a breaker may protect each size.

What size wire for 15 A at 240 V?

The same 14 AWG copper. At 240 V the full 15 A reaches 3 % at 78 ft, twice the 120 V distance.

What size ground wire for 15 A?

14 AWG copper or 12 AWG aluminum, from the 15 A row of Table 250.122.

What size NM cable for 15 A?

14 AWG copper NM cable, which 334.80 holds to the 60 °C column: 15 A, the breaker's rating.

Can 14 AWG wire go on a bigger breaker?

Not on an ordinary circuit: 240.4(D) protects 14 AWG copper at 15 A at most. The wire size for 20 amp guide covers the next breaker up.