Electrical Guides

100 Amp Wire Size Guide

Complete specifications for 100 A service entrance

4 AWG
Copper Wire
2 AWG
Aluminum Wire
8 AWG
Copper grounding conductor

Quick Answer: Wire Size for 100 Amp Service

For a 100 A dwelling service or main power feeder, use 4 AWG copper or 2 AWG aluminum (2023 NEC Table 310.12). A service needs a grounding electrode conductor: 8 AWG copper or 6 AWG aluminum (NEC Table 250.66, values from NFPA's 2020 grounding fact sheet). If these conductors are the main power feeder, they carry an equipment grounding conductor instead: 8 AWG copper or 6 AWG aluminum (NEC Table 250.122). A feeder to a subpanel is sized from NEC Table 310.16: see the wire size calculator.

Common 100 Amp Applications

Main Service

Small home main panel

Copper:4 AWG
Aluminum:2 AWG
GEC:8 AWG copper

Installation Requirements & Code References

ComponentSpecificationNEC Reference
Main Breaker100 A 2-pole breakerNEC 230.79
Wire Size (Copper)4 AWG (100 A dwelling service)NEC Table 310.12
Wire Size (Aluminum)2 AWG (100 A dwelling service)NEC Table 310.12
Equipment grounding conductor (main power feeder)8 AWG copperNEC Table 250.122
Grounding electrode conductor (service)8 AWG copperNEC Table 250.66

Step-by-Step Installation Guide

  1. 1

    Calculate Load Requirements

    Verify that 100 A is sufficient for your needs using NEC Article 220 load calculations.

  2. 2

    Measure Distance

    Measure the actual wire run distance including vertical runs and bends.

  3. 3

    Select Wire Size

    Choose wire based on distance: 4 AWG copper or 2 AWG aluminum for a 100 A dwelling service (Table 310.12), upsize for longer distances.

  4. 4

    Install Conduit

    Run conduit for the two ungrounded conductors and the neutral, plus an equipment grounding conductor if the run is the main power feeder.

  5. 5

    Pull Conductors

    Pull THHN/THWN-2 conductors through conduit, maintain proper color coding.

  6. 6

    Make Terminations

    Use proper torque specs.

  7. 7

    Install Grounding System

    Connect the 8 AWG copper grounding electrode conductor at the service, or the 8 AWG copper equipment grounding conductor on the main power feeder.

  8. 8

    Test & Inspect

    Test insulation resistance, verify connections, and schedule inspection.

Temperature & Environmental Factors

High Temperature Areas

  • Attics at 41–45 °C (105–113 °F): 0.82 in the 75 °C column (Table 310.15(B)(1)(1))
  • Consider upsizing wire for extreme heat conditions

Wet Locations

  • Use THWN-2 or XHHW for wet locations
  • Underground: USE-2 or direct burial cable
  • Schedule 80 PVC for physical protection

Common Mistakes to Avoid

Sizing Errors

  • ❌ Forgetting voltage drop for long runs

Installation Errors

  • ❌ Undersized conduit causing difficult pulls
  • ❌ Incorrect torque on terminals
  • ❌ Wrong ground wire size (10 AWG instead of 8 AWG)