Professional-grade electrical engineering education with interactive calculators, detailed explanations, and real-world examples.
Guide Topics
Complete AWG Wire Size Chart & Reference Guide
American Wire Gauge (AWG) comprehensive reference table with diameters, resistance, ampacity ratings, and metric conversions for electrical installations.
Quick AWG Reference - Most Common Sizes
14 AWG
- • Diameter: 1.628 mm
- • 15A circuits
- • Lighting & outlets
12 AWG
- • Diameter: 2.053 mm
- • 20A circuits
- • Kitchen & bathroom
10 AWG
- • Diameter: 2.588 mm
- • 30A circuits
- • Dryers & A/C
6 AWG
- • Diameter: 4.116 mm
- • 60A circuits
- • EV chargers
Complete AWG Wire Size Table
| AWG | Diameter (mm) | Diameter (inch) | Area (mm²) | Resistance (Ω/1000ft) | Cu Ampacity 75°C | Al Ampacity 75°C |
|---|---|---|---|---|---|---|
| 18 | 1.024 | 0.0403 | 0.823 | 6.385 | — | — |
| 16 | 1.291 | 0.0508 | 1.310 | 4.016 | — | — |
| 14 | 1.628 | 0.0641 | 2.08 | 2.525 | 20* | — |
| 12 | 2.052 | 0.0808 | 3.31 | 1.588 | 25* | 20* |
| 10 | 2.588 | 0.1019 | 5.26 | 0.999 | 35* | 30* |
| 8 | 3.264 | 0.1285 | 8.37 | 0.628 | 50 | 40 |
| 6 | 4.115 | 0.1620 | 13.30 | 0.395 | 65 | 50 |
| 4 | 5.189 | 0.2043 | 21.20 | 0.249 | 85 | 65 |
| 3 | 5.827 | 0.2294 | 26.70 | 0.197 | 100 | 75 |
| 2 | 6.543 | 0.2576 | 33.60 | 0.156 | 115 | 90 |
| 1 | 7.348 | 0.2893 | 42.40 | 0.124 | 130 | 100 |
| 1/0 | 8.255 | 0.3250 | 53.50 | 0.0983 | 150 | 120 |
| 2/0 | 9.266 | 0.3648 | 67.40 | 0.0779 | 175 | 135 |
| 3/0 | 10.404 | 0.4096 | 85.00 | 0.0618 | 200 | 155 |
| 4/0 | 11.684 | 0.4600 | 107.00 | 0.0490 | 230 | 180 |
* Limited by NEC 240.4(D) small conductor rule. 14 AWG max 15A, 12 AWG max 20A, 10 AWG max 30A protection.
AWG to Metric Wire Size Conversion
Common AWG to mm² Conversions
| AWG | mm² | Nearest Metric |
|---|---|---|
| 14 AWG | 2.08 | 2.5 mm² |
| 12 AWG | 3.31 | 4 mm² |
| 10 AWG | 5.26 | 6 mm² |
| 8 AWG | 8.37 | 10 mm² |
| 6 AWG | 13.3 | 16 mm² |
| 4 AWG | 21.2 | 25 mm² |
| 2 AWG | 33.6 | 35 mm² |
| 1/0 AWG | 53.5 | 50 mm² |
AWG System Explained
The AWG system is logarithmic - each 3-gauge decrease doubles the cross-sectional area.
Smaller AWG numbers = larger wire diameters. AWG 0000 (4/0) is the largest standard size.
For sizes larger than 4/0, kcmil (MCM) is used, representing thousands of circular mils.
Formula: Diameter(n) = 0.005 × 92^((36-n)/39) inches
Wire Size Selection by Application
Residential Circuits
- Lighting (15A)14 AWG
- Outlets (20A)12 AWG
- Kitchen GFCI (20A)12 AWG
- Bathroom (20A)12 AWG
Appliances
- Dryer (30A)10 AWG
- Range (50A)6 AWG
- Water Heater (30A)10 AWG
- A/C Unit (20-30A)12-10 AWG
Special Applications
- EV Charger (60A)6 AWG
- Hot Tub (50A)6 AWG
- Sub Panel (100A)2 AWG
- Service (200A)3/0 AWG
Important: These are typical sizes. Always calculate based on actual load, distance, and voltage drop. Consult NEC and local codes for specific requirements.
Wire Cost Comparison by Size
| Wire Size | Copper $/ft | Aluminum $/ft | Savings % | 100ft Cost Cu | 100ft Cost Al |
|---|---|---|---|---|---|
| 14 AWG | $0.45 | — | — | $45 | — |
| 12 AWG | $0.65 | $0.35 | 46% | $65 | $35 |
| 10 AWG | $0.95 | $0.45 | 53% | $95 | $45 |
| 8 AWG | $1.55 | $0.75 | 52% | $155 | $75 |
| 6 AWG | $2.80 | $1.20 | 57% | $280 | $120 |
| 2 AWG | $5.50 | $2.20 | 60% | $550 | $220 |
| 2/0 AWG | $12.50 | $4.80 | 62% | $1,250 | $480 |
*Prices are approximate 2024 market averages for THHN/THWN-2 wire and may vary by location and supplier.
