Wire Size for 20 Amp Breaker: 12 AWG Copper
By Marko Visic, BSc Physics · Updated · Sources below
A 20 A breaker takes 12 AWG copper or 10 AWG aluminum, whatever the terminals or cable. 14 AWG copper reaches 20 A in the 75 °C column of Table 310.16, but 240.4(D) limits it to a 15 A breaker.
The ground wire is 12 AWG copper or 10 AWG aluminum (Table 250.122). Over 100 ft the full 20 A on 12 AWG drops 6.45 % at 120 V and 3.22 % at 240 V.
Source: NFPA 70 (NEC) 2023, Table 310.16; NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint).
Why 14 AWG can't go on a 20 A breaker
Read from Table 310.16 alone, a 20 A circuit with 75 °C terminations would take 14 AWG copper: it carries 15 A at 60 °C and 20 A at 75 °C. 240.4(D) overrides the table for the small sizes. It holds 14 AWG copper to a 15 A breaker and 12 AWG copper to 20 A, so 12 AWG is the smallest copper a 20 A breaker may protect.
Aluminum moves the same way: 12 AWG aluminum carries 20 A at 75 °C, but 240.4(D) holds it to 15 A, so a 20 A breaker takes 10 AWG aluminum. The terminal rating of 110.14(C), which splits the answer at larger ratings, makes no difference here.
In NM cable, 334.80 holds 12 AWG copper to the 60 °C column, where it carries 20 A: the same size, at exactly the breaker's rating.
20 A at 120 V and at 240 V
The wire size is the same at either voltage; the distance is not. The same current drops the same number of volts, which is twice the percentage of 120 V as of 240 V. At the full 20 A, single-phase with the conductors at 75 °C, 12 AWG copper reaches 3 % at 47 ft on 120 V and at 93 ft on 240 V.
That 3 % comes from an informational note to 215.2(A), which says feeders sized to keep the drop under it, with no more than 5 % on feeder and branch circuits together, will provide reasonable efficiency. It is advice, not a limit. Over 100 ft, staying within it at full load takes 8 AWG copper at 120 V (2.55 %) and 10 AWG at 240 V (2.02 %).
Source: NIST (NBS) Handbooks 100 and 109; 75 °C and aluminum values calculated; NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft).
Copper: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 12 AWG | 47 ft | 93 ft |
| 10 AWG | 74 ft | 148 ft |
| 8 AWG | 118 ft | 236 ft |
| 6 AWG | 187 ft | 375 ft |
Aluminum: one-way length to a 3 % drop, ft
| Size | 120 V | 240 V |
|---|---|---|
| 10 AWG | 45 ft | 90 ft |
| 8 AWG | 72 ft | 143 ft |
| 6 AWG | 114 ft | 227 ft |
| 4 AWG | 181 ft | 362 ft |
A larger wire for distance takes a larger ground wire too (250.122(B)); the wire size calculator sizes both for your length and load.
20 A receptacles
Two NEMA receptacles carry a 20 A rating: the 5-20R at 125 V, with a hot and a neutral, and the 6-20R at 250 V, with two hots. Both take the circuit's 12 AWG copper.
The 20 A receptacles
| Receptacle | Volts | Wires |
|---|---|---|
| 5-20R | 125 V | 3: one hot, a neutral and a ground |
| 6-20R | 250 V | 3: two hots and a ground |
What else runs on 20 A
An EV charger set to a 16 A output goes on a 20 A breaker: 625.41 calls for a breaker of at least 125 % of the output. The EV charger wire guide has the makers' tables.
The Hot Spring Jetsetter plug-in hot tub lists a 20 A circuit at 120 V; the hot tub calculator sizes it with the drop over your run.
Questions
Is 12 AWG wire good for 20 A?
Yes: 12 AWG copper carries 20 A at 60 °C, and 240.4(D) allows up to a 20 A breaker on it.
Can I use 10 AWG wire on a 20 A breaker?
Yes. A larger wire is always allowed, and it runs farther: 10 AWG copper reaches 3 % at 74 ft on 120 V, against 47 ft for 12 AWG.
What size wire for a 20 A circuit 100 ft away?
For the full load within 3 %: 8 AWG copper at 120 V, 10 AWG at 240 V. A lighter load can stay on a smaller size.
What size NM cable for 20 A?
12 AWG copper NM cable: it carries 20 A in the 60 °C column 334.80 holds it to.
What size aluminum wire for 20 A?
10 AWG aluminum, with a 10 AWG aluminum ground wire. 12 AWG aluminum is held to 15 A by 240.4(D).
What size ground wire for 20 A?
12 AWG copper or 10 AWG aluminum, from the 20 A row of Table 250.122.
Sources
- NFPA 70 (NEC) 2023, Table 310.16 — retrieved Oct 2026
- NFPA 70 (NEC), 240.4(D) — NFPA revision record SR-8377 and 2023 text (Leviton reprint) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 110.14(C) (NFPA 2023-cycle Second Draft, SR-7793) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 334.80 and 310.15(E), as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Table 240.6(A), 240.4(B) and 240.4(D) (NFPA 2023-cycle Second Draft; Eaton and Leviton 2023 reprints) — retrieved Oct 2026
- NFPA, Using the Tables in Article 250 of the NEC (fact sheet, 2020), Tables 250.66 and 250.122; Table 250.122 also in NFPA 2026 revision record SR-8360 — retrieved Oct 2026
- Hubbell NEMA configuration chart and Hubbell and Leviton device specifications (NEMA WD 6) — retrieved Nov 2026
- NFPA 70 (NEC) 2023, Article 625, as reprinted in NFPA's 2026-cycle public inputs — retrieved Nov 2026
- Hot Spring, Bullfrog and Marquis pre-delivery/owner manuals (2026) — retrieved Oct 2026
- NFPA 70 (NEC) 2023, 210.19(A), 210.20(A), 215.2(A), 215.3 and 230.42(A) (2023 base text in NFPA Public Inputs and First Draft) — retrieved Oct 2026
- NIST (NBS) Handbooks 100 and 109 — retrieved Oct 2026; 75 °C and aluminum values calculated
The methodology page describes each source and how the values are found. NFPA 70®, National Electrical Code® and NEC® are registered trademarks of the National Fire Protection Association; wiresizes.com is not affiliated with or endorsed by NFPA.