Wire Size for 125 Amp Service or Subpanel: 2 or 1 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 125 A dwelling service takes 2 AWG copper or 1/0 AWG aluminum, from NEC Table 310.12. A 125 A feeder to a subpanel takes 1 AWG copper or 2/0 AWG aluminum, from the 75 °C column of Table 310.16, which 110.14(C)(1)(b) sets above 100 A.

The feeder's ground wire is 6 AWG copper or 4 AWG aluminum (Table 250.122); a service with 2 AWG copper takes an 8 AWG copper grounding electrode conductor (Table 250.66).

Allowable ampacity, NEC Table 310.16, of the sizes around 125 A in the 60 °C and 75 °C columns: 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 2 AWG copper 95 A at 60 °C, 115 A at 75 °C; 1 AWG copper 110 A at 60 °C, 130 A at 75 °C; 1/0 AWG copper 125 A at 60 °C, 150 A at 75 °C; 1 AWG aluminum 85 A at 60 °C, 100 A at 75 °C; 1/0 AWG aluminum 100 A at 60 °C, 120 A at 75 °C; 2/0 AWG aluminum 115 A at 60 °C, 135 A at 75 °C; 3/0 AWG aluminum 130 A at 60 °C, 155 A at 75 °C. A 125 A feeder takes 1 AWG copper or 2/0 AWG aluminum at 75 °C; a dwelling service may stop at 103.75 A, at 2 AWG copper or 1/0 AWG aluminum (Table 310.12).60 °C column75 °C column, the one above 100 A125 A breaker70 A80 A90 A100 A110 A120 A130 A140 A150 A160 AAmpacity (size on the left)Copper3 AWG85 A100 A2 AWG95 A115 A1 AWG110 A130 A1/0 AWG125 A150 AAluminum1 AWG85 A100 A1/0 AWG100 A120 A2/0 AWG115 A135 A3/0 AWG130 A155 AAllowable ampacity, NEC Table 310.16, of the sizes around 125 A in the 60 °C and 75 °C columns: 3 AWG copper 85 A at 60 °C, 100 A at 75 °C; 2 AWG copper 95 A at 60 °C, 115 A at 75 °C; 1 AWG copper 110 A at 60 °C, 130 A at 75 °C; 1/0 AWG copper 125 A at 60 °C, 150 A at 75 °C; 1 AWG aluminum 85 A at 60 °C, 100 A at 75 °C; 1/0 AWG aluminum 100 A at 60 °C, 120 A at 75 °C; 2/0 AWG aluminum 115 A at 60 °C, 135 A at 75 °C; 3/0 AWG aluminum 130 A at 60 °C, 155 A at 75 °C. A 125 A feeder takes 1 AWG copper or 2/0 AWG aluminum at 75 °C; a dwelling service may stop at 103.75 A, at 2 AWG copper or 1/0 AWG aluminum (Table 310.12).60 °C column75 °C column, the one above 100 A125 A breaker90 A110 A130 A150 AAmpacity (size on the left)Copper3 AWG2 AWG1 AWG1/0 AWGAluminum1 AWG1/0 AWG2/0 AWG3/0 AWG
The ampacity of the sizes around 125 A in the 60 °C column (open dots) and the 75 °C column (filled). A feeder needs a size that reaches 125 A at 75 °C. In the shaded band, from 83 % of the rating (103.75 A) up, a dwelling service may stop under Table 310.12.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793); NFPA 70 (NEC) 2023, Table 310.12.

Service or feeder: which table

Table 310.12 is for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit in a two-family or multifamily building. Section 310.12 lets those conductors have an ampacity of not less than 83 % of the rating, 103.75 A for 125 A, and the table lists 2 AWG copper or 1/0 AWG aluminum.

Every other 125 A feeder, such as one to a subpanel, is sized from Table 310.16. Above 100 A, 110.14(C)(1)(b) uses the 75 °C column, where 1 AWG copper carries 130 A and 2/0 AWG aluminum 135 A.

The conductors for 125 A, by use

UseCopperAluminum
Dwelling service, Table 310.122 AWG1/0 AWG
Feeder, Table 310.16 at 75 °C1 AWG2/0 AWG
Feeder whose load fits, 240.4(B)2 AWG1/0 AWG
Feeder ground wire, Table 250.1226 AWG4 AWG

The service sizes on a feeder, under 240.4(B)

At 75 °C, 2 AWG copper carries 115 A and 1/0 AWG aluminum 120 A. Neither is a standard rating of Table 240.6(A), so 240.4(B) lets the next higher standard rating, 125 A, protect them, up to 800 A, on a feeder that does not supply more than one receptacle for cord-and-plug-connected portable loads. They are the Table 310.12 sizes again, reached by a different rule.

The catch is the load: under 215.2(A) the feeder carries its noncontinuous load plus 125 % of its continuous load, and that sum must fit the smaller wire, 115 A on 2 AWG copper. A subpanel whose calculated load is that or less can use them; a fully loaded 125 A feeder cannot.

