Garage Subpanel Calculator: Feeder Wire and Burial Depth
The feeder from a house panel to a subpanel in a detached garage: wire and ground wire, voltage drop, the four wires, the garage's disconnect and how deep to bury the run.
By Marko Visic, BSc Physics · Updated · Sources below
A 60 A garage feeder takes 4 AWG copper or 3 AWG aluminum at 60 °C terminals, or 6 AWG copper or 4 AWG aluminum where every termination is listed and identified for 75 °C conductors. Its ground wire is 10 AWG copper or 8 AWG aluminum (Table 250.122), the fourth of four wires.
Under open ground, Table 300.5(A) asks for 18 in (450 mm) of cover over nonmetallic conduit and 24 in (600 mm) over cable buried directly.
Feeder wire size by breaker
Under 110.14(C)(1)(a), a feeder rated 100 A or less is sized in the 60 °C column of Table 310.16, unless the breaker, the subpanel and every other termination are listed and identified for 75 °C conductors; above 100 A, 110.14(C)(1)(b) starts from 75 °C. The site keeps NM and UF cable at 60 °C.
Copper feeder and ground wire
| Breaker | 60 °C | 75 °C | Ground |
|---|---|---|---|
| 30 A | 10 AWG | 10 AWG | 10 AWG |
| 40 A | 8 AWG | 8 AWG | 10 AWG |
| 50 A | 6 AWG | 8 AWG | 10 AWG |
| 60 A | 4 AWG | 6 AWG | 10 AWG |
| 70 A | 4 AWG | 4 AWG | 8 AWG |
| 80 A | 3 AWG | 4 AWG | 8 AWG |
| 90 A | 2 AWG | 3 AWG | 8 AWG |
| 100 A | 1 AWG | 3 AWG | 8 AWG |
Aluminum feeder and ground wire
| Breaker | 60 °C | 75 °C | Ground |
|---|---|---|---|
| 30 A | 8 AWG | 8 AWG | 8 AWG |
| 40 A | 6 AWG | 8 AWG | 8 AWG |
| 50 A | 4 AWG | 6 AWG | 8 AWG |
| 60 A | 3 AWG | 4 AWG | 8 AWG |
| 70 A | 2 AWG | 3 AWG | 6 AWG |
| 80 A | 1 AWG | 2 AWG | 6 AWG |
| 90 A | 1/0 AWG | 2 AWG | 6 AWG |
| 100 A | 1/0 AWG | 1 AWG | 6 AWG |
240.4(D) holds 10 AWG aluminum to 25 A, so a 30 A feeder takes 8 AWG aluminum in both columns.
One size smaller under 240.4(B)
Where a size's ampacity is not a standard rating in Table 240.6(A), 240.4(B) lets the next standard rating protect it, up to 800 A. 6 AWG copper carries 55 A at 60 °C, so a 60 A breaker may protect it on a garage whose calculated load is 55 A or less. The calculated load has to fit the feeder's ampacity under 215.2(A), continuous loads at 125 %. Enter the load in the calculator and it shows the smaller size when it fits.
Four wires and a grounding electrode
A feeder to a separate building, such as a detached garage, runs four wires: the two hots, the neutral and an equipment grounding conductor. Under 250.32(B)(1), the equipment grounding conductor runs with the feeder, connects to the garage's disconnecting means and to its grounding electrodes, and is sized from Table 250.122. The neutral is not connected to the equipment grounding conductor or to the grounding electrode at the garage.
Source: NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs; NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs.
The garage has its own grounding electrode system (250.32(A)), unless a single branch circuit with an equipment grounding conductor supplies it. A three-wire feeder installed under an earlier edition, with the neutral as the ground-fault return, may stay only under the three conditions of Exception No. 1 to 250.32(B)(1).
The neutral carries the feeder's neutral load: under 220.61, the largest load between it and either hot. A neutral the size of the hots always carries it, and the calculator sizes the hots.
The garage disconnect
Under 225.31 the garage gets its own disconnecting means, inside or outside, at a readily accessible place nearest the point where the feeder enters. Under 225.39 its rating is at least the calculated load and never below 60 A, so a garage on a smaller feeder breaker still has a disconnect rated 60 A or more. The floor drops to 30 A where the garage has no more than two 2-wire branch circuits, and to 15 A where one branch circuit supplies limited loads.
Section 225.30 allows one feeder or branch circuit to the building unless one of its listed conditions permits more.
How deep to bury the feeder
Table 300.5(A) sets the minimum cover by wiring method and by what lies above the run. Cover is measured from the top of the cable, conductor or conduit to the top of finished grade, concrete or a similar cover (Note 1 to the table).
Source: NFPA 70 (NEC) 2023, Table 300.5(A) (NFPA 2023-cycle Second Draft SR-8551).
