Residential Load Calculator: Dwelling Service Size, NEC Article 220

A house's calculated load by both NEC methods, standard and optional, with every step, and the service and conductors it needs.

By Marko Visic, BSc Physics · Updated · Sources below

Outside dimensions, no open porch.

1,500 VA each (220.52).

1,500 VA each (220.52).

Nameplate. Empty for gas or none.

Nameplate. Empty for gas or none.

Nameplate. Empty for gas or none.

Each 500 W or more; commas between.

Nameplate. Empty if none.

Heating

Nameplate rating. Empty if none.

Baseboard, furnace or wall heaters.

Each with its own control.

The NEC calculates a dwelling's load two ways. The standard method gives each kind of load its own rule; the optional method of 220.82 adds most loads at their rating, counts the first 10,000 VA at 100 % and the rest at 40 %, then adds the largest heating or cooling selection. A 2,000 ft² house with an electric range, dryer, water heater and heat comes to 34,625 VA, or 144.27 A, by the standard method: a 150 A service. The optional method gives 26,700 VA, or 111.25 A, and a 125 A service.

The same house by both methods

The example house has 2,000 ft², two small-appliance circuits and a laundry circuit, a 12 kW range, a 5,000 W dryer, a 4,500 W water heater, three more appliances of 1,500 W, 1,500 W and 500 W, 10,000 W of electric heat in one unit and 5,000 VA of air conditioning. With everything at its rating at once it would draw 210.42 A at 240 V. Neither method assumes that.

One house at 240 V: its connected load, 210.42 A; the standard method, 144.27 A, a 150 A service; the optional method of 220.82, 111.25 A, a 125 A service.0 A50 A100 A150 A200 A250 AConnected load50,500 VA210.42 Aevery load at its ratingStandard method34,625 VA144.27 A150 A serviceOptional method26,700 VA111.25 A125 A serviceOne house at 240 V: its connected load, 210.42 A; the standard method, 144.27 A, a 150 A service; the optional method of 220.82, 111.25 A, a 125 A service.0 A100 A200 AConnected load50,500 VA210.42 Aevery load at its ratingStandard method34,625 VA144.27 A150 A serviceOptional method26,700 VA111.25 A125 A service
The example house at 240 V: its connected load, then the calculated load by each method and the smallest Table 310.12 service at or above it.

Source: NFPA 70 (NEC) 2023, Article 220 (as reproduced in NFPA Public Input 4311); NFPA 70 (NEC) 2023, Table 310.12.

The optional method lands lower here because it takes 40 % of the general load past the first 10,000 VA, and the heat at 65 % instead of 100 %. It is not always lower: an 800 ft² unit with no electric appliances or heat comes to 4,365 VA by the standard method and 6,900 VA by the optional one, because the standard method counts lighting past the first 3,000 VA at 35 %. The calculator shows both, so the smaller one is in view.

Standard method, step by step

Article 220, Part III, gives each kind of load its own rule, and the results add up. For the example house:

  1. General lighting, 220.41: 2,000 ft² at 3 VA per ft² = 6,000 VA.
  2. Small-appliance and laundry circuits, 220.52: 3 × 1,500 VA = 4,500 VA, counted with the lighting: 10,500 VA.
  3. Table 220.45 takes the first 3,000 VA at 100 % and the remaining 7,500 VA at 35 %: 5,625 VA.
  4. Appliances fastened in place, 220.53: with 4 of them (the rule needs 4 or more), 8,000 VA × 75 % = 6,000 VA.
  5. Dryer, 220.54: the larger of 5,000 W and its 5,000 W nameplate: 5,000 VA.
  6. Range, Table 220.55, Column C: one range of 12 kW or less counts as 8 kW: 8,000 VA.
  7. Heating and cooling: electric heat at 100 % (220.51), 10,000 VA; air conditioning at 125 % (220.60, as this calculator reads it), 6,250 VA. The two do not run at once, so only the larger counts: 10,000 VA.
  8. Total: 34,625 VA ÷ 240 V = 144.27 A.
  9. The smallest service rating in Table 310.12 at or above it: 150 A, with 1 AWG copper or 2/0 AWG aluminum or copper-clad aluminum.

Optional method, step by step

220.82 puts the floor area, the circuits and the nameplates of the range, dryer, water heater and appliances into one general load, reduces it once, and adds the largest of six heating and cooling selections. For the same house:

  1. General load, 220.82(B): 2,000 ft² at 3 VA per ft², 6,000 VA; 3 small-appliance and laundry circuits at 1,500 VA, 4,500 VA; the nameplates of the range, dryer, water heater and 3 other appliances, 25,000 VA. Together: 35,500 VA.
  2. 220.82(B) takes the first 10,000 VA at 100 % and the remaining 25,500 VA at 40 %: 20,200 VA.
  3. Heating and cooling, 220.82(C): (C)(1), air conditioning at 100 %, gives 5,000 VA; (C)(4), electric heat in fewer than 4 separately controlled units at 65 %, gives 6,500 VA. Only the largest counts: 6,500 VA.
  4. Total: 26,700 VA ÷ 240 V = 111.25 A.
  5. The smallest service rating in Table 310.12 at or above it: 125 A, with 2 AWG copper or 1/0 AWG aluminum or copper-clad aluminum.

