Wire Size for 125 Amp Service or Subpanel: 2 or 1 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
A 125 A dwelling service takes 2 AWG copper or 1/0 AWG aluminum, from NEC Table 310.12. A 125 A feeder to a subpanel takes 1 AWG copper or 2/0 AWG aluminum, from the 75 °C column of Table 310.16, which 110.14(C)(1)(b) sets above 100 A.
The feeder's ground wire is 6 AWG copper or 4 AWG aluminum (Table 250.122); a service with 2 AWG copper takes an 8 AWG copper grounding electrode conductor (Table 250.66).
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793); NFPA 70 (NEC) 2023, Table 310.12.
Service or feeder: which table
Table 310.12 is for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit in a two-family or multifamily building. Section 310.12 lets those conductors have an ampacity of not less than 83 % of the rating, 103.75 A for 125 A, and the table lists 2 AWG copper or 1/0 AWG aluminum.
Every other 125 A feeder, such as one to a subpanel, is sized from Table 310.16. Above 100 A, 110.14(C)(1)(b) uses the 75 °C column, where 1 AWG copper carries 130 A and 2/0 AWG aluminum 135 A.
The conductors for 125 A, by use
| Use | Copper | Aluminum |
|---|---|---|
| Dwelling service, Table 310.12 | 2 AWG | 1/0 AWG |
| Feeder, Table 310.16 at 75 °C | 1 AWG | 2/0 AWG |
| Feeder whose load fits, 240.4(B) | 2 AWG | 1/0 AWG |
| Feeder ground wire, Table 250.122 | 6 AWG | 4 AWG |
The service sizes on a feeder, under 240.4(B)
At 75 °C, 2 AWG copper carries 115 A and 1/0 AWG aluminum 120 A. Neither is a standard rating of Table 240.6(A), so 240.4(B) lets the next higher standard rating, 125 A, protect them, up to 800 A, on a feeder that does not supply more than one receptacle for cord-and-plug-connected portable loads. They are the Table 310.12 sizes again, reached by a different rule.
The catch is the load: under 215.2(A) the feeder carries its noncontinuous load plus 125 % of its continuous load, and that sum must fit the smaller wire, 115 A on 2 AWG copper. A subpanel whose calculated load is that or less can use them; a fully loaded 125 A feeder cannot.
Ground wires at 125 A
A feeder carries an equipment grounding conductor sized by its breaker: a 125 A breaker falls in the row of Table 250.122 for breakers up to 200 A, so 6 AWG copper or 4 AWG aluminum. A service has a grounding electrode conductor instead, sized by its largest service conductor in Table 250.66: 8 AWG copper or 6 AWG aluminum for 2 AWG copper service conductors. The values are those of NFPA's 2020 grounding fact sheet. The ground wire calculator finds both for any rating.
A 125 A subpanel in a detached building
A feeder to a separate building runs four wires: two hots, the neutral and an equipment grounding conductor, and at that building the neutral stays off the grounding conductor and the electrode (250.32(B)(1)). Its disconnecting means is rated at least 100 A where the building is a one-family dwelling and 60 A for a garage or other building (225.39). The garage subpanel calculator sizes such a feeder and gives its burial depth.
125 A over a long run
At the full 125 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 1 AWG copper drops 3.77 V (1.57 %), 2/0 AWG aluminum 3.90 V (1.63 %), 2 AWG copper 4.75 V (1.98 %) and 1/0 AWG aluminum 4.92 V (2.05 %).
For feeders, an informational note to 215.2(A) says conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, Table 310.12; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
Copper: one-way length to a 3 % drop, ft
| Size | Length |
|---|---|
| 2 AWG | 152 ft |
| 1 AWG | 191 ft |
| 1/0 AWG | 241 ft |
| 2/0 AWG | 304 ft |
| 3/0 AWG | 383 ft |
| 4/0 AWG | 483 ft |
Aluminum: one-way length to a 3 % drop, ft
| Size | Length |
|---|---|
| 1/0 AWG | 146 ft |
| 2/0 AWG | 185 ft |
| 3/0 AWG | 233 ft |
| 4/0 AWG | 293 ft |
| 250 kcmil | 347 ft |
| 300 kcmil | 416 ft |
The wire size calculator finds the size for your length and load and grows the ground wire with it (250.122(B)).
Ampacity of the sizes around 125 A
From the service sizes to one past the feeder sizes, in both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.
Copper: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 3 AWG | 85 A | 100 A |
| 2 AWG | 95 A | 115 A |
| 1 AWG | 110 A | 130 A |
| 1/0 AWG | 125 A | 150 A |
Aluminum: Table 310.16 ampacity, A
| Size | 60 °C | 75 °C |
|---|---|---|
| 1 AWG | 85 A | 100 A |
| 1/0 AWG | 100 A | 120 A |
| 2/0 AWG | 115 A | 135 A |
| 3/0 AWG | 130 A | 155 A |
Questions
What size wire for a 125 A service?
2 AWG copper or 1/0 AWG aluminum for a 120/240 V dwelling service (Table 310.12), with an 8 AWG copper or 6 AWG aluminum grounding electrode conductor (Table 250.66).
What size wire for a 125 A subpanel?
1 AWG copper or 2/0 AWG aluminum at 75 °C, with a 6 AWG copper or 4 AWG aluminum ground wire; 2 AWG copper or 1/0 AWG aluminum where the subpanel's calculated load fits them (240.4(B)).
What size aluminum wire for 125 A?
1/0 AWG for a dwelling service, 2/0 AWG for a feeder at 75 °C, and 1/0 AWG on a feeder whose load stays within 120 A.
What size ground wire for 125 A?
6 AWG copper or 4 AWG aluminum with a feeder (Table 250.122); an 8 AWG copper grounding electrode conductor for a service with 2 AWG copper (Table 250.66).
What size wire for a 125 A subpanel 100 ft away?
At the full 125 A, 1 AWG copper drops 1.57 % and 2/0 AWG aluminum 1.63 %, inside the 3 % of the 215.2(A) note.
Sources
- NFPA 70 (NEC) 2023, Table 310.12 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.