RV Hookup Calculator: 30 and 50 Amp RV Wire Size and Park Load
The wire for a 30 A or 50 A RV outlet at a house, with the voltage drop over your run, and the calculated load of an RV park feeder from NEC 551.73.
By Marko Visic, BSc Physics · Updated · Sources below
A 50 A RV outlet (14-50R) takes 6 AWG copper or 4 AWG aluminum at 60 °C terminals, or 8 AWG copper or 6 AWG aluminum where the breaker and receptacle are listed for 75 °C. A 30 A outlet (TT-30R) takes 10 AWG copper or 8 AWG aluminum. Both take a 10 AWG copper ground wire (Table 250.122).
A long run needs more: at 175 ft a 50 A outlet on 6 AWG copper drops more than 3 % at the full rating, so it takes 4 AWG (2.20 %).
Wire for a 30 A and a 50 A RV outlet
An RV outlet circuit is sized by its breaker in Table 310.16. Under 110.14(C)(1)(a) a circuit of 100 A or less is sized in the 60 °C column unless the breaker, the receptacle and every other termination are listed and identified for 75 °C conductors. The site keeps NM and UF cable at 60 °C. 240.4(D) holds 10 AWG copper to 30 A.
Wire and ground wire for an RV outlet circuit
| Outlet | Copper 60 °C | Copper 75 °C | Aluminum 60 °C | Aluminum 75 °C | Ground |
|---|---|---|---|---|---|
| 50 A 14-50R | 6 AWG | 8 AWG | 4 AWG | 6 AWG | 10 AWG / 8 AWG |
| 30 A TT-30R | 10 AWG | 10 AWG | 8 AWG | 8 AWG | 10 AWG / 8 AWG |
Long runs and voltage drop
Table 310.16 sizes for current, not distance. The tables below give the one-way length at which copper at 75 °C drops 3 % at the full rating: 120 V for a TT-30R, 240 V between the hots for a 14-50R. An RV that draws less than the rating drops less. Past your target, the calculator moves the wire up a size and the ground wire with it (250.122(B)).
14-50R: one-way length at which the full rating drops 3 %
| Copper | Length |
|---|---|
| 6 AWG | 150 ft |
| 4 AWG | 238 ft |
| 3 AWG | 300 ft |
| 2 AWG | 379 ft |
| 1 AWG | 478 ft |
TT-30R: one-way length at which the full rating drops 3 %
| Copper | Length |
|---|---|
| 10 AWG | 49.4 ft |
| 8 AWG | 78.5 ft |
| 6 AWG | 125 ft |
| 4 AWG | 199 ft |
TT-30R and 14-50R
The TT-30R is rated 30 A, 125 V, 2-pole 3-wire grounding: one hot, a neutral and a ground. The 14-50R is rated 50 A, 125/250 V, 3-pole 4-wire grounding: two hots, a neutral and a ground. The calculator sizes each for a breaker of its own rating.
GFCI for an RV outlet
At a house, 210.8(F) asks for GFCI protection at outdoor outlets on single-phase circuits of up to 50 A and 150 V to ground, so an outdoor TT-30R or 14-50R needs it.
At an RV park, 551.71(F) asks for GFCI protection in site equipment only for the 125 V, single-phase, 15 A and 20 A receptacles; the 30 A and 50 A receptacles there do not need it.
RV park feeders: Table 551.73(A)
551.73(A) sets a load for each site by its supply, and Table 551.73(A) the lowest demand factor allowed for the number of sites. Under 551.73(B) the factor for the number of sites applies to all of them: the NEC's example is 20 sites at 45 % of 3,600 VA, which is 1,620 VA a site and 32,400 VA in all, or 135.0 A at 240 V.
Calculated load per site, NEC 551.73(A)
| Site | Load |
|---|---|
| Site with 50 A, 120/240 V or 208Y/120 V supply | 12,000 VA |
| Site with both 20 A and 30 A supply | 3,600 VA |
| Site with only 20 A supply | 2,400 VA |
| Tent site with only 20 A supply | 600 VA |
Source: NFPA 70 (NEC) 2023, 551.71 and 551.73, as reprinted in NFPA's 2026-cycle public inputs.
Service buildings, recreational buildings and pools are calculated on their own and added where they share the service. Where one supply serves two RVs, 551.73(A) counts only its two highest-rated receptacles.
Receptacles an RV park provides
Under 551.71 every site with electrical supply has a 20 A, 125 V receptacle. At least 70 % of the sites also have a 30 A, 125 V receptacle, and at least 20 % of existing and 40 % of new sites a 50 A, 125/250 V receptacle, each of those with a 30 A receptacle as well. Tent sites with only 15 A or 20 A supply may be left out of these shares (551.71(D)).
Questions
What size wire for a 50 amp RV outlet?
6 AWG copper or 4 AWG aluminum at 60 °C terminals; 8 AWG copper or 6 AWG aluminum where the breaker and the 14-50R are listed for 75 °C. The ground wire is 10 AWG copper or 8 AWG aluminum, and the circuit runs four wires.
What size wire for a 30 amp RV outlet?
10 AWG copper or 8 AWG aluminum, with a 10 AWG copper or 8 AWG aluminum ground wire; the TT-30R circuit runs three wires.
What wire for a 50 amp RV outlet 175 ft away?
4 AWG copper keeps the drop at the full 50 A to 2.20 %; 6 AWG would reach 3.50 %. With the larger wire the ground wire grows too: 6 AWG copper.
Does an RV outlet need GFCI protection?
Outdoors at a house, yes: 210.8(F) covers outdoor outlets up to 50 A. In RV park site equipment, only the 125 V, 15 A and 20 A receptacles need it (551.71(F)).
How much load do 20 RV sites put on a feeder?
With 20 A and 30 A supply at each, 32,400 VA (the NEC's own example in 551.73(B)), or 135.0 A at 240 V.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
- Hubbell NEMA configuration chart and Hubbell and Leviton device specifications (NEMA WD 6) — retrieved Nov 2026
- NFPA 70 (NEC) 2023, sections as cited — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 551.71 and 551.73, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
The rules are the 2023 NEC's; the NEC edition by state shows which edition applies where you live. The methodology page describes how the calculator works and each source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.