Technical Resources & Standards
NEC Standards
- NFPA 70 - NEC
- • Article 310 - Conductors
- • Table 310.16 - Ampacities
- • Chapter 9, Table 8 - Properties
Industry Standards
- ASTM B258 - AWG Sizes
- UL Wire & Cable Guide
- • IEC 60228 - Metric sizes
Manufacturer Data
- Southwire Specifications
- General Cable Resources
- • Wire specification sheets
The Math Behind AWG — ASTM B258 and the Geometric Progression
AWG is not arbitrary. The numbers in the table above derive from a specific geometric progression defined by ASTM B258 (the Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors). Understanding the math lets you derive any AWG specification from first principles.
The geometric definition
AWG is anchored at two endpoints: 0000 (4/0) AWG = 0.4600″ diameter, and 36 AWG = 0.0050″ diameter. The 38 sizes between 4/0 and 36 are spaced in a geometric progression.
Above 4/0 — kcmil takes over
AWG runs out at 4/0 (0.4600″). Larger conductors are specified by cross-sectional area in kcmil (thousands of circular mils). 1 circular mil = the area of a circle with diameter 0.001 inch (1 mil).
AWG ↔ Metric SI conversion
Most of the world uses metric SI sizes (mm²) instead of AWG. Conversion is exact: 1 kcmil = 0.5067 mm². The table below pairs each AWG size with the closest commercial metric SI size, the conversion factor, and a note on whether the substitution is safe.
| AWG | Exact area (mm²) | Closest std SI size | SI vs AWG | Substitution note |
|---|---|---|---|---|
| 14 | 2.08 | 2.5 mm² | SI is +20% | 2.5 mm² is fine for 14 AWG circuits; common in EU residential. |
| 12 | 3.31 | 4 mm² | SI is +21% | 4 mm² is the EU standard for 20 A circuits. |
| 10 | 5.26 | 6 mm² | SI is +14% | 6 mm² substitutes safely; common for EU dryers. |
| 8 | 8.37 | 10 mm² | SI is +20% | 10 mm² for cookers, water heaters in EU. |
| 6 | 13.30 | 16 mm² | SI is +20% | 16 mm² for sub-mains in EU dwellings. |
| 4 | 21.15 | 25 mm² | SI is +18% | 25 mm² for service-entrance / submains. |
| 2 | 33.62 | 35 mm² | SI is +4% | 35 mm² is closest match — same ampacity tier. |
| 1/0 | 53.49 | 50 mm² | SI is −6% | 50 mm² is slightly smaller — verify ampacity. |
| 2/0 | 67.43 | 70 mm² | SI is +4% | 70 mm² matches. |
| 4/0 | 107.2 | 120 mm² | SI is +12% | 120 mm² is the standard SI replacement for 4/0. |
| 250 kcmil | 126.7 | 150 mm² | SI is +18% | 150 mm² runs cooler — preferred where available. |
| 500 kcmil | 253.4 | 240 mm² | SI is −5% | 240 mm² is the closest standard size. |
Stranded vs solid — when each is required
All AWG diameters in the table above are for SOLID conductor. Stranded conductors of the same AWG have a slightly larger overall diameter (typically 8–15 % larger) because of the gaps between strands.
- Solid: required for fixed wiring 14–10 AWG (NEC 334.10 NM-B cable). Cheaper, easier to terminate under screw lugs.
- Stranded: required above 8 AWG (too stiff to bend). Required by Class B / Class C strand counts in NEC Chapter 9 Table 10. Necessary for control wiring, vibration applications.
- Class B (typical building): 7 strands at small AWG, 19 strands above 1/0.
- Class C / D / K (flexible): finer stranding for control cable, welding cable, portable cord.
Insulation type — pick by environment
Two conductors of identical AWG can have very different ampacities depending on insulation rating. NEC 310.16 organizes by insulation temperature class:
- 60°C (TW, UF): direct burial, wet locations, older NM. Lowest ampacity.
- 75°C (THW, THWN, RHW, USE, XHHW wet, NM-B at conductor): general-purpose; most common termination rating.
- 90°C (THHN, XHHW-2 dry, RHH, USE-2): highest ampacity in conduit. NM-B cable insulation is 90°C but ampacity is capped at 60°C column per NEC 334.80.
Key: the entire circuit’s ampacity is limited by the lowest-rated component. Most breakers and panels in residential service are rated 75°C, so even if you use 90°C THHN conductor, you must use the 75°C ampacity column — NEC 110.14(C).
Worked derivation — why 12 AWG is rated 25 A at 75°C
The ampacity values in NEC 310.16 are not arbitrary. They derive from a heat-balance equation between I²R losses in the conductor and convective + radiative cooling at the conductor surface, normalized to the insulation’s rated operating temperature with 30°C ambient.
Why 12 AWG ampacity is 25 A but the breaker can’t exceed 20 A
NEC 240.4(D) is the “small-conductor rule”: regardless of higher 310.16 ampacity, the OCPD on 14, 12, 10 AWG copper is capped:
- 14 AWG: ampacity 20 A (75°C), OCPD max 15 A
- 12 AWG: ampacity 25 A (75°C), OCPD max 20 A
- 10 AWG: ampacity 35 A (75°C), OCPD max 30 A
Why the discrepancy? Small conductors are disproportionately sensitive to mechanical damage, poor terminations, and accumulated dust. The 240.4(D) cap creates a safety margin that 8 AWG and larger conductors don’t need. There are five exceptions (motor circuits, taps, listed equipment, Air-conditioning per Article 440, fire alarm per Article 760) but they’re narrow.