Wire Size for 20 Amp Breaker: 12 AWG Copper

By Marko Visic, BSc Physics · Updated · Sources below

A 20 A breaker takes 12 AWG copper or 10 AWG aluminum, whatever the terminals or cable. 14 AWG copper reaches 20 A in the 75 °C column of Table 310.16, but 240.4(D) limits it to a 15 A breaker.

The ground wire is 12 AWG copper or 10 AWG aluminum (Table 250.122). Over 100 ft the full 20 A on 12 AWG drops 6.45 % at 120 V and 3.22 % at 240 V.

Allowable ampacity in NEC Table 310.16 of the small conductors that 240.4(D) limits, against the largest breaker 240.4(D) allows on each: 14 AWG copper: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 12 AWG copper: 20 A at 60 °C and 25 A at 75 °C, breaker at most 20 A; 10 AWG copper: 30 A at 60 °C and 35 A at 75 °C, breaker at most 30 A; 12 AWG aluminum: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 10 AWG aluminum: 25 A at 60 °C and 30 A at 75 °C, breaker at most 25 A.Largest breaker, 240.4(D)Table 310.16 at 60 °C and 75 °C0 A10 A20 A30 A40 A20 A breakerAmperes (size on the left)Copper14 AWG15 A12 AWG20 A10 AWG30 AAluminum12 AWG15 A10 AWG25 AAllowable ampacity in NEC Table 310.16 of the small conductors that 240.4(D) limits, against the largest breaker 240.4(D) allows on each: 14 AWG copper: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 12 AWG copper: 20 A at 60 °C and 25 A at 75 °C, breaker at most 20 A; 10 AWG copper: 30 A at 60 °C and 35 A at 75 °C, breaker at most 30 A; 12 AWG aluminum: 15 A at 60 °C and 20 A at 75 °C, breaker at most 15 A; 10 AWG aluminum: 25 A at 60 °C and 30 A at 75 °C, breaker at most 25 A.Largest breaker, 240.4(D)Table 310.16 at 60 °C and 75 °C0 A20 A40 A20 A breakerAmperes (size on the left)Copper14 AWG12 AWG10 AWGAluminum12 AWG10 AWG
Each bar ends at the largest breaker 240.4(D) allows on the size; the dots show its Table 310.16 ampacity at 60 °C (open) and 75 °C (filled). 14 AWG copper's 75 °C dot reaches 20 A, its bar stops at 15 A.

Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint).

Why 14 AWG can't go on a 20 A breaker

Read from Table 310.16 alone, a 20 A circuit with 75 °C terminations would take 14 AWG copper: it carries 15 A at 60 °C and 20 A at 75 °C. 240.4(D) overrides the table for the small sizes. It holds 14 AWG copper to a 15 A breaker and 12 AWG copper to 20 A, so 12 AWG is the smallest copper a 20 A breaker may protect.

Aluminum moves the same way: 12 AWG aluminum carries 20 A at 75 °C, but 240.4(D) holds it to 15 A, so a 20 A breaker takes 10 AWG aluminum. The terminal rating of 110.14(C), which splits the answer at larger ratings, makes no difference here.

In NM cable, 334.80 holds 12 AWG copper to the 60 °C column, where it carries 20 A: the same size, at exactly the breaker's rating.

20 A at 120 V and at 240 V

The wire size is the same at either voltage; the distance is not. The same current drops the same number of volts, which is twice the percentage of 120 V as of 240 V. At the full 20 A, single-phase with the conductors at 75 °C, 12 AWG copper reaches 3 % at 47 ft on 120 V and at 93 ft on 240 V.

That 3 % comes from an informational note to 215.2(A), which says feeders sized to keep the drop under it, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. Over 100 ft, staying within it at full load takes 8 AWG copper at 120 V (2.55 %) and 10 AWG at 240 V (2.02 %).

One-way length at which 20 A drops 3 % on copper conductors at 75 °C, single-phase: 12 AWG 47 ft at 120 V and 93 ft at 240 V; 10 AWG 74 ft at 120 V and 148 ft at 240 V; 8 AWG 118 ft at 120 V and 236 ft at 240 V; 6 AWG 187 ft at 120 V and 375 ft at 240 V.120 V240 V0100200300400One-way length to a 3 % drop, ft (copper)12 AWG47 ft93 ft10 AWG74 ft148 ft8 AWG118 ft236 ft6 AWG187 ft375 ftOne-way length at which 20 A drops 3 % on copper conductors at 75 °C, single-phase: 12 AWG 47 ft at 120 V and 93 ft at 240 V; 10 AWG 74 ft at 120 V and 148 ft at 240 V; 8 AWG 118 ft at 120 V and 236 ft at 240 V; 6 AWG 187 ft at 120 V and 375 ft at 240 V.120 V240 V0200400One-way length to a 3 % drop, ft (copper)12 AWG47 ft93 ft10 AWG74 ft148 ft8 AWG118 ft236 ft6 AWG187 ft375 ft
One-way length at which 20 A drops 3 % on copper, at 120 V (gray) and 240 V (copper).

Source: NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).

Copper: one-way length to a 3 % drop, ft

Size120 V240 V
12 AWG47 ft93 ft
10 AWG74 ft148 ft
8 AWG118 ft236 ft
6 AWG187 ft375 ft

Aluminum: one-way length to a 3 % drop, ft

Size120 V240 V
10 AWG45 ft90 ft
8 AWG72 ft143 ft
6 AWG114 ft227 ft
4 AWG181 ft362 ft

A larger wire for distance takes a larger ground wire too (250.122(B)); the wire size calculator sizes both for your length and load.

20 A receptacles

Two NEMA receptacles carry a 20 A rating: the 5-20R at 125 V, with a hot and a neutral, and the 6-20R at 250 V, with two hots. Both take the circuit's 12 AWG copper.

The 20 A receptacles

ReceptacleVoltsWires
5-20R125 V3: one hot, a neutral and a ground
6-20R250 V3: two hots and a ground

What else runs on 20 A

An EV charger set to a 16 A output goes on a 20 A breaker: 625.41 calls for a breaker of at least 125 % of the output. The EV charger wire guide has the makers' tables.

The Hot Spring Jetsetter plug-in hot tub lists a 20 A circuit at 120 V; the hot tub calculator sizes it with the drop over your run.

Questions

Is 12 AWG wire good for 20 A?

Yes: 12 AWG copper carries 20 A at 60 °C, and 240.4(D) allows up to a 20 A breaker on it.

Can I use 10 AWG wire on a 20 A breaker?

Yes. A larger wire is always allowed, and it runs farther: 10 AWG copper reaches 3 % at 74 ft on 120 V, against 47 ft for 12 AWG.

What size wire for a 20 A circuit 100 ft away?

For the full load within 3 %: 8 AWG copper at 120 V, 10 AWG at 240 V. A lighter load can stay on a smaller size.

What size NM cable for 20 A?

12 AWG copper NM cable: it carries 20 A in the 60 °C column 334.80 holds it to.

What size aluminum wire for 20 A?

10 AWG aluminum, with a 10 AWG aluminum ground wire. 12 AWG aluminum is held to 15 A by 240.4(D).

What size ground wire for 20 A?

12 AWG copper or 10 AWG aluminum, from the 20 A row of Table 250.122.

Sources

The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.