Ground wires at 125 A

A feeder carries an equipment grounding conductor sized by its breaker: a 125 A breaker falls in the row of Table 250.122 for breakers up to 200 A, so 6 AWG copper or 4 AWG aluminum. A service has a grounding electrode conductor instead, sized by its largest service conductor in Table 250.66: 8 AWG copper or 6 AWG aluminum for 2 AWG copper service conductors. The values are those of NFPA's 2020 grounding fact sheet. The ground wire calculator finds both for any rating.

A 125 A subpanel in a detached building

A feeder to a separate building runs four wires: two hots, the neutral and an equipment grounding conductor, and at that building the neutral stays off the grounding conductor and the electrode (250.32(B)(1)). Its disconnecting means is rated at least 100 A where the building is a one-family dwelling and 60 A for a garage or other building (225.39). The garage subpanel calculator sizes such a feeder and gives its burial depth.

125 A over a long run

At the full 125 A over 100 ft, single-phase at 240 V with the conductors at 75 °C: 1 AWG copper drops 3.77 V (1.57 %), 2/0 AWG aluminum 3.90 V (1.63 %), 2 AWG copper 4.75 V (1.98 %) and 1/0 AWG aluminum 4.92 V (2.05 %).

For feeders, an informational note to 215.2(A) says conductors sized to keep the drop at the farthest outlet under 3 %, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit.

Voltage drop of a 125 A circuit at full load, single-phase at 240 V, against one-way length, on the sizes in the key: at 300 ft, 1 AWG copper, feeder 4.71 %, 2/0 AWG aluminum, feeder 4.88 %, 2 AWG copper, service 5.94 %, 1/0 AWG aluminum, service 6.15 %1 AWG copper, feeder2/0 AWG aluminum, feeder2 AWG copper, service1/0 AWG aluminum, service036912050100150200250300One-way length, ft (drop in % on the left)3 %: the feeder noteVoltage drop of a 125 A circuit at full load, single-phase at 240 V, against one-way length, on the sizes in the key: at 300 ft, 1 AWG copper, feeder 4.71 %, 2/0 AWG aluminum, feeder 4.88 %, 2 AWG copper, service 5.94 %, 1/0 AWG aluminum, service 6.15 %1 AWG copper, feeder2/0 AWG aluminum, feeder2 AWG copper, service1/0 AWG aluminum, service0369120100200300One-way length, ft (drop in % on the left)3 %: the feeder note
Voltage drop at the full 125 A, single-phase at 240 V, against one-way length: the feeder sizes as solid lines, the service sizes dashed, with the 215.2(A) note's 3 %.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, Table 310.12; NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

SizeLength
2 AWG152 ft
1 AWG191 ft
1/0 AWG241 ft
2/0 AWG304 ft
3/0 AWG383 ft
4/0 AWG483 ft

Aluminum: one-way length to a 3 % drop, ft

SizeLength
1/0 AWG146 ft
2/0 AWG185 ft
3/0 AWG233 ft
4/0 AWG293 ft
250 kcmil347 ft
300 kcmil416 ft

The wire size calculator finds the size for your length and load and grows the ground wire with it (250.122(B)).

Ampacity of the sizes around 125 A

From the service sizes to one past the feeder sizes, in both columns of NEC Table 310.16, which assumes an ambient temperature of 30 °C and no more than three current-carrying conductors together.

Copper: Table 310.16 ampacity, A

Size60 °C75 °C
3 AWG85 A100 A
2 AWG95 A115 A
1 AWG110 A130 A
1/0 AWG125 A150 A

Aluminum: Table 310.16 ampacity, A

Size60 °C75 °C
1 AWG85 A100 A
1/0 AWG100 A120 A
2/0 AWG115 A135 A
3/0 AWG130 A155 A

Questions

What size wire for a 125 A service?

2 AWG copper or 1/0 AWG aluminum for a 120/240 V dwelling service (Table 310.12), with an 8 AWG copper or 6 AWG aluminum grounding electrode conductor (Table 250.66).

What size wire for a 125 A subpanel?

1 AWG copper or 2/0 AWG aluminum at 75 °C, with a 6 AWG copper or 4 AWG aluminum ground wire; 2 AWG copper or 1/0 AWG aluminum where the subpanel's calculated load fits them (240.4(B)).

What size aluminum wire for 125 A?

1/0 AWG for a dwelling service, 2/0 AWG for a feeder at 75 °C, and 1/0 AWG on a feeder whose load stays within 120 A.

What size ground wire for 125 A?

6 AWG copper or 4 AWG aluminum with a feeder (Table 250.122); an 8 AWG copper grounding electrode conductor for a service with 2 AWG copper (Table 250.66).

What size wire for a 125 A subpanel 100 ft away?

At the full 125 A, 1 AWG copper drops 1.57 % and 2/0 AWG aluminum 1.63 %, inside the 3 % of the 215.2(A) note.

Sources

The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.