Minimum cover, NEC Table 300.5(A)
| Buried under | Buried directly | Nonmetallic conduit | RMC or IMC |
|---|---|---|---|
| Lawn or open ground (any place not listed below) | 24 in600 mm | 18 in450 mm | 6 in150 mm |
| In a trench below 2 in thick concrete or equivalent | 18 in450 mm | 12 in300 mm | 6 in150 mm |
| Under an exterior concrete slab at least 4 in thick with no vehicle traffic, extending at least 6 in past the run | 18 in450 mm | 4 in100 mm | 4 in100 mm |
| Under a one- or two-family dwelling driveway or parking area | 18 in450 mm | 18 in450 mm | 18 in450 mm |
| Under a street, road, alley, or other driveway or parking lot | 24 in600 mm | 24 in600 mm | 24 in600 mm |
Under a one- or two-family dwelling's driveway, all three methods need 18 in (450 mm). The table's other columns, for residential branch circuits and low-voltage landscape circuits, do not apply to a feeder.
Voltage drop on a long run
Table 310.16 sizes a feeder for current, not distance. At the full rating, single-phase at 240 V with the conductors at 75 °C, each 60 °C size reaches a drop of 3 % at these lengths:
One-way length at which the full rating drops 3 %
| Breaker | Copper | Length | Aluminum | Length |
|---|---|---|---|---|
| 30 A | 10 AWG | 98.8 ft | 8 AWG | 95.4 ft |
| 40 A | 8 AWG | 118 ft | 6 AWG | 114 ft |
| 50 A | 6 AWG | 150 ft | 4 AWG | 145 ft |
| 60 A | 4 AWG | 199 ft | 3 AWG | 152 ft |
| 70 A | 4 AWG | 170 ft | 2 AWG | 164 ft |
| 80 A | 3 AWG | 188 ft | 1 AWG | 181 ft |
| 90 A | 2 AWG | 210 ft | 1/0 AWG | 203 ft |
| 100 A | 1 AWG | 239 ft | 1/0 AWG | 183 ft |
An informational note to 215.2(A) ties a feeder drop of up to 3 %, and 5 % for feeder and branch circuit together, to reasonable efficiency: advice, not a rule. The drop falls in proportion to the current, so a garage that draws less than the rating drops less. Past your target, the calculator moves the feeder up a size and the ground wire with it, as 250.122(B) requires.
Questions
What size wire for a 60 A subpanel in a detached garage?
4 AWG copper or 3 AWG aluminum at 60 °C terminals; 6 AWG copper or 4 AWG aluminum where every termination is listed and identified for 75 °C conductors. Four wires in all; the ground wire is 10 AWG copper or 8 AWG aluminum.
What size wire for a 100 A garage subpanel?
1 AWG copper or 1/0 AWG aluminum at 60 °C terminals, 3 AWG copper or 1 AWG aluminum at 75 °C; the ground wire is 8 AWG copper or 6 AWG aluminum. The 100 amp guide covers that feeder in full.
How deep do I bury wire to a detached garage?
Under open ground, 24 in (600 mm) for cable or conductors buried directly, 18 in (450 mm) in nonmetallic conduit listed for direct burial and 6 in (150 mm) in rigid or intermediate metal conduit, measured to the top of the run (Table 300.5(A)). Under a dwelling's driveway, 18 in (450 mm) for all three.
Can I run three wires to a detached garage?
Not for a new feeder. Under 250.32(B)(1) an equipment grounding conductor runs with it, and the neutral is not connected to it at the garage. A three-wire feeder installed under an earlier edition may stay only under the conditions of Exception No. 1.
Does a detached garage need a ground rod?
It needs a grounding electrode system of its own under 250.32(A), connected to the equipment grounding conductor, unless a single branch circuit with an equipment grounding conductor supplies the garage.
What size disconnect does a garage subpanel need?
At least the calculated load and at least 60 A, or 30 A where the garage has no more than two 2-wire branch circuits (225.39). It goes at a readily accessible place nearest where the feeder enters the garage (225.31).
Can 6 AWG copper go on a 60 A breaker?
At 60 °C it carries 55 A, so only on a garage whose calculated load is 55 A or less, under 240.4(B). Where every termination is listed and identified for 75 °C conductors, it carries 65 A and needs no exception.
How far can a 60 A garage feeder run?
At the full 60 A and 240 V, 4 AWG copper reaches a 3 % drop at 199 ft and 3 AWG aluminum at 152 ft. That is advice, not a limit; the calculator finds the size for your length.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 250.32, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 225, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Table 300.5(A) (NFPA 2023-cycle Second Draft SR-8551) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, Article 220 (as reproduced in NFPA Public Input 4311) — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
The rules are the 2023 NEC's; the NEC edition by state shows which edition applies where you live. The methodology page describes how the calculator works and each source. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.