Where each load goes

The two methods count the same loads differently. Floor area is measured from the outside dimensions and leaves out open porches and unfinished spaces not adaptable for future use; the optional method also names garages.

How each method counts a dwelling's loads, NEC 2023

LoadStandard methodOptional method, 220.82
Floor area3 VA per ft² (220.41), then Table 220.45 with the circuits below3 VA per ft², in the general load
Small-appliance and laundry circuits1,500 VA each, added to the lighting (220.52)1,500 VA each, in the general load
Water heater and other appliances fastened in placeNameplate; 75 % of the total with 4 or more (220.53)Nameplate, in the general load
Clothes dryer5,000 W or the nameplate, the larger (220.54)Nameplate, in the general load
RangeTable 220.55, Column C: 8 kW for one range of 12 kW or lessNameplate, in the general load
EV charger7,200 W or the nameplate, the larger (220.57)Nameplate, in the general load (this calculator’s reading)
Electric heat100 % (220.51)65 %, or 40 % with 4 or more separately controlled units
Air conditioning125 %, against the heat; the larger counts (220.60, as read here)100 %; the largest heating or cooling selection counts
Heat pumpWith its backup heat at 100 % as heating, alone at 125 % as cooling (as read here)100 %, plus 65 % of any backup heat
The sumNo further factorGeneral load: the first 10,000 VA at 100 %, the rest at 40 % (220.82(B))

Table 220.45 counts the first 3,000 VA of lighting and circuits at 100 %, up to 120,000 VA at 35 % and the rest at 25 %. “As read here” marks the calculator's reading of a rule; the methodology page sets out each one.

Source: NFPA 70 (NEC) 2023, Article 220 (as reproduced in NFPA Public Input 4311).

From the load to the service

Divide the calculated load by 240 V and take the smallest service rating at or above the current. Table 310.12 gives the conductors for each rating, for a 120/240 V single-phase service, or a feeder, that carries the entire load of a one-family dwelling or of one dwelling unit. A 200 A service covers a calculated load of up to 48,000 VA.

Table 310.12, NEC 2023

ServiceCopperAluminum or copper-clad aluminum
100 A4 AWG2 AWG
110 A3 AWG1 AWG
125 A2 AWG1/0 AWG
150 A1 AWG2/0 AWG
175 A1/0 AWG3/0 AWG
200 A2/0 AWG4/0 AWG
225 A3/0 AWG250 kcmil
250 A4/0 AWG300 kcmil
300 A250 kcmil350 kcmil
350 A350 kcmil500 kcmil
400 A400 kcmil600 kcmil

The service entrance calculator adds the ground wire and the voltage drop for a rating; the 200 A guide compares Table 310.12 with the ampacity table.

NEC 2023 and 2026

The 2026 NEC moved these load calculations from Article 220 to Article 120. The calculator uses the 2023 values and section numbers; the 2026 values are not verified here yet, so it does not offer them. Which edition applies depends on the state or city: NEC edition by state.

Questions

What size service does a 2,000 ft² house need?

It depends more on what runs on electricity than on the floor area, which adds 3 VA per ft². The example house needs 150 A by the standard method or 125 A by the optional one. Heated by gas instead, it comes to 128.65 A by the standard method, still a 150 A service, and 105 A by the optional one, a 110 A service.

Is a 200 A service enough?

Yes when the calculated load stays at or under 48,000 VA, which is 200 A at 240 V. Adding a 9,600 W EV charger to the example house takes the standard method to 184.27 A (200 A) and the optional method to 127.25 A (150 A).

Do the heat and the air conditioning both count?

No, only the larger. 220.60 lets a calculation use only the largest of loads that are unlikely to run at the same time, and where a motor or air-conditioning load is not the largest, it says “125 percent of either the motor load or air-conditioning load” is used. The calculator reads that as comparing the heat with the air conditioning at 125 %. The optional method takes the largest of its six heating and cooling selections (220.82(C)).

How does an EV charger count?

In the standard method at 7,200 W or its nameplate, whichever is larger (220.57). The 2023 optional method has no line of its own for one; the calculator adds its nameplate to the general load with the appliances on a specific circuit, its reading of 220.82(B).

How does a heat pump count?

In the optional method at 100 % of its rating plus 65 % of its backup electric heat, or at 100 % with no backup heat (220.82(C)). The standard method names no heat pump, so the calculator counts it as heating with its backup heat and as cooling on its own. With a 6,000 VA heat pump and 10,000 W of backup heat in place of its heat and air conditioning, the example house needs 175 A by the standard method and 150 A by the optional one.

Which appliances count as fastened in place?

Appliances rated 500 W or more, or 1/4 hp or more, that are fastened in place, such as a water heater. Cooking equipment, clothes dryers, space heating, air conditioning and EV chargers have rules of their own and stay out of the count (220.53).

Can any house use the optional method?

220.82 covers a dwelling unit whose entire load is served by a single 120/240 V or 208Y/120 V 3-wire set of service or feeder conductors with an ampacity of 100 A or more. Every service in Table 310.12 is at least that.

Sources

The methodology page sets out each step, each source and each reading. A calculated load is the code's minimum for the loads entered; it leaves no room for loads added later. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.