Circuit Breaker Calculator: Breaker Size for a Load, NEC 210.20(A)

The smallest standard breaker or fuse for a load, with continuous loads at 125 %, and the wire and ground wire it needs.

By Marko Visic, BSc Physics · Updated · Sources below

Leave it empty if none.

Leave it empty if none.

Conductor material
Wiring method

Cable stays in the 60 °C column. Choose it when not sure.

A breaker or fuse must be rated at least the noncontinuous load plus 125 % of the continuous load (NEC 210.20(A)), rounded up to a standard rating in Table 240.6(A). A continuous load of 16 A takes a 20 A breaker, 24 A takes 30 A, 40 A takes 50 A and 48 A takes 60 A.

Largest continuous load on each breaker

Turned around, the rule caps a continuous load at the rating divided by 1.25: 16 A on a 20 A breaker, 24 A on 30 A. A noncontinuous load may use the full rating, and a mixed load fits when the noncontinuous part plus 125 % of the continuous part stays within it.

Each rating the calculator offers

Breaker or fuseLargest continuous load
15 A12 A
20 A16 A
25 A20 A
30 A24 A
35 A28 A
40 A32 A
45 A36 A
50 A40 A
60 A48 A
70 A56 A
80 A64 A
90 A72 A
100 A80 A
110 A88 A
125 A100 A
150 A120 A
175 A140 A
200 A160 A
225 A180 A
250 A200 A
300 A240 A
350 A280 A
400 A320 A

Largest breaker for each wire size

The breaker protects the wire. 240.4(D) holds 14 AWG, 12 AWG and 10 AWG copper to 15 A, 20 A and 30 A in either column, and 12 AWG and 10 AWG aluminum to 15 A and 25 A. Above those sizes, a wire's breaker may match its ampacity, or under 240.4(B) be the next standard rating above it, up to 800 A, when the circuit does not supply more than one receptacle for cord-and-plug-connected portable loads. Read the 60 °C column for NM or UF cable and for circuits of 100 A or less, the 75 °C column for terminals listed for it and for circuits over 100 A.

Copper

Size60 °C75 °C
14 AWG15 A15 A
12 AWG20 A20 A
10 AWG30 A30 A
8 AWG40 A50 A
6 AWG60 A under 240.4(B)70 A under 240.4(B)
4 AWG70 A90 A under 240.4(B)
3 AWG90 A under 240.4(B)100 A
2 AWG100 A under 240.4(B)125 A under 240.4(B)
1 AWG110 A150 A under 240.4(B)
1/0 AWG125 A150 A
2/0 AWG150 A under 240.4(B)175 A
3/0 AWG175 A under 240.4(B)200 A
4/0 AWG200 A under 240.4(B)250 A under 240.4(B)

Aluminum or copper-clad aluminum

Size60 °C75 °C
12 AWG15 A15 A
10 AWG25 A25 A
8 AWG35 A40 A
6 AWG40 A50 A
4 AWG60 A under 240.4(B)70 A under 240.4(B)
3 AWG70 A under 240.4(B)80 A under 240.4(B)
2 AWG80 A under 240.4(B)90 A
1 AWG90 A under 240.4(B)100 A
1/0 AWG100 A125 A under 240.4(B)
2/0 AWG125 A under 240.4(B)150 A under 240.4(B)
3/0 AWG150 A under 240.4(B)175 A under 240.4(B)
4/0 AWG150 A200 A under 240.4(B)

† Only under 240.4(B), with its condition met; otherwise the standard rating below it, such as 50 A for 6 AWG copper at 60 °C.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793); NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint); NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints).

A mixed load, step by step

A circuit carries 10 A that runs continuously and 8 A that does not. The smallest rating is 8 A plus 125 % of 10 A, or 20.5 A, so the breaker is the next standard rating, 25 A, and the wire is 10 AWG copper, which carries 30 A at 60 °C.

A load of 8 A noncontinuous and 10 A continuous: 18 A as it runs; the smallest rating is 8 A plus 125 % of 10 A, 20.5 A; the next standard breaker is 25 A; 10 AWG copper carries 30 A in the 60 °C column.NoncontinuousContinuous0 A10 A20 A30 AThe loadas it runs18 ASmallest rating125 % rule20.5 ABreakerTable 240.6(A)25 A10 AWG60 °C column30 AA load of 8 A noncontinuous and 10 A continuous: 18 A as it runs; the smallest rating is 8 A plus 125 % of 10 A, 20.5 A; the next standard breaker is 25 A; 10 AWG copper carries 30 A in the 60 °C column.NoncontinuousContinuous0 A10 A20 A30 AThe loadas it runs18 ASmallest rating125 % rule20.5 ABreakerTable 240.6(A)25 A10 AWG60 °C column30 A
8 A noncontinuous and 10 A continuous: the load as it runs, the smallest rating with the continuous part at 125 %, the breaker, and the ampacity of the wire for it.

Source: NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft); NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints); NFPA 70 (NEC) 2023, Table 310.16.

A continuous load of 44 A needs 55 A, so a 60 A breaker. The wire that carries the full rating is 4 AWG copper in NM cable, but 240.4(B) also lets the breaker protect 6 AWG (55 A at 60 °C), which still carries the 55 A the load needs (210.19(A)). The calculator shows both.

Standard breaker and fuse ratings

Table 240.6(A) lists the standard ratings of fuses and inverse time circuit breakers: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1,000, 1,200, 1,600, 2,000, 2,500, 3,000, 4,000, 5,000 and 6,000 A. The calculator offers 15 A to 400 A, the range of its wire sizing.

Questions

What size breaker for 12 AWG wire?

20 A for 12 AWG copper and 15 A for 12 AWG aluminum: 240.4(D) sets both, whatever the column.

What size breaker for 10 AWG wire?

30 A for 10 AWG copper and 25 A for 10 AWG aluminum, the 240.4(D) limits.

What size breaker for 8 AWG wire?

8 AWG copper carries 40 A at 60 °C, so 40 A in NM cable, and 50 A at 75 °C, so 50 A on terminals listed for it.

What size breaker for 6 AWG wire?

6 AWG copper carries 55 A at 60 °C and 65 A at 75 °C. Neither is a standard rating, so 240.4(B) allows 60 A and 70 A when the circuit does not supply more than one receptacle for cord-and-plug-connected portable loads; otherwise 50 A and 60 A.

How many amps can a 20 A breaker carry?

16 A of continuous load, since 125 % of it must fit the rating, and the full 20 A of noncontinuous load.

What size breaker for a 40 A continuous load?

50 A: 125 % of 40 A is 50 A, a standard rating, with 6 AWG copper in NM cable.

Can I put a bigger breaker on the same wire?

Not past two limits: 240.4(D) caps 14 AWG, 12 AWG and 10 AWG copper at 15 A, 20 A and 30 A, and for larger wire 240.4(B) allows at most the next standard rating above its ampacity. A larger load needs larger wire: the wire size calculator sizes it.

Sources

Retrieved .

The methodology page sets out each step and each source. Motor and air conditioner circuits follow rules of their own, which this calculator does not cover. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.